UNC100 Integra/Axiom Light Hardware Manual V1.3 Page
15
of
21
RBH Access Technologies Inc.
Reader Interface
Two standard Wiegand interfaces provide the following connections for typical proximity readers.
Thermal fuse protected power (500ma @13vdc).
Reader Tamper Input(s): Initially, if open it will be ignored, but once a short is connected it will report a
reader tamper alarm whenever the input is opened.
LED and beeper outputs are open collector current limited to 100ma.
Reader Connection
UNC-100 to 12-Volt Reader Connection Diagram
1
For ULC-S319-05
III
compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
1
Reader wire colours may vary for different reader manufactures. Please verify your wiring.