RS485 Port Baud Rate Selection 

 
The controller's serial port baud rate is set with controller DIP switches 6 and 7.  This setting determines 
the speed used to communicate with other controllers.  The baud rate must be the same as the baud rate 
set for all Integra™ units on the network.  The default baud rate is 9600. 
 

Controller Baud Rate Selection 

 

DIP Switch 6 

DIP Switch 7 

Baud Rate  

OFF 

OFF 

9600  

OFF 

ON 

38400  

 

Host Connection 

 
The  controller  is  connected  to  the  local  Ethernet  via  a  static  IP  address  only  [default  address  is 
192.168.168.125
].  To change the IP address of the unit you can either use IP Locator [a utility program 
provided by RBH
] or Telnet.  The communications configuration is set in the Integra™ software under the 
network’s properties under the Comms tab. 

PC to UNC100 Connection 

 

 

 

PC to UNC100 Connection

 

 

 
For ULC-S319-05 

III

 compliance, all wiring into the panel’s cabinet must enter through metal conduit.  

Also be sure to mount the panel in a protected area. 
 

Name  

 

Defaults 

 

Description and notes 

 

Summary of Contents for Integra 32 UNC100

Page 1: ...UNC100 Integra Axiom Light Hardware Manual V1 3 Page 1 of 21 RBH Access Technologies Inc UNC100 Integra Axiom Light Manual 2018 12 17 V1 3 ...

Page 2: ...other product names mentioned herein are the property of their respective owners Use of a term in this book should not be regarded as affecting the validity of any trademark or service mark Disclaimer This book is provided as is without warranty of any kind either express or implied including but not limited to performance merchantability or fitness for any particular purpose Neither RBH Access Te...

Page 3: ... the use of the Power Input Output Moved all cable specs to one location Moved all input specs to one location Moved all output specs to one location Reduced the number of pages 03 19 14 DM 1 1 Minor editing of text 03 24 14 RB 1 2 Changing output voltage from 12V to 12v 14v Changing battery charger spec 07 21 14 DM 1 2 Editing of text Changed graphic Removed relevant information Confirmed correct...

Page 4: ...ings 9 Controller Addressing 9 RS485 Port Baud Rate Selection 10 Host Connection 10 PC to UNC100 Connection 10 Integra Network 11 UNC100 IOC8 Connection 12 RS485 Configuration 14 Reader Interface 15 Reader Connection 15 Outputs 16 Switching Inductive Devices Locks Bells 16 Output Operation 17 General Purpose Output 17 Lock Output 17 Handicap Output 17 Forced Tamper 17 Modem Power Output 17 Supervi...

Page 5: ...ht Hardware Manual V1 3 Page 5 of 21 RBH Access Technologies Inc Door Held Open Warning 20 Door Held Open Alarm 20 Keypad Reader Combination 20 Access Granted 20 Access Denied 20 UNC100 Specification 21 Cable Specification 21 ...

Page 6: ...UNC100 Integra Axiom Light Hardware Manual V1 3 Page 6 of 21 RBH Access Technologies Inc UNC 100 Graphics ...

Page 7: ...ery voltage Reverse Battery Protection A combination of a three ampere diode and a 1 6 amp thermal fuse protects against accidental connection of a battery in the reverse direction Battery Test A battery test cycle is operator initiated or scheduled When initiated the charger is turned off and a 24Ω resistor provides a load to the battery for about ten seconds If during this period the voltage dro...

Page 8: ...Communication The UNC100 has one RS485 port and an Ethernet 10 100 interface Communications from the host computer running Integra software is achieved via the Ethernet interface The UNC100 s RS485 channel may be programmed as either NONE INTEGRA or IOC8 Use the DIP switches to select the baud rate for the Integra network communications as 9600 38400 57600 or 115200 Networks There are two networks...

Page 9: ...ressing Switch 1 Switch 2 Switch 3 Switch 4 Address Off Off Off Off Clear Memory On Off Off Off 1 Off On Off Off 2 On On Off Off 3 Off Off On Off 4 On Off On Off 5 Off On On Off 6 On On On Off 7 Off Off Off On 8 On Off Off On 9 Off On Off On 10 On On Off On 11 Off Off On On 12 On Off On On 13 Off On On On 14 On On On On 15 Use DIP switches 1 2 3 and 4 to select the controller address The address i...

Page 10: ... 6 DIP Switch 7 Baud Rate OFF OFF 9600 OFF ON 38400 Host Connection The controller is connected to the local Ethernet via a static IP address only default address is 192 168 168 125 To change the IP address of the unit you can either use IP Locator a utility program provided by RBH or Telnet The communications configuration is set in the Integra software under the network s properties under the Co...

Page 11: ...RT NUMBER 3003 Alternate port number applies to LAN application RS485 INTEGRA Set the RS485 to INTEGRA in order to connect via RS485 to the PC and other Integra devices Telnet Password password This is a string of up to 10 characters that allows the user access to this program Integra Network URC2000 panels may also be used in place of IRC 2000 panels Note When UNC100 panels are used in conjunctio...

Page 12: ...8 will be configured to connect to IOC8s and will only connect to IOC8s and will not connect to other Integra boards Other Integra boards still be added to the system via a different network i e a different IP address The IOC8 comes in two types One version with eight programable inputs and two open collector outputs The other version with the four programable inputs and four outputs two open coll...

Page 13: ...UNC100 Integra Axiom Light Hardware Manual V1 3 Page 13 of 21 RBH Access Technologies Inc For details on Input I P wiring see page Input I P Circuit Types18 For details on Output O P wiring see page 16 ...

Page 14: ...three possible selections NONE INTG IOC8 Select NONE if the port isn t going to be used INTG is used for PC connection and connection to other Integra panels IOC8 will connect only to IOC8 boards and will not connect to any other Integra panels Note The UNC100 will connect to either other Integra panels or to IOC8 boards not both ...

Page 15: ...t will be ignored but once a short is connected it will report a reader tamper alarm whenever the input is opened LED and beeper outputs are open collector current limited to 100ma Reader Connection UNC 100 to 12 Volt Reader Connection Diagram1 For ULC S319 05 III compliance all wiring into the panel s cabinet must enter through metal conduit Also be sure to mount the panel in a protected area 1 R...

Page 16: ...n Collector 100ma 3 Lock Reader 2 Relay form C 4 Forced Entry Alarm Reader 2 Open Collector 100ma Switching Inductive Devices Locks Bells Exercise caution when switching an inductive load Inductive devices include external relay solenoids bells and door locks All of these devices generate extremely high voltage spikes several thousand volts when applied power is removed Possible disruption of oper...

Page 17: ...t This output is used to drive door operators It turns on in less than one second after the Lock Output is turned on and stays on until the Lock Output is turned off Only designated cardholders will activate this output Forced Tamper The Forced Tamper output turns on if the door is forced open or if a reader tamper is detected This output remains on for as long as the alarm condition exists Modem ...

Page 18: ...15 but not enough to enter the next state an illegal state is reported Input I P Circuit Types The UNC 100 supports seven different input circuit types ranging from no resistor for low security applications to two resistor normally closed circuits where the highest security is required This circuit provides a high degree of supervision and detects both short and open circuit fault conditions Use t...

Page 19: ... Exit RTE input is connected to a push button mounted on the door or to a motion detector mounted near the door A normally open or normally closed button can be used and the circuit type can be programmed from the PC Activating the RTE input will unlock the door The RTE can be disabled by time zone Normally Open One Resistor Loop Resistance State Short Alarm 1k Restore Open Circuit Trouble Normall...

Page 20: ...Buzzer sounds continuously Lockout Alarm The Buzzer beeps rapidly A lockout alarm occurs when a user defined number of Access Denied messages occur These messages can include Invalid Card Number No Access at this Time No Access at this Reader or Invalid PIN Code Door Held Open Warning The Buzzer beeps slowly Door Held Open Alarm The Buzzer sounds continuously Keypad Reader Combination The Buzzer e...

Page 21: ...Time Clock Built in as standard Watch Dog Circuit Built in as standard Board Dimensions H 5 in x W 5 in 14 x 12 cm Operating Temperature 0 to 70C 35 150F Operating Humidity 20 to 85 RH non condensing Cable Specification Circuit Function Cable type Length PC To Controller Ethernet CAT5 communications cable 323 feet 100 meters PC To Controller RS485 Twisted pair shielded stranded 18 to 22 AWG 2000 4...

Reviews: