background image

Location of the openings is the same as in the previ-
ous case - that is, within 12" of the top, and within 12"
of the bottom of the enclosure. If horizontal ducts are
used,  the  area  must  be  doubled  and  the  duct  area
shall  not  be  less  than  the  area  of  the  openings  they
connect, and in no case shall the smallest dimension
be less than 3".

venting Connections

These boilers have built-in drafthoods. Vent piping the
same size or larger than the drafthood outlet is recom-
mended;  however,  when  the  total  vent  height
(drafthood outlet to vent terminal) is at least ten (10)
feet,  the  vent  pipe  size  may  be  reduced  by  one  size
only  as  specified  in  the  latest  edition  of  the  National
Fuel Gas Code, ANSI Z223.1. 

As  much  as  possible,  avoid  long  horizontal  runs  of
vent pipe and too many elbows. If installation requires
horizontal runs, the vent pipe must have a minimum of
1/4 inch per foot rise and should be supported at not
less than five foot intervals. Maximum vent connector
horizontal  length  shall  be  1-1/2  feet  (18  inches)  for
each inch of connector diameter as shown in Table E.

Gas vents supported only by the flashing and extend-
ing  above  the  roof  more  than  five  feet  should  be
securely guyed or braced to withstand snow and wind
loads.  We  recommend  use  of  insulated  vent  pipe
spacer through the roofs and walls.

For  protection  against  rain  or  blockage  by  snow,  the
vent pipe must terminate with a listed vent cap which
complies  with  the  local  codes  or,  in  the  absence  of
such codes, to the latest edition of the National Fuel
Gas Code, ANSI Z223.1.

The discharge opening must be a minimum of two (2)
feet vertically from the roof surface and at least two (2)
feet higher than any part of the building within eight (8)
feet. Vent stack shall be at least five (5) feet in vertical
height above the drafthood outlet. 

The vent cap location shall have a minimum clearance
of four (4) feet horizontally from, and in no case above
or below, unless a 4-foot horizontal distance is main-
tained,  from  electric  meters,  gas  meters,  regulators
and relief equipment.

The weight of the vent stack or chimney must not rest
on the boiler's drafthood. Support must be provided in
compliance with applicable codes. The boiler top and
drafthood must be readily removable for maintenance
and inspection. Vent pipe should be adequately sup-
ported to maintain proper clearances from combustible
construction.

Type "B" double-wall (or equivalent) vent pipe is rec-
ommended. However, single-wall metal vent pipe may
be  used  as  specified  in  the  latest  edition  of  the
National Flue Gas Code ANSI Z223.1.

Model No.

Vent

Connector

Diameter (in.)

Max.

Horizontal

Length (ft)

0042

4

6

0066, 0090

5

7.5

0135

6

9

0180

7

10.5

Table E: Maximum Horizontal Length of Vent Pipe

Lowest  Discharge
       Opening

Listed Cap

Listed Gas Vent

X

12

Roof Pitch is X/12

H - Minimum Height from

      Roof to Lowest
      Discharge Opening

Fig. 4: Minimum Height from Roof to Lowest Discharge

Opening

Refer to Table F for detailed information

9

Summary of Contents for 0042B

Page 1: ... in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service age...

Page 2: ...2 Rev 33 reflects the following Changes to Wiring Diagram for IID On Off on page 20 Wiring Diagram for IID 2 Stage on page 21 Additions None Deletions None ...

Page 3: ...18 WIRING DIAGRAMS 20 SERvICING PROCEDURES 26 General Location of Controls 26 SEqUENCE OF OPERATION 26 Intermittent Ignition Device IID 26 START UP PROCEDURES 27 Lighting the Boiler 27 Filling the System 27 Checking the Circulator 27 Safety Information 27 Operating the Boiler 27 To Turn Off Gas to the Boiler 28 Shut down Procedure 28 Testing the Ignition Safety Shut off 29 Safe Shut down Tests 29 ...

Page 4: ...s on which the heater will operate is the same type as that specified on the heater rating plate DANGER Failure to install the draft hood on indoor installations and properly vent the heater to the outdoors as outlined in the Venting section of this manual can result in unsafe operation of the heater To avoid the risk of fire explosion or asphyxiation from carbon monoxide never operate this heater...

Page 5: ...est edition of the American National Standard ANSI Z21 13 CSA 4 9 Each boiler has been constructed and pressure tested in accordance with the requirements of Section IV of the American Society of Mechanical Engineers Code and factory fire tested These boilers are designed for indoor installation with a built in drafthood and a built in sub base for com bustible flooring Models are equipped with an...

Page 6: ...H 0042 42 35 30 1 in 1 2 in 11 in 5 3 4 in 5 1 2 in 4 in H 0066 66 54 47 1 in 1 2 in 11 in 5 3 4 in 5 3 4 in 5 in H 0090 90 74 64 1 in 1 2 in 11 in 5 3 4 in 5 3 4 in 5 in H 0135 135 109 95 1 1 4 in 1 2 in 18 in 6 1 4 in 6 1 4 in 6 in H 0180 180 148 129 1 1 4 in 1 2 in 18 in 6 1 4 in 8 in 7 in Table A Specifications 6 ...

Page 7: ...addition the boiler shall be installed such that the gas ignition system components are protected from water dripping spraying rain etc during appliance operation and service circulator replacement control replacement etc Clearance Requirements 1 Minimum clearances from combustible materials are listed in Table B below 2 A front clearance of at least 24 is recommended for adequate service of burne...

Page 8: ... found in refrigerants aerosol propellants drycleaning fluids degreasers and paint removers Other harmful elements may come from bleaches air fresheners or mastics Vapors from these types of products can form corrosive acid compounds when burned in a gas flame The resulting acid condensate can damage or substantially reduce the life of the heater It may be necessary to provide outside air directly...

Page 9: ...st terminate with a listed vent cap which complies with the local codes or in the absence of such codes to the latest edition of the National Fuel Gas Code ANSI Z223 1 The discharge opening must be a minimum of two 2 feet vertically from the roof surface and at least two 2 feet higher than any part of the building within eight 8 feet Vent stack shall be at least five 5 feet in vertical height abov...

Page 10: ...Venting of Equipment section of the National Fuel Gas Code ANSI Z223 1 or applicable provisions of the local building codes Common vents Manifolds that connect more than one boiler to a com mon chimney must be sized to handle the combined load Consult available guides for proper sizing of the manifold and the chimney At no time should the area be less than the area of the largest outlet Fig 5 Mini...

Page 11: ...been determined that each appliance remaining connected to the common venting sys tem properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so that the installation conforms with the latest edition of the Nation...

Page 12: ...t system as this will create a haz ardous condition Fig 9 Installing The Vent Damper in Horizontal Vertical Vents Fig 10 D80D General Wiring Diagram Install the vent damper to service only the single appliance for which it is intended If improperly installed a hazardous condition such as an explo sion or carbon monoxide poisoning could result vent Damper Operation For safe efficient operation the ...

Page 13: ... main burners are operating Flair Damper NOTE To place vent damper in the open position to allow burner operation Turn the power off Turn the damper blade to fully open position arrow facing same direction as vent pipe Turn power on SS R2 SS2 ES R SC R1 M 2 3 4 1 JUMPER GV 24 VAC TR HL L L 1 2 120 VAC 60Hz TH 1 Fig 12 System Schematic Abbreviation Description M Damper Motor R Relay ES End Switch S...

Page 14: ...VENT DAMPER 14 ...

Page 15: ...LLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE OVER PRESSURED GAS VALVES ARE NOT COVERED BY WARRANTY The boiler and its gas connections shall be leak tested before placing the appliance in operation Use soapy water for leak test DO NOT use open flame NOTE Do not use teflon tape on gas line pipe thread A flexible sealant suitable for use with Natural and Propane gases is recommended These boilers are...

Page 16: ...ns at the boiler to facilitate servicing The pressure relief valve is mounted on the boiler and must be piped to a drain We recommend that all high points be vented and that purge valves be installed A boiler installed above radiation level must be provided with a low water cutoff device The boiler when used in connection with a refrigera tion system must be installed so that the chilled medium is...

Page 17: ...tlet sensor error While present operation ceases IND Call On Solid Turns on when IND Call short or 0 32 Vac is present Flashing System supply sensor error While present operation continues using boiler outlet sensor WWSD On Solid Turns on when in Outdoor Reset AND WWSD Active AND control in WWSD Flashing Outdoor sensor error While present operation continues with Fixed boiler target of 140 based o...

Page 18: ... The Boiler Pump P1 is controlled by the boiler and is cycled off using a 5 minute fixed purge delay after burner operation has ceased The DIP switch settings are as follows DIP 1 ON ON OFF OFF 2 STAGE DIP 2 ON OUTDOOR RESET DIP 3 ON WWSD 70 F DIP 4 ON 190 F BOIL MAX DIP 5 ON HYDRONIC Hydronic with Outdoor Air Reset For hydronic operation with outdoor air reset the System Supply Sensor S2 is used ...

Page 19: ...Fig 17 Multiple Zones with Circulators Fig 18 Multiple Zones with Circulators and Indirect DHW Tank 19 ...

Page 20: ...Wiring Diagrams 20 ...

Page 21: ...21 ...

Page 22: ... PROVIDED BY OTHERS PROVIDED BY OTHERS Fig 19 Single Zone Taco Valve Fig 20 Dual Zone Taco Valve NOTE Maximum three 3 zone valves per one 1 40 VA transformer 22 ...

Page 23: ... Zone Honeywell Valve NOTE Maximum five 5 zone valves per one 1 40 VA Transformer PROVIDED BY OTHERS Fig 22 System with Three 3 Zone Pumps NOTE Check VA rating of each relay coil Total load must not exceed VA rating of transformer 23 ...

Page 24: ...Fig 23 Power Vent System with Zone Valve Taco 24 ...

Page 25: ...25 Fig 23 Power Vent System with Zone Valve Honeywell ...

Page 26: ... does not light the module will not energize the second main valve and the burners will not light Ignition spark continues only until the timed trial for ignition period ends Then the module goes into safe ty shutdown or lockout Lockout de energizes the first main valve operator and closes the first main pilot valve in the gas control stopping pilot gas flow The ignition control system must be res...

Page 27: ... light the pilot by hand WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life START UP PROCEDURES Lighting the Boiler Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specified in the latest edition of the A...

Page 28: ...9 Honeywell Pilot Shut down Procedure To prevent freeze damage to the heating system it is recommended that the following system shut down procedure be performed 1 Set the room thermostat to OFF or the lowest setting 2 Turn off all electrical switches to the boiler 3 Turn off all gas valves supplying gas to the boiler Refer to operating instruction label on the boiler 4 Shut off the water supply t...

Page 29: ...ould restart Inspection Procedures Burners Clean main burners and air louvers of dust lint and debris Keep boiler area clear and free from com bustibles and flammable liquids Do not obstruct the flow of combustion and ventilation air Make visual check of burner and pilot flame Yellow flame indicates clogging of air openings Lifting or blowing flame indi cates high gas pressure Low flame indicates ...

Page 30: ...ean the tubes remove the heat exchanger ream tubes and immerse heat exchanger in non inhibited de scale solvent Heat Exchanger Removal 1 Shut water gas and electricity off close valves relieve pressure and remove relief valve Remove front inspection panel 2 Remove top holding screws 3 Remove draft diverter lift and remove top and flue collector on stack type models 4 Loosen bolts and disconnect fl...

Page 31: ...uld be replaced with new ones 2 Install in out and return water headers and install header retainer nuts and torque nuts evenly 3 Replace V baffles 4 Install thermostat sensing bulbs in header wells and replace bulb retaining clips 5 Install inlet and return pipes in water headers using pipe thread sealant 6 Install water pressure relief valve flow switch and low water cut off devices if so equipp...

Page 32: ...e to re install Gas valve Adjustment Robertshaw Invensys 7000 Series 2 Stage Gas valve with Solenoid valve 1 Turn the heater off 2 Remove the 3 8 nut or the 10 Torx screw 3 Lift solenoid valve up keeping the wires connect ed to the solenoid valve 4 If only low fire adjustment is needed go to Step 9 5 Using a 3 8 wrench carefully remove the alu minum cap that was under the solenoid valve count of t...

Page 33: ... control cover screws and open control compartment 3 Disconnect wiring to the board 4 Carefully pull out the control board from the nylon pin supports Reverse above procedure to re install Fast Response Temperature Sensor Probe Replacement 1 Shut off electrical power to the boiler 2 Shut off water supply to the boiler and open drain valve to remove water to the sensor probe level 3 Remove control ...

Page 34: ...ompletely filled in with the heater serial number model number etc and shipped to Raypak freight prepaid If determined defective by Raypak and within warran ty the part will be returned in kind or equal substitution freight collect Credit will not be issued RAYPAK INC 2151 Eastman Avenue Oxnard CA 93030 NOTE To supply the correct part it is important that you supply the model number serial number ...

Page 35: ...this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if requested with transportation charges prepaid and all applicable warranty conditions satisfied The replacement part will be warranted for only the unexpired portion of the original warranty Raypak makes no warranty whatsoever on parts manufactured by others but Raypak will apply ...

Page 36: ...36 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A ...

Reviews: