shipped loose. The full open position is appropriate for
most systems, and ensures adequate flow through the
boiler.
If system flow is inadequate, (indicated by excessive
temperature drop through the system) the bypass
valve can be throttled slightly. Care must be taken
against over-throttling which may lead to inadequate
flow through the boiler and boiler harmonics (a hum-
ming sound from the heat exchanger).
If adequate system flow cannot be obtained without
causing harmonics, an additional pump is required.
The factory-mounted circulator will provide adequate
water flow for systems designed at a 20°F temperature
drop, and system pressure drop or head not exceed-
ing that which is shown in Table J.
When the total system head exceeds the available
head pressures, a primary/secondary pumping system
is recommended.
The minimum boiler operating temperature to avoid
condensation must be 105°F. When operating at low
temperature applications, ∆T (temperature rise) must
be 20°F or less.
Propylene glycol solution is commonly used in the
heating system when freeze protection is required.
This will affect the system design and pump perform-
ance. As a rule of thumb, 50% solution of propylene
glycol will require the system flow (gpm) to increase by
14%, and the system head (ft/WC) by 23% in order to
maintain the same heat transfer load.
Systems with multiple zones may require an addition-
al circulator. Consult manufacturer's data for valve
pressure drops. When an indirect water heating sys-
tem is used, it is recommended that a separate
circulator be installed to meet the required flow and
pressure drop conditions of the indirect water heater.
We recommend that the make-up water from the cold
water line have a check valve, gate valve, and feedwa-
ter regulator set at 12 psi. Install unions and gate or
Model No.
System Flow
(gpm)
Max. System
Head (ft/WC)
H-0042
3.5
8.0
H-0066
5.3
8.5
H-0090
7.3
6.5
H-0135
11.0
10.0
H-0180
14.6
7.0
Table J: System Pressure Drop
ball valves at inlet and outlet connections at the boiler
to facilitate servicing.
The pressure relief valve is mounted on the boiler and
must be piped to a drain. We recommend that all high
points be vented and that purge valves be installed. A
boiler installed above radiation level must be provided
with a low water cutoff device.
The boiler, when used in connection with a refrigera-
tion system, must be installed so that the chilled
medium is piped in parallel with the boiler with appro-
priate valves to prevent the chilled medium from
entering the boiler.
The boiler piping system of a hot water heating boiler,
that is connected to heating coils located in air han-
dling units where they may be exposed to refrigerated
air circulation, must be equipped with flow control
valves or other automatic means to prevent gravity cir-
culation of the boiler water during the cooling cycle.
A diaphragm expansion tank should be installed in the
return line. A typical 8"-diameter expansion tank can
be used on models H-0042, and H-0066, and an 11"-
diameter expansion tank can be used on models
H-0090, H-0135 and H-0180. Consult tank manufac-
turer for correct sizing.
Electrical Wiring
The electrical power supply requirement for these boil-
ers is 120 VAC, single-phase, 60 Hz. Field wiring
connections and electrical grounding must comply with
the local codes, or in the absence of local codes, with
the latest edition of the National Electrical Code,
ANSI/NFPA 70.
Provide a separate fused circuit from the main electri-
cal panel to the boiler, and a disconnecting means
within sight of the boiler.
Remove the control box cover and make the power
supply connections in the field wiring compartment.
(See general location of controls drawing on page 26).
The pump is supplied and factory-wired to operate
with the boiler. The "TH" wire leads are for the room
thermostat or zone valve connections.
The room thermostat should be installed in accor-
dance with the manufacturer's instructions. The
thermostat heat anticipator should be set at 1.0
ampere (automatic ignition) and 0.60 ampere (stand-
ing pilot) for single- zone installations. For multi-zone
applications, the heat anticipator setting should be
based on the ampere load in the thermostat circuit.
16
Summary of Contents for 0042B
Page 14: ...VENT DAMPER 14 ...
Page 20: ...Wiring Diagrams 20 ...
Page 21: ...21 ...
Page 24: ...Fig 23 Power Vent System with Zone Valve Taco 24 ...
Page 25: ...25 Fig 23 Power Vent System with Zone Valve Honeywell ...