Distribution Unit
138--118
DISTRIBUTION
UNIT
43
3647.DOC010302
Edition: Sept. 05, 2005
4.2.3.5
Adjustment of NMEA Formats (E10)
The Distribution Unit can provide for each output one of three
different data formats (Course bus, NMEA1 and NMEA2).
Selected format can be recognized by the respective
LED colour.
The content of the course bus format cannot be changed, but
both NMEA formats can be adjusted concerning to telegram--
type and repetition rate.
Procedure for NMEA1:
OPEN
DIP--Schalter B20
B23
B22
Fig.26:
DIP--Switch position to adjust the NMEA1 interface
-- Switch 1 of the DIP--Switch into the upper position.
Number of oper-
ations of push button
B23
Display
Baudrate
Interface
after switching switch 1
(B20) into the upper
position
nME1
NMEA Channel 1
1x
CY. 1
4800Bd
NMEA 1.0sec
2x
CY.10
4800Bd
NMEA 0.1sec
3x
cY.10
9600Bd
NMEA 0.1sec
4x
CY.50
38,4kBd
NMEA 0.02sec
5x
EHdT
HEHDT--Telegram
6x
CHdT
HCHDT--Telegram
7x
IHdG
HCHDG--Telegram
8x
IroT
TIROT--Telegram*
9x
EroT
HEROT--Telegram*
* to adjust the turn rate, see section 4.2.3.7
Summary of Contents for 138-118
Page 5: ...Distribution Unit 138 118 DISTRIBUTION UNIT III 3647 DOC010302 Edition Sept 05 2005 ...
Page 6: ...Distribution Unit 138 118 IV Edition Sept 05 2005 3647 DOC010302 ...
Page 8: ...Distribution Unit 138 118 VI Edition Sept 05 2005 3647 DOC010302 ...
Page 92: ...Distribution Unit 138 118 84 3647 DOC010302 Edition Sept 05 2005 ...
Page 94: ...left blank ...
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......