Thermalert GP Series Operator’s Manual
2.0
THERMALERT GP MONITOR
2.1
SPECIFICATIONS
The following sections cover thermal, operational, electrical, and physical
specifications for each model.
2.1.1 Operational
Input Accuracy:
0-5V input resolution 1
mV
, accuracy ± 2
mV
4-20
mA
input resolution 0.01
mA
, accuracy ± 0.02mA
J, K, E, N, T thermocouple input, ± 0.5% or ± 2°C,
whichever is greater
R, S thermocouple input, ± 0.5% or ± 3°C,
whichever is
greater
Output Accruacy:
4-20
mA
output resolution 0.014
mA
, accuracy ± 0.02mA
J, K, E, N, T thermocouple output, ± 0.5% or ± 2°C,
whichever is greater
R, S thermocouple output, ± 0.5% or ± 4°C,
whichever is
greater
Response Time:
GPR/GPS (system): 300ms
GPM (system): 400ms
All other inputs: 200ms
Display:
4 digit LED
Emissivity:
0.10 to 1.09
(adjustable in 0.01 increments-H001 and H002 only)
Warmup time:
5 seconds
Peak Hold Range: 0 to 998 seconds (999=infinite hold)
Valley Hold Range: 0 to 998 seconds (999=infinite hold)
Averaging Range: 0 to 60 seconds
Fail-safe:
Full or low scale, depending upon system failure
(refer to
Section 3.2)
Setpoint Ranges:
Head Types H001, H002: -18 to 538°C (0 to 1000°F)
Head Type H003: 0 to 500°C (32 to 932°F)
Head Type H004: 0V input setting = low scale, 5V input
setting = high scale
Head Type H005: 4mA input setting = low scale, 20mA
inpute setting = high scale
Head Type H006: scale = input thermocouple range
www.
.com
1.800.561.8187
Summary of Contents for Thermalert GP series
Page 4: ...www com information itm com 1 800 561 8187...
Page 72: ...64 Thermalert GP Series Operator s Manual www com information itm com 1 800 561 8187...
Page 80: ...72 Thermalert GP Series Operator s Manual www com information itm com 1 800 561 8187...
Page 82: ...74 Thermalert GP Series Operator s Manual www com information itm com 1 800 561 8187...
Page 84: ...76 Thermalert GP Series Operator s Manual www com information itm com 1 800 561 8187...