background image

Raytech USA, Inc.

All rights reserved.  No portion may be reproduced without written consent

5

INTRODUCTION

The Raytech three phase voltage system option SM206 (T-Rex) is an optional system accessory
for 3-Phase transformer ratiometer test sets designed by Raytech (ie...TR-Spy, Mark II).

T-Rex was designed to allow Engineers and Test Technicians the ability to test the phase
relationships and actual voltage ratios of transformer windings while applying three phase
voltage.
The system can precisely measure the ratio and angular relationship of transformer phases with

voltage applied to all three phases simultaneously. This is a “real condition” measurement, which

allows greater understanding of how the transformer will operate connected to a 3 phase system.

The T-Rex is especially useful for transformers with:

Phase relationships other than 30

.

Zig Zag windings.

Uncentered neutral points.

Suspected broken, damaged, or missing core laminations.

The T-Rex is contained within a separate yellow case and comes complete to connect to the
Raytech TR-Spy or Mark II, three phase transformer ratiometer.

The system: The T-Rex is a completely new approach in technology. Raytech, an innovative
research and development company, has developed a system for three phase measurements in a
single lightweight package. There are no other systems available to the engineer that allows such
quick and accurate measurements. The system is precision built and extremely accurate.

Ease of use: The T-Rex is an intelligent system option that communicates with the TR-Spy or
Mark II during three phase voltage measurements. No additional programming is required.
The system and option can operate a full 3 phase testing sequence with a single push button operation.
Connect the leads, Select the transformer configuration and vector phasing, Press GO to initiate the
test.

Unique Measuring Technique: This newly designed option incorporates high precision
circuitry for phase resolution measurements. The design utilizes a precision crystal controlled
frequency generator for precise phase measurements.

Operation: The T-Rex applies a preset, three phase voltage on the HIGH windings of the
transformer and measures back through the LOW side of the transformer.
The results are reported on the easy to read liquid crystal display of the TR-Spy or Mark II.

Compact Design: The T-Rex is a lightweight option that comes complete with its own rugged
waterproof Fieldcase.

Simple Maintenance: There is No maintenance required. There is No calibration procedure (No
potentiometers to turn). This is due to the utilization of high precision components in the design.

Advanced Protection: Upon powering on the system initializes itself with a self-calibrating,
circuit checking sequence. If any problems are detected during this initialization period, or
during operation, the operator is immediately notified. The system constantly monitors the
condition of the transformer under test.

Summary of Contents for T-REX

Page 1: ...RAYTECH USA Inc 118 S 2nd Street Perkasie PA 18944 USA Tel 888 4 THE SPY Tel 267 404 2676 Fax 267 404 2685 THREE PHASE VOLTAGE OPTION Model T REX Instruction Manual Ver 2 3...

Page 2: ...HE SPY 484 3779 Tel 267 404 2676 Fax 267 404 2685 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY PRECAUTIONS 3 UNCRATING 4 INTRODUCTION 5 THEORY OF OPERATION 6 Circuitry Design 6 Design Consideration 6...

Page 3: ...nse the input power from the mains plus from 100 to 240 vac 50 60Hz Varying the input voltage will cause the test voltage to vary and result in a higher or lower test voltage than indicated GROUND THE...

Page 4: ...mmediately RAYTECH Toll free service support telephone 1 888 4 THE SPY 484 3779 Note 1 The T Rex Fieldcase is a waterproof design that incorporates a pressure relief valve that should be slightly open...

Page 5: ...h quick and accurate measurements The system is precision built and extremely accurate Ease of use The T Rex is an intelligent system option that communicates with the TR Spy or Mark II during three p...

Page 6: ...ounterclockwise direction With this indication the engineer is able to adjust the vector grouping Phase displacement number on the ratiometer to correspond to the closest relationship in 30 degree inc...

Page 7: ...easurement Parameters PHASE ANGLE 180 Degrees ACCURACY 0 1 Degree RESOLUTION 0 1 Degree Temperature Operating 10 C to 60 C Storage 40 C to 70 C Cable Set 3 Phase cable extension set Interconnect Power...

Page 8: ...e T Rex marked TO TURNS RATIO SPY to the H X connectors on the TR Spy or Mark II 2 Connect the 25 pin Interface cable from the connector located on the middle right side of the T Rex marked TO TR SPY...

Page 9: ...d ratio test refer to the TR Spy or Mark II manual The TR Spy or Mark II will display the correct vector phasing at the completion of the test 2 Select the following screen on the TR Spy or Mark II to...

Page 10: ...t and test Afterwards check the results against the nameplate 2 Greater accuracy of the actual phase displacement can be achieved by selecting a vector grouping as close to the actual phase displaceme...

Page 11: ...nce of credit for such parts and or materials shall be the sole responsibility of purchaser This warranty shall not apply to any accessories parts or materials not manufactured or supplied by RAYTECH...