3.

 

Open the rear compartment to access terminal block. Wire the Mains cable 
into the terminal block. Provision has been made for this and identified as the 

E (Earth), L1 (switched live) and L2 (permanent live) and N (Neutral) terminals. 
There are two pairs of contacts for each of these to facilitate a mains cable that 
can be looped in and out of the unit. The L2 terminals on a standard unit is 
not electrically connected but allows them to be used on the same circuits as

 

emergency floodlights

.

 

4.

 

Installer should earth the unit separately 

 an internal and external earth point 

are provided as standard. 

5.

 

Connect wires to mains supply. 

6.

 

If the unit is opened for any reason, disconnect mains 

 

On emergency 

luminaires there may be more than one mains supply.

 

7.

 

All WARRIOR floodlights have terminal blocks suitable for looping 4mm2 cable, 
only one  cable should be connected to each terminal block connection. 

8.

 

Emergency WARRIOR floodlights may have a single green LED fitted 
adjacent to the incoming cable glands, when illuminated the green LED 

indicates that the emergency system is healthy.

 

9.

 

The battery fuse located in the power supply lid on emergency variants 
is disconnected after final manufacturing testing. When installing the 
floodlight the battery fuse will need to be reconnected and the unit 
charged for 24 hours and then discharged (repeated 3 times) to bring 
the battery up to peak capacity.

 

10.

 

If a 4 core cable is used on emergency luminaires 

 L1, L2, N and E the 

link cable at the front of the terminal block between L1 and L2 should be 
removed.

 

11.

 

During emergency operation the light output and duration will be 
determined by the variant purchased.

 

12.

 

Once wiring is complete replace rear cover. Ensure gasket is located neatly 
in channel and no wires are trapped between cover and body. Tighten cover 
screws to 3Nm. 

13.

 

If carrying out Insulation Resistance tests the normal method of insulation 
testing is to connect Live and Neutral together and test between this point and 
Earth to prevent the risk of damage to the electronic control gear. 

Summary of Contents for WARRIOR 24

Page 1: ...The WARRIOR series of industrial floodlights are specialist devices for use in industrial operating environments The units must be installed in accordance with these instructions and must be installed...

Page 2: ...eads such as PSU cover and external earth points During installation ensure exterior surface of the product is not in direct contact with a dissimilar metal such as galvanised steel If so fit a nylon...

Page 3: ...ation Mounting WARRIOR Unit 1 To meet the requirements of certification a MINIMUM of 2 fixing points must be used the fixing points must be suitable for the conditions of use Raytec recommend using M8...

Page 4: ...epending on the mounting application where possible the cable glands should be kept to the bottom of the floodlight It is very important that the red fibre washers are fitted between the WARRIOR housi...

Page 5: ...UK Europe Tel 44 0 1670 520055 Americas Tel 1 613 270 9990 www raytecled com 5 Typical wiring diagram standard luminaires Typical wiring diagram emergency luminaires...

Page 6: ...ck connection 8 Emergency WARRIOR floodlights may have a single green LED fitted adjacent to the incoming cable glands when illuminated the green LED indicates that the emergency system is healthy 9 T...

Page 7: ...and make the equipment dangerous 3 Isolate the WARRIOR unit from the mains supply and allow to cool before carrying out any maintenance work 4 The unit has 2 independent power supplies in the event t...

Page 8: ...onsumption Emergency variant 71W max 139W max Power Factor 0 95 Mains Frequency 50 60Hz Inrush Current Ipeak 50 40A t 300 s Total Harmonic Distortion 230Vac full load 10 IP Rating IP66 67 Weight Envir...

Page 9: ...put is turned on at the source 4 On emergency variants check fuse to ensure it has not blown 5 If LED panel fails to light is it possible to identify if problem is with LED panel or power supply by sw...

Page 10: ...ing Americas Tel 44 0 1670 520055 sales raytecled com Raytec Ltd Unit 15 Wansbeck Business Park Rotary Parkway Ashington Northumberland NE63 8QW United Kingdom raytecled com Raytec Americas Tel 1 613...

Reviews: