1. SAFETY INSTRUCTIONS 
 

1.

  Read this leaflet carefully before commencing to install the SPARTAN Bulkhead unit 

and retain it for future use. Installation can only be carried out by suitably qualified 
personnel. 
 

2.

  Check the certification to ensure that the mains supply, ambient temperature present and 

‘T’ rating are suitable for the environment the unit is being installed in. 

 

 

3.

  If the SPARTAN unit is to be installed in areas of high vibration, please consult with 

Raytec. 
 

4.

  The SPARTAN unit housing is constructed from marine grade aluminium and toughened 

glass. The end user must ensure that these materials are suitable for the environment 
the SPARTAN unit will be installed in; Zone 1 and Zone 2 Hazardous areas. 

 

 

5.

  Check certification nameplate on side of floodlight to ascertain type of threaded cable 

entry on the luminaire. Select suitably certified ATEX/IEC Ex cable glands and stopper 
plugs, these must be parallel thread, have a minimum of 5 full thread engagement and 
be of a medium/fine tolerance to ISO965-1 and ISO965-3. The cable entry devices 
selected must maintain the IP rating of the luminaire 
 

6.

  The incoming mains cable should not exceed a temperature rise of 20

o

C above the 

ambient conditions; select suitable cable.  

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for SPARTAN SPX Series

Page 1: ...AN series of explosion protected bulkheads are specialist devices certified for use in specific operating environments The units must be installed in accordance with these instructions must be correct...

Page 2: ...nstructed from marine grade aluminium and toughened glass The end user must ensure that these materials are suitable for the environment the SPARTAN unit will be installed in Zone 1 and Zone 2 Hazardo...

Page 3: ...0003 Page 3 Revision B 2 INSTALLATION Mounting SPARTAN Unit 1 To meet the requirements of certification a MINIMUM of 2 fixing points must be used the fixing points must be suitable for the conditions...

Page 4: ...upplied without the mounting brackets fitted these can be found in a polythene bag in the main carton and should be secured to the rear of the unit before installation The bolts packaged along with th...

Page 5: ...ed and the unit charged for 24 hours and then discharged repeated 3 times to bring the battery up to peak capacity 9 If a 4 core cable is used on emergency luminaires L Ls N and E the link cable at th...

Page 6: ...60Hz IP Rating IP66 67 Weight std 5Kg 6Kg Dimensions See previous pages for line diagrams ATEX and IECEx Rating See below PROTECTION CERTIFICATION CML13ATEX3007 or IEC Ex CML14 0001 II 2 GD Ex em IIC...

Page 7: ...t 50 option SPX BL24 W 120120 Spartan Bulkhead 24 LED White Light 120 option SPX BL24 W 3510 Spartan Bulkhead 24 LED White Light 35x10 SPX BL24 W 6025 Spartan Bulkhead 24 LED White Light 60x25 SPX BL2...

Page 8: ...ane Eccleston Chester CH4 9JN Certificate numbers CML13ATEX3007 or IEC Ex CML14 0001 Quality Assurance Notification Sira Equipment Marking II 2 GD Ex em IIC T4 or T5 Gb Ta 52 o C to 55 o C or II 2 GD...