Raypak XTherm Series Installation & Operating Instructions Manual Download Page 13

an additional room(s) of sufficient volume so that the 

com-bined volume of all spaces meets the criteria for 

a room large in comparison (NFGC). The total input of 

all gas utilization equipment installed in the combined 

space shall be considered in making this determina-

tion. 

Each opening

 shall have a minimum free area 

of 1 in.

per 1,000 BTUH (2,225 mm

2

 per kW) of the 

total input rating of all gas utilization equipment in the 

confined space, but not less than 100 in.

2

 (645 cm

2

). 

One opening shall commence within 12 in. (305 mm) 

of the top, and one opening shall commence within 

12 in. (305 mm) of the bottom of the enclosure. The 

minimum dimension of air openings shall be not less 

than 3 in. (76 mm) in any direction.

All Air from Outdoors

The confined space shall communicate with the out-

doors in accordance with one of the methods below. 

The minimum dimension of air openings shall not be 

less than 3 in. (76 mm) in any direction. Where ducts 

are used, they shall be of the same cross-sectional 

area as the net free area of the openings to which they 

connect.

1. 

Two permanent openings

, one commencing 

within 12 in. (305 mm) of the top, and one com-

mencing within 12 in. (305 mm) of the bottom of 

the enclosure, shall be provided. The openings 

shall communicate directly, or by ducts, with the 

outdoors or spaces (crawl or attic) that freely com-

municate with the outdoors.

a.  Where directly communicating with the out-

doors or where communicating to the outdoors 

through vertical ducts, 

each opening 

shall 

have a minimum free area of 1 in.

2

 per 4,000 

BTUH (550 mm

2

 per kW) of total input rating 

of all equipment in the enclosure.

b.  Where communicating with the outdoors 

through horizontal ducts, each opening shall 

have a minimum free area of 1 in.

2

 per 2,000 

BTUH (1,100 mm

2

 per kW) of total input rat-

ing of all equipment in the enclosure. 

2. 

One permanent opening

, commencing within 12 

in. (305 mm) of the top of the enclosure, shall be 

permitted where the equipment has clearances 

of at least 1 in. (25 mm) from the sides and back 

and 6 in. (152 mm) from the front of the appliance. 

The opening shall directly communicate with the 

out-doors or shall communicate through a vertical 

or horizontal duct to the outdoors or spaces that 

freely communicate with the outdoors, and shall 

have a minimum free area of:

13

a.  1 in.

2

 per 3,000 BTUH (740 mm

2

 per kW) of 

the total input rating of all equipment located 

in the enclosure, and

b.  Not less than the sum of the areas of all vent 

connectors in the confined space.

Canadian Installations

1.  Ventilation of the space occupied by the heater 

shall be provided by an opening(s) for ventilation 

air at the highest practical point communicating 

with the outdoors. The total cross-sectional area 

of such an opening(s) shall be at least 10% of the 

area required in 2. and 3. (below), but in no case 

shall the cross-sectional area be less than 10 in.

2

 

(65 cm

2

).

2.  For heaters using a barometric damper in the 

vent system there shall be a permanent air supply 

opening(s) having a cross section area of not less 

than 1 in.

2

 per 7,000 BTUH (320 mm

2

 per kW) 

up to and including 1 million BTUH, plus 1 in.

2

 

per 14,000 BTUH (160 mm

2

 per kW) in excess 

of 1 million BTUH. This opening(s) shall be either 

located at or ducted to a point not more than 18 in. 

(450 mm) nor less than 6 in. (152 mm) above the 

floor level. The duct can also “goose neck” through 

the roof. The duct is preferred to be straight down 

and terminated 18 in. (450 mm) from the floor, but 

not near piping. This air supply opening require-

ment shall be in addition to the air opening for 

ventilation air required in 1. (above).

3.  For heaters not using a barometric damper in the 

vent system, and when air supply is provided by 

natural air flow from outdoors for a power burner 

and there is no draft regulator, drafthood or sim-

ilar flue gas dilution device installed in the same 

space, in addition to the opening for ventilation air 

required in 1., there shall be a permanent air sup-

ply opening(s) having a total cross-sectional area  

of not less than 1 in.

2

 for each 30,000 BTUH (74 

WARNING:

 Care must be taken to ensure that the 

equipment room is not under negative-pressure 

conditions.

CAUTION:

 All combustion air must be drawn from 

the air outside of the building; the mechanical equip-

ment room must communicate directly with the 

outdoors.

WARNING: 

Do not use the “one permanent opening” 

method if the equipment room is under negative-

pressure conditions.

Summary of Contents for XTherm Series

Page 1: ...iquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not to...

Page 2: ...2 Rev 2 reflects the following Changes to Additions Deletions...

Page 3: ...ting 20 Gas Supply 21 Electrical Power Connections 22 Field Wiring Connection 23 Venting 28 Venting Installation Tips 31 Venting Configurations 31 Condensate Managment 36 Outdoor Installation 37 Contr...

Page 4: ...onnect switch may be required to de energize the equipment before servicing CAUTION This heater requires forced water circulation when the burner is operating See tables F and G for flow rate informat...

Page 5: ...rd warranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the upper rear jacket panel of the heater The model number w...

Page 6: ...VC FLUE OUTLET RATING PLATE AIR INLET FILTER GAS SUPPLY CONNECTION 2 1 2 NPT HIGH VOLTAGE ELECTRICAL CONNECTIONS WATER OUTLET 4 GROOVED Component Locations Panels omitted for clarity Fig 1 Component L...

Page 7: ...R FRONT OF HEATER OUTDOOR AIR COVER SHOWN Top panel blower and gas train omitted for clarity Fig 4 Component Locations Top Max Min Flue Intake 2505 2501 200 10 10 3005 3000 240 10 10 3505 3500 280 10...

Page 8: ...o determine the water temperature being delivered turn on a hot water fau cet and place a thermometer in the hot water stream and read the thermometer Time Temperature Relationships in Scalds The foll...

Page 9: ...ground use the hole pattern shown in Fig 5 following local codes Clearances Indoor Installations 9 Heater Side Minimum Clearance from Combustible Surfaces Minimum Service Clearance Floor 0 0 Rear 12...

Page 10: ...12 36 Front Open 30 Access Side 1 24 Opposite Side 1 1 Top Unobstructed 10 Vent Termination 12 12 AIR FILTER ACCESS PANEL BOTH SIDES Fig 7 Outdoor Air Intake When installed according to the listed mi...

Page 11: ...elow or to side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above paved sidewalk o...

Page 12: ...by an opening s for ventilation air within 12 of the highest practical point communicating with the outdoors The total cross sectional area of these openings shall be at least 1 square inch free air...

Page 13: ...th the out doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of 13 a 1 in 2 per 3...

Page 14: ...in such a way that ensures the sensor bulb is in the flow path Raypak Integral Cold Water Protection mm2 per kW of total rated input of the burner s and the location of the opening s shall not inter f...

Page 15: ...w 50 F Continuous operation below 50 F return water temperature may cause operational issues for the unit as well as temperature control insta bility XTherm WH models are equipped with pumps and propo...

Page 16: ...tems have unique levels of operating diversity that must be accounted for in the system design The system should always include adequate system flow in excess of the connected boiler flow for proper o...

Page 17: ...ibrary at www raypak com Min System Flow 120 of Max Boiler Flow Mode 1 Type H Units Only Sys Ret Temp F Model 2505 30F Sys Delta T Model 3005 30F Sys Delta T Model 3505 32F Sys Delta T Model 4005 33F...

Page 18: ...oosted to Target Max when using the Indirect DHW sensor S5 during an indirect call for heat Priority mode toggles off the System Pump P2 when an indirect call for heat is present The Boiler Injection...

Page 19: ...hd Soft 2 4 Med 5 15 Hard 16 25 Pipe max eq ft 190gpm 2 1ft hd Supply Temp F Sys Flow GPM Supply Temp F Sys Flow GPM Supply Temp F Sys Flow GPM Supply Temp F Sys Flow GPM Supply Temp F Sys Flow GPM Su...

Page 20: ...is mandatory for all Pool Applications To complete installation of the heater the system sen sor must be installed in the return water line upstream of the heater The supplied electronic operating co...

Page 21: ...ecommend ed that a union be installed in the gas supply piping DANGER Make sure the gas on which the heater will operate is the same type as specified on the heater s rating plate adjacent to the heat...

Page 22: ...30 45 80 200 400 600 4005 25 35 65 160 300 400 CAUTION For proper operation no more than a 30 drop in gas supply pressure from no load to full load conditions is acceptable Under no circumstances sho...

Page 23: ...nd is proven See Fig 26 Fig 26 Multi meter Check the power source AC 108 VAC Minimum 132 VAC Maximum BC 108 VAC Minimum 132 VAC Maximum AB 216 VAC Minimum 264 VAC Maximum Making the Electrical Connect...

Page 24: ...ration after servicing DANGER SHOCK HAZARD Make sure electrical power to the heater is dis con nected to avoid potential serious injury or damage to components 2 If using an Outdoor Sensor option B 32...

Page 25: ...DHW pump whenever the Indirect DHW call is active The Boiler pump will also be activated based on the Indirect DHW piping configuration setting Consult the VERSA IC manual Cat 5000 72 for additional c...

Page 26: ...anagement system or other auxiliary control signal to the terminals marked 0 10V on the field wiring terminals see Fig 29 Caution should be used to ensure that the 0 10V connection does not create a s...

Page 27: ...5 Connect the Enable Disable wiring to terminals 11 and 12 on the field wiring strip located on the Master boiler See Fig 29 This connection must be provided through dry contacts closure run communic...

Page 28: ...e appliance categorization and suitability of a vent material for application on a Category IV vent system Using improper venting materials can result in personal injury death or property damage CAUTI...

Page 29: ...use a specific vent starter adapter supplied by the vent manufacturer WARNING Use only the materials vent systems and terminations listed in Table P DO NOT mix vent systems of different types or manuf...

Page 30: ...ck vent pipe U S Installations Refer to the latest edition of the National Fuel Gas Code Vent termination requirements are as follows 1 Vent must terminate at least 4 ft below 4 ft hori zontally from...

Page 31: ...er or near elbows Venting Configurations For heaters connected to gas vents or chimneys vent installations shall be in accordance with the NFGC U S or B149 Canada or applicable provisions of local bui...

Page 32: ...braced to withstand snow and wind loads Common Venting The NFGC does not address sizing guidelines for the common venting of multiple Category IV heaters This is covered in the NFGC under Engineered V...

Page 33: ...e gas and flue temperature of 350 F at 100 firing rate mea sured at a test port 12 above the flue collar NOTE Data for 100 firing rate Table P Typical Vent Pressure and Volume of Flue Products Fig 36...

Page 34: ...llations utilize the heater mounted blow er to vent the combustion products to the outdoors Combustion air is taken from inside the room and the vent is installed horizontally through the wall to the...

Page 35: ...t exceed the distances listed in Tables O and Q Each elbow used Subtract 10 ft per elbow Max 4 elbows 1 Requires D 33 Poly vent adaptor limit kit Table Q Category IV Horizontal Vent Horizontal Direct...

Page 36: ...The condensate from the boiler is acidic Its pH is typically between 3 2 and 4 5 Raypak recommends treating the condensate with a Condensate Treatment kit Sales order option Z 12 The Treatment kit is...

Page 37: ...lier Failure to do so may result in control damage heater malfunction property damage personal injury or death WARNING Turn off the power to the heater before installation adjustment or service of any...

Page 38: ...device The optional manual reset high limit is located inside the cabinet on the upper left corner post Access the limit by hinging the control box open to view and make adjustments Standard The fixe...

Page 39: ...pressure is present for proper valve regulator performance The low gas pressure switch automatically shuts down the heater if gas supply drops below the factory setting of 3 0 in WC for natu ral gas...

Page 40: ...supplied to the indirect system Boil OUTLET All Current boiler outlet temperature Boil INLET All Current boiler inlet temperature Boil T All Current temperature difference between boiler outlet and b...

Page 41: ...10 F Differential for the target indirect DHW tank temperature requires IND SENSOR ON 6 F IND SUPPLY H MODE 2 3 OFF 50 F to PIM value Target boiler temperature for the DHW heat exchanger during indire...

Page 42: ...or manual high limit The CFH will resume after the soft lockout fault has been corrected and a 15 min waiting period has expired VENT WALL Not available Not Available LIMIT TEMP ALL Current Outlet Lim...

Page 43: ...to clear INLET LO All Records the lowest boiler outlet temperature Press UP DOWN for 1 sec to clear DELTA T All Captures the highest Delta T Temperature recorded Press UP DOWN buttons for 3 sec to cl...

Page 44: ...degree the outdoor temperature drops the tempera ture of the heating water will increase one degree With the VERSA both ends of the slope are adjust able It is factory set at 70 F water temperature Bo...

Page 45: ...completing heat loss calculations for the building Boiler Design Boil DESIGN The Boil DESIGN temperature is the water temperature required to heat the boiler zones when the outdoor air is as cold as...

Page 46: ...WIRING DIAGRAM Models 2505 4005 46 For a full size drawing visit www raypak com commercial wiring_diagrams...

Page 47: ...neigh bor s telephone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control valve handle Never use tools If...

Page 48: ...e upstream of the heater Start Up 1 Turn power on 2 Turn on the heater wait approximately 15 sec onds after the blower starts the igniter should start to glow observable through the observation port l...

Page 49: ...C 3505 4 1 4 1 2 in WC 4005 1 0 1 9 2 in WC Table W XTherm Air Pressure Settings Table X XTherm Manifold Pressure Settings User Test Set DIP switch 1 on the VERSA IC control to ON Set USER TEST ON in...

Page 50: ...dle valve and open the upstream manual gas valve Make sure that test point A B bleedle valves have been opened so as to allow gas to flow This will bring gas pressure to the second valve seat 5 Open t...

Page 51: ...ow one time operation of the limit and then must be returned to normal operation by turning DIP switch 8 back to the OFF position Power to the unit must then be cycled off then on to return to normal...

Page 52: ...perature or manual reset high limit is not tripped c Enable Disable circuit is closed d Gas is on at the meter and the heater e Incoming dynamic gas pressure to the gas valve is NOT less than 4 0 in W...

Page 53: ...er replace control DELTA T Temperature difference between the inlet and outlet exceeded the set point Check water flow LOW 24VAC Low 24 VAC power Check power supply wiring and transformer BLOW SPEED B...

Page 54: ...ary N A Red LED 6 Flashes N A Hi Limit Fault Red LED 7 Flashes Check for proper water flow Check hi limit setting and outlet sensor Sensor Fault Red LED 8 Flashes Check the VERSA IC Control for fault...

Page 55: ...c tion deterioration or leakage 4 Visually inspect for proper operation of the con densate drain in the venting If leaks are observed repair at once 5 Check air vents for leakage Yearly Beginning Of E...

Page 56: ...l input rate Weekly For low pressure heaters test low water cut off device With heater in pre purge depress the low water cut off test button Appliance should shut off and ignition fault light should...

Page 57: ...at 77 F 5 Check flame signal strength Flame signal should be greater than 1 microampere as measured at the 2 pins on the bottom of the PIM 6 Check firing rate control by checking the manifold pressur...

Page 58: ...ontaminated ar eas this may also experience deterioration Products causing contaminated combustion air spray cans containing chloro fluorocarbons permanent wave solutions chlorinated waxes cleaners ch...

Page 59: ...l horizontally vented gas fueled equip ment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth an...

Page 60: ...utes Vent Size _____________ Stack Height _______ Low Water Cutoff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material ____...

Page 61: ...61...

Page 62: ...62...

Page 63: ...63...

Page 64: ...64...

Page 65: ...65...

Page 66: ...66 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Reviews: