TempTracker mod+ Hybrid Installation and Operation Manual
39
HTC# 059105-00D
BoIler status
The TempTracker mod+ Hybrid boiler status gives immediate access to each boiler stages or modulation.
• ---
Boiler is off due to no call for heat.
• <<A>>
A is the lead boiler in the lead Hybrid group. See "Lead Stages" on page 34.
• <C>
C is the lead boiler in the lag Hybrid group or the lead boiler in Staging or Modulating Boiler Type. See "Lead
• C/E
Extension panel is NOT communicating back to the TempTracker mod+ Hybrid. See "Connecting to the Extensions
and 4-20mA EMS Interface" on page 16.
• mON
All boiler stages are set to ON.
• mOFF
All boiler stages are set to OFF.
display Modulating Boiler status
• 97%
Boiler is modulating at the indicated percentage.
• m95%
Boiler Stage Mode is set to Manual Modulation to the specified percent. See "Mode" on page 41.
• h50%
Boiler is in post purge for 30 seconds.
display staging Boiler status
• High
Boiler highest firing stage is active. The boiler Mode is set to either Auto or Standby.
• Med
Boiler Middle stage on a 3-stage boiler is active. The boiler Mode is set to either Auto or Standby.
• Mhigh
Boiler Middle High stage on a 4-stage boiler is active. The boiler Mode is set to either Auto or Standby.
• Mlow
Boiler Middle Low stage on a 4-stage boiler is active. The boiler Mode is set to either Auto or Standby.
• Low
Boiler lowest firing stage is active. The boiler Mode is set to either Auto or Standby.
OD=
55
o
F SYS=
143
o
F
<<A>>
B
67%
20%
STAGE
◄
►
MENU
STAGE A SETTINGS
Mode
Auto
<Prev Stage>
<Next Stage>
BACK
▲
▼
SELECT
STAGE A SETTINGS
Mode
Auto
Ignition %
1%
Mod Start %
80%
<Prev Stage>
<Next Stage>
Copy Settings
BACK
▲
▼
SELECT
STAGE A MODE
Auto
Standby
Manual
Off
On
BACK
▲
▼
SAVE
STAGE A
- IGNITION POINT -
1%
[
]
BACK
▲
▼
SAVE
STAGE A
MODULATION START
75%
[
]
BACK
▲
▼
SAVE
staging
Modulation
BoIler staGe Menu