Catalog No.: 2000.20P
Effective: 12-1-07
Replaces: 4-1-05
Raytherm - Type H
Hydronic Heating Boilers
Model 133
Indoor Outdoor
Shipping
Weight
Model
No.
Input MBTU
Output MBTU
AFUE
Output MBTU
Lbs. (Approx.)
H-133 136
112 82.7% 109
160
NOTES:
Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce
ratings at the rate of 4% for each 1,000 feet above sea level.
BOILER RATE OF FLOW AND PRESSURE DROP
10
°∆
T 20
°∆
T 30
°∆
T 40
°∆
T
GPM
∆
P FT.
GPM
∆
P FT.
GPM
∆
P FT.
GPM
∆
P FT.
22 14.7 11 3.8 N/A N/A N/A N/A
Raypak, Inc.
2151 Eastman Avenue, Oxnard, CA 93030
(805) 278-5300
Fax (800) 872-9725