26
on-off cycling heater. The valve has a remote capillary
bulb immersed in a well, at the header outlet, to main-
tain a constant outlet water temperature. When
multiple valves are furnished, they can be staged to
give greater flexibility of control. Standard factory set-
ting is at position 5. Consult the dial setting tag
attached to the control for your desired temperature.
See Fig. 22 below.
Fig. 22: Dial Setting Tag
Fig. 23: Mechanical Modulating Valve Location—
Models 0724-1336
Fig. 24: Motorized Gas Valve Location—Model 3001
Limit Controls
High Limit
The heater is equipped with a manual reset High Limit.
Push the reset button and set the limit(s) to 30°F–40°F
above desired operating temperature. Maximum set-
ting is 200°F; other options may be available.
Flow Switch
This dual-purpose control shuts off the heater in case
of pump failure or low water condition and is strongly
recommended. It is mounted and wired in series to the
main gas valve.
Fig. 25: High Limit
NOTE:
The flow switch is a safety device and not a
control. Do not operate the heater with flows less
than the minimums stated in this manual.
Fig. 26: Flow Switch
Summary of Contents for RAYTHERM 133-4001
Page 15: ...15 Fig 9 Indoor Top Installation...
Page 24: ...24 Piping Diagram Type WH Unitemp 80 System...
Page 28: ...28 Location of Controls 0400 WH1 WH2 WH3 0181 LOW NOx WH1...
Page 29: ...29 Location of Controls 0824...
Page 38: ...38 WIRING DIAGRAMS Wiring Diagram W2 WH2 133...
Page 39: ...39 Wiring Diagram WH1 0181 0261...
Page 40: ...40 Wiring Diagram WH1 0331 0401...
Page 41: ...41 Wiring Diagram WH1 0514 0724...
Page 42: ...42 Wiring Diagram WH1 0824 1826...
Page 43: ...43 Wiring Diagram WH1 2100 2500...
Page 44: ...44 Wiring Diagram WH1 3001 4001...
Page 50: ...50...
Page 51: ...51...