FLAME ROLL-OUT SAFETY SWITCH
Atmospheric heaters are equipped with a thermal cutoff
device to prevent flame roll-out in the event the heat
exchanger becomes blocked. This is a "Single-use" type
fusible link or thermal fuse, that must be replaced when
disabled by an over temperature condition, caused by
excessive restriction in the heat exchanger flue passage.
HIGH LIMITS
The heater is equipped with two automatic high limits.
Both are located in the inlet/outlet header. Both are set
to open at 135°F.
NOTE:
An erratic high limit is often characteristic of
internal heat exchanger problem, i.e. scale buildup,
defective bypass. Refer to troubleshooting sections.
HIGH LIMIT REMOVAL
34
PRESSURE SWITCH
The pressure switch, or heater actuator, insures that the
heater operates only when the filter pump is in operation.
It is located on the inlet/outlet header. It is factory set at
1.75 PSI for deck level installations. When the heater is
located below the level of the spa or pool, it may be
necessary to reset the pressure switch to compensate
for the no-flow static head. If it is necessary to reset the
pressure switch, utilize the following procedure:
PRESSURE SWITCH ADJUSTMENT
Adjustment
Knob
NOTE:
If heater is installed outside of the limits shown,
a higher pressure rated (11 psi) switch may be used or a
flow switch mounted and wired adjacent to the heater may
be used in place of the factory mounted pressure switch.
See Parts List for 11 psi pressure switch.
TWO SPEED PUMPS
In some cases, the flow on the low speed is insufficient
to operate the heater. This is apparent when the pressure
switch cannot be further adjusted or if the heater makes
banging noises or goes off on high limit. In these cases,
the pump must be run at high speed when heating the
water.
Fig. # 8152.2
PRESSURE SWITCH
ADJUSTMENT RANGE
Fig. #9440
1. With pump and heater on,
turn adjustment knob
(clockwise) until a click is
heard from the gas valve.
2. Turn adjustment knob
(counter clockwise)
1/4
turn.
3. Turn pump off and on several
times. Heater should shut
off immediately. If it does
not, repeat steps above until
proper adjustments made.
Fig. # 9439
1. Shut off main electrical
power switch to heater.
2. Remove inlet/outlet in-
spection panel.
3. Remove defective high
limit and replace with a
new high limit.
4. Replace inspection
panel.
PILOT SAFETY (Millivolt)
The heaters equipped with the standing pilot (millivolt
system), have pilot generators which act as a safety
device to shut off the flow of gas to the main burners and
the pilot burner in case the pilot flame is extinguished.
The pilot burner must be manually relighted to place the
heater in operation again. Refer to the lighting instruc-
tions provided on the heater label.
PILOT SAFETY (Electronic)
The heater employs a pilot safety which closes the main
gas valve within 8/10ths of a second whenever the pilot
flame is interrupted. Pilot flame is automatically lit when
the device is powered. Unit performs its own safety check
and opens the main valve only after the pilot is proven to
be lit.
Fig. #9438
CAUTION:
Do not operate the heater without the
function of a properly adjusted pressure switch or flow
switch.
Summary of Contents for P-R185B To P-R405B, C-R185B To
Page 2: ......
Page 22: ...22 HEATEXCHANGERPRESSUREDROPTABLES ...
Page 26: ...26 WIRING DIAGRAM MILLIVOLT UNITS MECHANICAL THERMOSTAT ...
Page 27: ...WIRING DIAGRAM IID UNITS atmospheric 27 ...
Page 28: ...WIRING DIAGRAM IID UNITS Low NOx 28 ...
Page 42: ...42 DIGITAL CONTROL LOGIC FLOW CHART ...
Page 44: ...44 ...
Page 46: ...46 ...
Page 47: ...47 ...
Page 48: ...48 ...
Page 49: ......
Page 50: ......
Page 51: ...51 ...