![Raypak HI DELTA HD101 THRU 2342B User Manual Download Page 1](http://html2.mh-extra.com/html/raypak/hi-delta-hd101-thru-2342b/hi-delta-hd101-thru-2342b_user-manual_4091127001.webp)
Project Name / Date
Division 23 52 33.13 - 1
DIVISION 23 52 33.13
FINNED WATER-TUBE BOILERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes gas-fired, copper finned-tube hydronic heating boilers
B. Related
Sections
Specifier Note: Use as needed
1. Building Services Piping – Division 23 21 00
2. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00
3. HVAC Instrumentation and Controls – Division 23 09 00
4. Electrical – Division 23 09 33
1.2 REFERENCES
A. ANSI Z21.13/CSA 4.9
B. ASME, Section IV
C. 2006 UMC, Section 1107.6
D. ANSI/ASHRAE 15-1994, Section 8.13.6
E. National Fuel Gas Code, ANSI Z223.1/NFPA 54
F. I=B=R
G. NEC
1.3 SUBMITTALS
A. Product data sheet (including dimensions, rated capacities, shipping weights, accessories)
B. Wiring
diagram
C. Warranty information
D. Installation and operating instructions
1.4 QUALITY
ASSURANCE
A. Regulatory
Requirements
1. ANSI Z21.13/CSA 4.9
2. Local and national air quality regulations for low NOx (<20 PPM NOx emissions) boilers
B. Certifications
1. CSA
2. ASME H Stamp and National Board Listed
3. ISO
9001
1.5 WARRANTY
A. Limited one-year warranty from date of installation
B. Limited twenty-year thermal shock warranty
C. Limited ten-year closed-system heat exchanger warranty
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. Raypak,
Inc.
1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;
Fax: (800) 872-9725; Web site: www.raypak.com
Catalog No.: 2000.961
Effective: 6-25-09
Replaces: New
Hi Delta SS™, TYPE H - MODELS HD101-HD401
SUGGESTED SPECIFICATIONS