Project Name / Date 

 

3

 

associated with constant pump operation. 

G. Firing 

Mode 

1.  For all models, provide on-off firing control of the gas input to the pool heater. 

H. Pool 

Heater 

Diagnostics 

1.  Provide external LED panel displaying the following pool heater status/faults: 

a.  Power on - Blue 
b.  Call for heat – Amber 
c.  Flow - Green 
d.  Stages 1,2, 3 and 4 – Green 
e.  Fans 1, 2, and 3 proven - Green 
f.  Ignition fault - Red 
g.  Safety fault - Red 

2.  Provide internal circuit board with fault history indicating the following safety faults by LED 

signal: 
a. System enabled 
b. Manual reset hi-limit 
c.  Blocked vent switch 
d.  Air pressure switch 
e. Flow switch 
f. Ignition 

lock-out 

g.  Low gas pressure switch 

Specifier Note:  The following items are options. Delete if not being specified. 

h.  Auto reset high limit 
i.  Low water cut-off 
j.  High gas pressure switch 

3.  A Central Point Wiring board with diagnostic LED’s indicating the status of each relay. 
4.  Provide ignition module indicating the following flash codes by LED signal: 

a.  1 flash – low air pressure 
b.  2 flashes – flame in the combustion chamber w/o CFH 
c.  3 flashes – ignition lock-out (flame failure) 
d.  4 flashes – low hot surface igniter current 
e.  5 flashes – low 24VAC 
f.  6 flashes – internal fault (replace module) 

I. 

Combustion Chamber: The lightweight, high temperature, multi-piece, interlocking ceramic fiber 
combustion chamber liner shall be sealed to reduce standby radiation losses, reducing jacket 
losses and increasing unit efficiency. 

J. Venting 

1.  When routed vertically, the pool heater’s flue material and size shall be in accordance with the 

National Fuel Gas Code, ANSI Z223.1/NFPA54 latest edition (Category I). 

2.  When routed horizontally, the pool heater’s flue material and size shall meet or exceed the 

requirements as specified for Category III in the National Fuel Gas Code, ANSI Z223.1/NFPA 
54 latest edition. 

3.  The pool heater(s) shall be ducted combustion air ready. 

K. Cabinet 

1.  The corrosion-resistant galvanized steel jackets shall be finished with a baked-on epoxy 

powder coat, which is suitable for outdoor installation, applied prior to assembly for complete 
coverage, and shall incorporate louvers in the outer panels to divert air past heated surfaces. 

2.  The pool heater(s), if located on a combustible floor, shall not require a separate combustible 

floor base. 

3.  The pool heater(s) shall have the option of venting the flue products either through the top or 

the back of the unit. 

4.  Combustion air intake shall be on the left side of the cabinet, right side optional. 

Specifier Note: The remaining items in this section are options. Delete those that are not being 

specified. The Low Gas Supply Pressure and FlexGas Manifolds also cannot be used 
on the same boiler. 

Summary of Contents for Finned Water-Tube Pool Heaters 2072B-2342B

Page 1: ...am C Warranty information D Installation and operating instructions 1 4 QUALITY ASSURANCE A Regulatory Requirements 1 ANSI Z21 10 3 CSA 4 3 2 Local and national air quality regulations for low NOx 0 30 PPM NOx emissions pool heaters B Certifications 1 CSA 2 ASME HLW Stamp and National Board Listed 3 ISO 9001 1 5 HEAT EXCHANGER WARRANTY A Limited ten year warranty from date of installation B Limite...

Page 2: ...ports and slots be capable of quiet ignition and extinction without flashback at the orifice and be manufactured from corrosion resistant titanium stabilized stainless steel with low expansion coefficient 2 The burners will be supplied with a fan assisted clean burning and highly efficient fuel air mixture D Pilot Control System 1 The pool heater s shall be equipped with a 100 percent safety shutd...

Page 3: ... The lightweight high temperature multi piece interlocking ceramic fiber combustion chamber liner shall be sealed to reduce standby radiation losses reducing jacket losses and increasing unit efficiency J Venting 1 When routed vertically the pool heater s flue material and size shall be in accordance with the National Fuel Gas Code ANSI Z223 1 NFPA54 latest edition Category I 2 When routed horizon...

Page 4: ...un system shall be completely wired and mounted at the factory 5 The control shall have the following diagnostic LED s a Call for heat b Start up mode c Inlet temperature error d Sensor out of range 6 The controller shall have the capability to add optional alarm contacts P Low Gas Supply Pressure Manifold 1 The pool heater s shall be CSA certified for full input operation down to 4 0 inches W C d...

Page 5: ...rvice clearances and venting guidelines B Manufacturer s representative to verify proper and complete installation 3 2 START UP A Shall be performed by Raypak factory trained personnel B Test during operation and adjust if necessary 1 Safeties 2 2 F 2 Operating Controls 2 3 3 Static and full load gas supply pressure 4 Gas manifold and blower air pressure C Submit copy of start up report to Archite...

Reviews: