FINNED WATER-TUBE POOL HEATERS 

PART 1 - GENERAL 

1.1 SUMMARY 

A.  Section includes gas-fired, copper finned-tube pool heaters. 

B. Related 

Sections 

Specifier Note:  Use as needed 

1.  Building Services Piping – Division 23 21 00 
2.  Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00 
3.  Electrical – Division 23 09 33 

1.2 REFERENCES 

A.  ANSI Z21.10.3/CSA 4.3 

B.  ASME, Section IV 

C.  2006 UMC, Section 1107.6 

D.  ANSI/ASHRAE 15-1994, Section 8.13.6 

E.  National Fuel Gas Code 

F. NEC 

G.  ASME CSD-1, 2006 

1.3 SUBMITTALS 

A.  Product data sheet (including dimensions, rated capacities, shipping weights, accessories) 

B. Wiring 

diagram 

C. Warranty 

information 

D.  Installation and operating instructions 

1.4 QUALITY 

ASSURANCE 

A. Regulatory 

Requirements 

1.  ANSI Z21.10.3/CSA 4.3 
2.  Local and national air quality regulations for low NOx (0-30 PPM NOx emissions) pool heaters  

B. Certifications 

1. CSA 
2.  ASME HLW Stamp and National Board Listed 
3. ISO 

9001 

1.5 HEAT 

EXCHANGER 

WARRANTY 

A.  Limited ten-year warranty from date of installation  

B.  Limited twenty-year thermal shock warranty from date of installation 

PART 2 - PRODUCTS 

2.1 MANUFACTURER 

A. Raypak, 

Inc. 

1.  Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;  

Fax: (800) 872-9725; Web site: www.raypak.com 

2.  Product: Hi Delta

®

 copper finned-tube pool heater(s) 

2.2 POOL 

HEATERS 

A. General 

 

Catalog No.:      6000.62 
Effective: 9-15-08
Replaces: 6-1-08

HI DELTA

®

, TYPE WHP - MODELS 2072B-2342B

SUGGESTED SPECIFICATIONS

 

Summary of Contents for Finned Water-Tube Pool Heaters 2072B-2342B

Page 1: ...am C Warranty information D Installation and operating instructions 1 4 QUALITY ASSURANCE A Regulatory Requirements 1 ANSI Z21 10 3 CSA 4 3 2 Local and national air quality regulations for low NOx 0 30 PPM NOx emissions pool heaters B Certifications 1 CSA 2 ASME HLW Stamp and National Board Listed 3 ISO 9001 1 5 HEAT EXCHANGER WARRANTY A Limited ten year warranty from date of installation B Limite...

Page 2: ...ports and slots be capable of quiet ignition and extinction without flashback at the orifice and be manufactured from corrosion resistant titanium stabilized stainless steel with low expansion coefficient 2 The burners will be supplied with a fan assisted clean burning and highly efficient fuel air mixture D Pilot Control System 1 The pool heater s shall be equipped with a 100 percent safety shutd...

Page 3: ... The lightweight high temperature multi piece interlocking ceramic fiber combustion chamber liner shall be sealed to reduce standby radiation losses reducing jacket losses and increasing unit efficiency J Venting 1 When routed vertically the pool heater s flue material and size shall be in accordance with the National Fuel Gas Code ANSI Z223 1 NFPA54 latest edition Category I 2 When routed horizon...

Page 4: ...un system shall be completely wired and mounted at the factory 5 The control shall have the following diagnostic LED s a Call for heat b Start up mode c Inlet temperature error d Sensor out of range 6 The controller shall have the capability to add optional alarm contacts P Low Gas Supply Pressure Manifold 1 The pool heater s shall be CSA certified for full input operation down to 4 0 inches W C d...

Page 5: ...rvice clearances and venting guidelines B Manufacturer s representative to verify proper and complete installation 3 2 START UP A Shall be performed by Raypak factory trained personnel B Test during operation and adjust if necessary 1 Safeties 2 2 F 2 Operating Controls 2 3 3 Static and full load gas supply pressure 4 Gas manifold and blower air pressure C Submit copy of start up report to Archite...

Reviews: