Division 23 52 33.13 - 4

 

that ensures the boiler will experience inlet temperatures in excess of 105ºF in less than 7-
minutes to avoid damaging condensation. The unit will automatically shut down if the inlet 
temperature is not achieved within the 7-minute time frame. 

2.  The cold water start system shall be configured with a modulating three-way valve that is 

controlled by a system-matched PID controller. The PID controller temperature sensor shall be 
located in the inlet header of the boiler. 

3.  The control shall have a temperature setting dial located on the face of the board. The 

temperature range of the dial shall be 105ºF to 120ºF. The PID Logic shall be capable of 
limiting system overshoot to a maximum of 10ºF on initial start-up or call-for-heat. 

4.  The cold water start system shall be completely wired and mounted at the factory. 
5.  The control shall have the following diagnostic LED’s: 

a.  Call for heat 
b.  Start-up mode 
c.  Inlet temperature error 
d.  Sensor out of range 

6.  The controller shall have the capability to add optional alarm contacts. 

P.  Cold Water Run System 

1.  The boiler(s) shall be configured with a cold water run automatic proportional by-pass system 

that ensures the boiler will experience inlet temperatures in excess of 105ºF in less than 7 
minutes to avoid damaging condensation. The unit will automatically shut down if the inlet 
temperature is not achieved within the 7-minute time frame. 

2.  The cold water run system shall be configured with a variable-speed pump that is controlled by 

a system-matched PID control that injects the correct amount of cold water directly into the 
boiler loop to maintain a minimum inlet temperature. The PID controller temperature sensor 
shall be located in the inlet header of the boiler. 

3.  The control shall have a temperature setting dial located on the face of the board. The 

temperature range of the dial shall be 105ºF to 120ºF. The PID Logic shall be capable of 
limiting system overshoot to a maximum of 10ºF on initial start-up or call-for-heat. 

4.  The cold water start system shall be completely wired and mounted at the factory. 
5.  The control shall have the following diagnostic LED’s: 

a.  Call for heat 
b.  Start-up mode 
c.  Inlet temperature error 
d.  Sensor out of range 

6.  The controller shall have the capability to add optional alarm contacts. 

2.3 

SOURCE QUALITY CONTROL 

A.  The boiler(s) shall be completely assembled, wired, and fire-tested prior to shipment from the 

factory. 

B.  The boiler(s) shall be furnished with the sales order, ASME Manufacturer’s Data Report, 

inspection sheet, wiring diagram, rating plate and Installation and Operating Manual. 

PART 3 - EXECUTION  

3.1 

INSTALLATION 

A.  Must comply with  

1.  Local, state, provincial, and national codes, laws, regulations and ordinances 
2.  National Fuel Gas Code, ASNI Z223.1/NFPA 54 – latest edition 
3.  National Electrical Code, ANSI/NFPA 70 – latest edition 
4.  Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, 

when required 

5.  Canada only: CAN/CSA B149 Installation Code and CSA C22.1 CEC Part I 
6.  Manufacturer’s installation instructions, including required service clearances and venting 

guidelines 

B.  Manufacturer’s representative to verify proper and complete installation. 

Summary of Contents for DELTA LIMITED 989B-2339B

Page 1: ...1 3 SUBMITTALS A Product data sheet including dimensions rated capacities shipping weights accessories B Wiring diagram C Warranty information D Installation and operating instructions 1 4 QUALITY ASS...

Page 2: ...C Burners 1 The tubular burners shall have multiport radial gas orifices punched ports and slots be capable of quiet ignition and extinction without flashback at the orifice and be manufactured from...

Page 3: ...edition Category I 2 When routed horizontally the boiler s flue material and size shall meet or exceed the requirements as specified for Category III in the National Fuel Gas Code ANSI Z223 1 NFPA 54...

Page 4: ...t is controlled by a system matched PID control that injects the correct amount of cold water directly into the boiler loop to maintain a minimum inlet temperature The PID controller temperature senso...

Page 5: ...c and full load gas supply pressure 4 Gas manifold and blower air pressure C Submit copy of start up report to Architect and Engineer 3 3 TRAINING A Provide factory authorized service representative t...

Page 6: ...r Proving Switch Pump Time Delay Relay Status Display Lights Gas Train Manual Gas Shut Off Valve s Combination Valves Low Gas Pressure Switch Manual Firing Stages 2 Stage Model 989B 3 Stage Model 1259...

Page 7: ...6 12 1520 Pump not included Natural Gas Only Dimensions are in inches Rates shown are for natural or propane gas and elevations up to 4 500 feet For installation above 4 500 feet please contact manufa...

Reviews: