Division 23 52 33.13 - 1 

 

 
 

DIVISION 23 52 33.13 

 

FINNED WATER-TUBE BOILERS 

PART 1 - GENERAL 

1.1 

SUMMARY 

A.  Section includes gas-fired, copper finned-tube hydronic heating boilers 

B.  Related Sections 

Specifier Note:  Use as needed 

1.  Building Services Piping – Division 23 21 00 
2.  Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00 
3.  HVAC Instrumentation and Controls – Division 23 09 00 
4.  Electrical – Division 23 09 33 

1.2 

REFERENCES 

A.  ANSI Z21.13/CSA 4.9 

B.  ASME, Section IV 

C.  2006 UMC, Section 1107.6 

D.  ANSI/ASHRAE 15-1994, Section 8.13.6 

E.  National Fuel Gas Code ANSI Z223.1/NFPA 54 

F.  I=B=R 

G.  NEC 

H.  ASME CSD-1, 2006 

1.3 

SUBMITTALS 

A.  Product data sheet (including dimensions, rated capacities, shipping weights, accessories) 

B.  Wiring diagram 

C.  Warranty information 

D.  Installation and operating instructions 

1.4 

QUALITY ASSURANCE 

A.  Regulatory Requirements 

1.  ANSI Z21.13/CSA 4.9 
2.  Local and national air quality regulations for low NOx (0-30 PPM NOx emissions) boilers  

B.  Certifications 

1.  CSA 
2.  ASME H Stamp and National Board Listed 
3.  ISO 9001 

1.5 

WARRANTY 

A.  Limited one-year warranty from date of installation  

B.  Limited twenty-year thermal shock warranty 

C.  Limited ten-year closed-system heat exchanger warranty 

PART 2 - PRODUCTS 

2.1 

MANUFACTURER 

A.  Raypak, Inc. 

1.  Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;  

 

 

DELTA LIMITED™, TYPE H - MODELS 989B-2339B 

SUGGESTED SPECIFICATIONS

 

Catalog No.:  2000.98A 
Effective: 

11-15-08 

Replaces: 

9-15-02 

Summary of Contents for DELTA LIMITED 989B-2339B

Page 1: ...1 3 SUBMITTALS A Product data sheet including dimensions rated capacities shipping weights accessories B Wiring diagram C Warranty information D Installation and operating instructions 1 4 QUALITY ASS...

Page 2: ...C Burners 1 The tubular burners shall have multiport radial gas orifices punched ports and slots be capable of quiet ignition and extinction without flashback at the orifice and be manufactured from...

Page 3: ...edition Category I 2 When routed horizontally the boiler s flue material and size shall meet or exceed the requirements as specified for Category III in the National Fuel Gas Code ANSI Z223 1 NFPA 54...

Page 4: ...t is controlled by a system matched PID control that injects the correct amount of cold water directly into the boiler loop to maintain a minimum inlet temperature The PID controller temperature senso...

Page 5: ...c and full load gas supply pressure 4 Gas manifold and blower air pressure C Submit copy of start up report to Architect and Engineer 3 3 TRAINING A Provide factory authorized service representative t...

Page 6: ...r Proving Switch Pump Time Delay Relay Status Display Lights Gas Train Manual Gas Shut Off Valve s Combination Valves Low Gas Pressure Switch Manual Firing Stages 2 Stage Model 989B 3 Stage Model 1259...

Page 7: ...6 12 1520 Pump not included Natural Gas Only Dimensions are in inches Rates shown are for natural or propane gas and elevations up to 4 500 feet For installation above 4 500 feet please contact manufa...

Reviews: