AUTOMATIC CHLORINATORS AND CHEMICAL FEED-
ERS

All chemicals must be introduced and completely

diluted into the pool or spa water before being circulated
through the heater.  Do not place chlorine tablets or
bromine sticks in the skimmer.  High chemical concen-
trations will result when the pump is not running (i.e.
overnight).

Chlorinators must feed downstream of the heater and

have an anti-siphoning device to prevent chemical back-
up into the heater when the pump is shut off.

NOTE:

 High chemical concentrates from feeders and

chlorinators that are out of adjustment will cause very
rapid corrosion to the heat exchanger in the heaters.
Such damage is not covered under the warranty.

UNITHERM GOVERNOR OPERATION

The patented Unitherm Governor is a thermostatic

mixing valve specifically designed to maintain constant
heater internal temperature between 105°F to 115°F
despite continually changing flow rated from the filter and
changing pool temperatures.  This narrow range is
needed to prevent damaging condensation on the burn-
ers which will occur if the heater runs for any length of
time below 100°F.  It is also needed to inhibit scale
formation in the tubes by maintaining temperatures well
below accelerated scaling temperatures.

EXTERNAL AUXILIARY BYPASS VALVE
(Where Required)

An auxiliary bypass valve should be used when flow

rates exceed 115 GPM (usually a high performance
pump size larger than two HP will exceed this flow rate).
This valve is required to complement the function of the
automatic bypass valve, particularly when starting the
heater in winter or early spring when the spa or pool
temperature is down below 55°F.  It also serves to
eliminate needless pressure drop through the heat and
accompanying reduction in the flow rate to the spa jets,
etcetera.

FROM

TO

HEATER

HEATER

TO POOL

          FROM
           POOL

Fig. # 8150.0

AUXILIARY BYPASS VALVE ADJUSTMENT

13

To set bypass: with clean filter, adjustment is made

by feeling the inlet and outlet pipes at the heater.  Outlet
pipes should be slightly warmer than inlet and comfortable
to the touch.  If pipe is hot, close bypass; if cold open
bypass.

The heater is also equipped with a manual bypass

built into the header.  This is in addition to the automatic
bypass valve.  This may be used with flow rates up to 120
GPM and  adjusted as below.

NOTE:  

Sooting or liming caused by improper bypass

adjustment voids the warranty

BYPASS VALVE

         INLET/OUTLET

HEADER

Fig. # 8223.0

MANUAL BYPASS ADJUSTMENT

   OPEN POSITION

CLOSED POSITION

Fig. # 8222.0

PRESSURE RELIEF VALVE INSTALLATION

To conform to local building codes, it may be

necessary to install a pressure relief valve.  A 3/4”
pressure relief valve having a capacity equal to BTU/HR
output of the model to be installed is recommended for this
appliance.

A 3/4” NPT connection is provided in the inlet/outlet

header for installation of a pressure relief valve.  The valve
shall be installed in a vertical position.

    PRESSURE RELIEF VALVE

          INLET/OUTLET HEADER

INLET

OUTLET

Fig. # 8223.0

Summary of Contents for 514-824

Page 1: ...on may result causing property damage personal injury or death WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performe...

Page 2: ... NOT EXCEED 5 PPM Occasional chemical shock dosing of the poolm or spa water should not damage the heater providing the water is balanced Automaticchemicaldosingdevicesandsaltchlorinatorsareusuallymoreefficient in heated water unless controlled they can lead to excessive chlorine level which can damage your heater Furtheradviceshouldobtainedfromyourpoolorspabuilder accreditedpoolshop or chemical s...

Page 3: ...RECEIVING EQUIPMENT 7 SECTION2 GENERALSPECIFICATION 7 SECTION3 INSTALLATIONINSTRUCTIONS 8 Base Installation 8 Clearances 9 CombustionAir 9 VentingConnections Outdoor 11 Gas Supply Connections 12 Plumbing for Water Connections 14 Electrical Wiring 15 WiringDiagrams 19 SECTION 4 SERVICING INSTRUCTIONS 19 General Location of Controls 19 Controls Adjustments Replacements 23 SECTION 5 TROUBLESHOOTING G...

Page 4: ...IONS SYSTEMS A This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand B BEFORE OPERATING smell all around the appli ance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch...

Page 5: ...POSITION THE ON POSITION GAS INLET Fig 8220 0 7 Wait fire 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 8 For Models 514 724 Turn gas control knob counter clockwise to On For Model 824 Turn main gas shut off and pilot shut off valves clockwise to on 9...

Page 6: ... is suggested for young children 2 Drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could lead to unconsciousness and subsequently result in drowning 3 Pregnant Women Beware Soaking in water over 102 F 39 C can cause fetal damage during the first three months of pregnancy resulting in the birth of a braindamaged or deformed child Preg nant women should...

Page 7: ...om the carton and if it is damaged report the damage to the carrier immediately On occasion we ship some items loose Be sure that you receive the number of packages indicated on the Bill of Lading When ordering parts you must specify model and serial number of heater When ordering under warranty conditions you must also specify date of installation Raypak recommends that this manual be reviewed th...

Page 8: ... from or one 1 foot above any door window or gravity inlet to a building The top surface of the heater shall be at least three 3 feet above any forced air inlet or intake ducts located within ten 10 feet horizontally Installation must be in accordance with local codes or in the absence of local codes with the latest edition of the National Fuel Gas Code ANSI Z223 1 and National Electrical Code ANS...

Page 9: ...624 627 824 825 b All air from outdoors When air is supplied directly from outside of build ing each opening shall valve a minimum net free square inches as noted Model Square Inches 514 128 624 157 724 182 824 207 VENTING CONNECTIONS VENTTERMINAL Outdoor STEP 1 Loweroutdoor Stackless topontounit Positiontopso it is centered on unit from side to side and front to rear STEP 2 Tighten the 4 screws S...

Page 10: ... while the other appliances remain ing connected to the common venting system are not in operation a Seal any unused openings in the common ventingsystem b Visually inspect the venting system for proper size and horizontal pitch and deter mine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition c Insofar as is practical close all build...

Page 11: ...gas connections shall be leak tested before placing the appliance in operation Use soapy water for leak test Do NOT use open flame NOTE Do not use teflon tape on gas line pipe thread A flexible sealant is recommended A minimum of 7 W C and a maximum of 14 W C upstream pressure under load and no load conditions must be provided for natural gas or a minimum of 12 W C and a maximum of 14 for propane ...

Page 12: ...CAUTION NEVER install PVC directly into heater Four feet of copper or high temperature pipe and two elbows are required between the heater and the PVC connections Fig 8129 0 12 Whenlocalcodespermittheuseoflessthanfourfeet hightemperaturepipingortwoelbows provisionsshould be made to always shut the heater off a minimum of 15 minutes prior to pump shut down in order to carry away residualheatandprev...

Page 13: ...formance pump size larger than two HP will exceed this flow rate This valve is required to complement the function of the automatic bypass valve particularly when starting the heater in winter or early spring when the spa or pool temperature is down below 55 F It also serves to eliminate needless pressure drop through the heat and accompanying reduction in the flow rate to the spa jets etcetera FR...

Page 14: ...a dual voltage trans former for 120V or 240V input power hookup 14 S8600 IGNITION CONTROL Fig 8929 1 For 120 V input power to the unit connect the black wire to the L1 or hot leg of the power supply Connect the white wire to the L2 or neutral leg of the power supply Attach the wire nut to the red wire There should be no connection to the red wire for 120V operation Fig 9240 For 240 V input power t...

Page 15: ...15 ...

Page 16: ...16 151965 824 825 000 BTUH ...

Page 17: ...17 152141 514 724 512 000 THRU 726 000 BTUH 5 ...

Page 18: ...18 152142 824 825 000 BTUH 6 ...

Page 19: ...MECHANICAL THERMOSTAT Fig 8060 1 TYPICALCOMFORTABLE SPATEMPERATURE RANGE KNOBSTOP RING SET SCREW TYPICAL COMFORTABLE POOL TEMPERATURE RANGE Fig 8104 0 KNOBSTOPADJUSTMENT If desired a higher setting of the thermostat can be obtainedbyadjustingtheknobstopringonthedialplate Loosenthesetscrew adjusttheknobstopforthehigher desiredtemperaturesettingandretightenthesetscrew 19 SECTION4 SERVICINGINSRUCTION...

Page 20: ...eheater makes banging noises In these cases the pump must be run at high speed when heating the water CAUTION Do not operate the heater without the function of a properly adjusted pressure switch HIGHLIMITS Theheaterisequippedwithtwoautomatichighlimits Set to operate at 135 F and 140 F NOTE An erratic high limit is often characteristic of internal heat exchanger problem i e scale build up U G oper...

Page 21: ...on panels 4 Loosen bolts and disconnect flange nuts on inlet outlet header loosen union s at gas pipe and slide boiler away from piping until stud clear the header 5 Remove heat exchanger corner brackets 6 Remove combustion chamber slips at the four corners of the heat exchanger 7 Lift heat exchanger straight up using caution not to damage refractory 8 Reverse above procedure to reinstall TUBECLEA...

Page 22: ...idthinningoutanypart of the tube wall excessively over 015 Use same procedure at the opposite end of the tube Apply line pressure test and re roll if necessary before reassembly of the heater DESOOTINGPROCEDURE CAUTION SOOT IS COMBUSTIBLE EXERCISE EXTREME CARE Sootwillclogareasbetweenfinsandcauseeventual tube failure Any sign of soot at the base of the burners or around the outer jacket indicates ...

Page 23: ... Lowgaspressure Insects or debris clogging burnerintakeports Broken refractory caused by shippingdamageorimpropercombustion Excessive sooting of heat exchanger Calculatetemperaturein hr Filternotrunninglongenough Dirtyfilter Gas line or meter undersized SOLUTION Check movement by putting in hot water 110 F or higher If no movement replace Locate the restriction and remove Flush system and clean Re...

Page 24: ...ce heat exchanger and maintain chemistry properly See pressure switch adjustment Replacerefractory Determine cause of sooting and correct Bypassingtoomuchwater U G notfunctioning Overacid Overacid Heaterrunningafterpumpshutsoff Refractorydamage Sootedheater Liming Leaking at well Leaking at heat exchanger Gasketbrittleandleaking overheated 24 ...

Page 25: ...ff pilot gas if pilot fails to light To reset interrupt power to heater Intermittent Pilot System TROUBLESHOOTING HONEYWELL S8600 NOTE Before troubleshooting familiarize yourself with the startup and checkout procedure Check line voltage power low voltage transformer limit controller thermostat control ler and wiring Pull ignition lead and check spark at module SparkOkay YES Check ignition cable g...

Page 26: ... under standard companywarrantiesmustbeproperlytaggedwithRAYPAK returnpartstag completelyfilledinwiththeheaterserial number model number etc and shipped to the Com pany freight prepaid If determined defective by the Company and within warranty the part will be returned in kind or equal substitution freight collect Credit will not be issued Raypak Inc 31111 Agoura Road Westlake Village CA 91361 ...

Page 27: ...this page is empty ...

Page 28: ...28 PILOTASSEMBLY ELECTRONICIGNITION PILOTASSEMBLY STANDINGPILOT Fig 9293 Fig 9294 ...

Page 29: ...29 ...

Page 30: ...30 ...

Page 31: ......

Page 32: ...RAYPAK INC 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 FAX 800 872 9725 Litho in U S A www raypak com ...

Reviews: