8
3.5. Maintenance
A
A
WARNING:
Check the heater for possible rodent nests
after long periods of non-use.
To be followed one month after start-up and then semi-
annually.
1. Inspect top of heater and drafthood for soot, a
sticky black substance around finned tubes and “V”
baffles, and open flue gas passageways. Any visible
soot should be cleaned for proper operation.
A
A
CAUTION:
Soot may be combustible. Wet sooted
surfaces completely prior to cleaning. Do not use steel
wire brush.
2. Clean main burners and pilot burner of dust and lint.
3. Inspect and operate all controls, gas valve and
pressure relief valve (if equipped).
4. Make visual check of the burner and pilot flames.
Yellow flame means restriction of the air openings.
Lifting or blowing flame indicates high gas pressure.
Low flame means low gas pressure. Should the
latter occur, shut the heater off and contact your gas
supplier or qualified service agency.
5. On indoor heaters, clean room intake openings to
ensure adequate flow of combustion and ventilation
air.
A
A
CAUTION:
Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
heater and void the warranty.
6. Keep area around heater clear and free from
combustible materials, gasoline and other flammable
and corrosive vapors and liquids.
If Heater Will Not Fire:
If you have no electrical power, it may be that your “circuit
breaker” has tripped. Try re-setting it.
If you have electrical power but the heater will not fire
check the following or see Troubleshooting section:
1. The time clock must be in the “ON” position.
2. Your pump strainer basket may be full. If so remove
debris.
3. Your filter may be dirty. If so, backwash or clean
filter. (To tell if your filter is dirty, look to see if the
filter pressure will be higher than usual).
4. The pump may have lost its prime and be running
dry. Check the pressure on the filter. If there is no
pressure; then you are not moving water (or your
gauge is broken). Try to get the pump to run at its
normal flow rate.
5. Check flow switch operation and paddles (“F” paddle
on 268 or “A” paddle on 408).
3.6. Cold Weather Operation
3.6.1. Important Freeze Information
MODERATE CLIMATE: Heater operation can continue
during short-term cold spells. When temperatures are
between 0° (-17°C) and 32°F (0°C), flow (continuous pump
operation) must be maintained.
A
A
CAUTION:
Do not use the heater to maintain water
temperatures just above freezing or for freeze protection.
When heater is used during freezing weather, care must
be taken to avoid freeze-ups. Continuous pump operation
is a must. Additional protection may be required. The
heater is not warranted against freeze-ups.
COLD CLIMATE: Prolonged operation with water
temperatures below 50°F (10°C) is not recommended.
When starting the heater with water temperatures below
50°F (10°C), operate the heater continuously until higher
temperatures are reached. Operating the heater for
prolonged periods with pool water below 50°F (10°C)
can seriously damage the heater, and is not covered by
the warranty. For cold climate areas, please follow the
winterizing procedures listed.
3.6.2. Winterizing the Pool and Spa
Heater
Heaters installed outdoors in freezing climate areas
may be shut down for the winter. Observe the following
procedure for winterizing the heater:
1. Turn off gas valve, manual gas valve, and electrical
supply to the heater.
2. Open drain valve located on the inlet/outlet header,
(under water pipes). Remove the heat exchanger
inspection panel on the side opposite water piping
to gain access to the drain plug on the return header.
Open drain plug on return header.
DRAIN
Figure 2. Return Header Drain Valve