27
TRANSFORMER WIRING
120 VAC WIRING
For 120 VAC input power to the unit, connect the black wire to the “L1” or hot leg of the power supply. Connect
the white wire to the “Ret” or neutral leg of the power supply. Attach the wire nut to the red wire.
There should
be no connection to the red wire for 120 VAC operation.
For Lo NOx pool heaters attach a wire nut to each
red wire independently.
240 VAC WIRING
For 240 VAC input power to the unit, connect the black wire to the “L1” or hot leg of the power supply. Connect
the red wire to the “L2” or second hot leg of the power supply. Attach the wire nut to the white wire.
There should
be no connection to the white wire for 240 VAC operation.
For Lo NOx pool heaters attach a wire nut to
each white wire independently.
Heater must be electrically grounded and bonded in accordance with local codes, or, in the absence of local
codes, with the latest edition of the National Electrical Code, ANSI/NFPA 70. (Canada - Canadian Electrical
Code, CSA C22.1, Part 1 and Part 2.)
120V ATMOSPHERIC HEATER
120V LOW NOx HEATER
SUPPLY
SIDE
SUPPLY
SIDE
RETURN
or
NEUTRAL
RETURN
or
NEUTRAL
HEATER
4 WIRES
HEATER
7 WIRES
GROUND
L1
L1
HOT
RED
RED
RED
BLACK
BLACK
BLACK
BLACK
HOT
BLACK
GREEN
GREEN
GREEN
GREEN
WHITE
WHITE
WHITE
WHITE
WHITE
240V ATMOSPHERIC HEATER
240V LOW NOx HEATER
HEATER
4 WIRES
HEATER
7 WIRES
GROUND
L1
L2
L1
L2
RED
RED
BLACK
BLACK
BLACK
HOT
RED
RED
RED
HOT
HOT
BLACK
HOT
BLACK
GREEN
GREEN
GREEN
GREEN
WHITE
WHITE
WHITE
SUPPLY
SIDE
SUPPLY
SIDE
NOTE:
Input power to the heater (120 or 240 VAC) can be supplied from the load (pump) side of time clock or
directly from the GFCI power source.
It is preferred that full-time power be supplied to the heater from the
GFCI power source, and that the heater be controlled by the fireman’s switch connection or using a two
or three-wire remote. See pages 36-38.
If using a switched GFCI power source, the heater could display false
service indicators on the display panel if the pump is turned off.
NOTE:
If the transformer’s primary side is wired for 120 VAC and 240 VAC is applied, damage to the transformer
and PC board may result. Such damages are not covered under manufacturer’s limited warranty.
WARNING:
DO NOT attempt to operate the heater at 208 VAC.
Summary of Contents for 336A
Page 28: ...28 WIRING DIAGRAM MILLIVOLT MECHANICAL THERMOSTAT...
Page 29: ...29 WIRING DIAGRAM ATMOSPHERIC...
Page 30: ...30 WIRING DIAGRAM LO NOx...
Page 48: ...48 19 M 20 M 22 M 24 M 23 M 21 M 22 M ATMOSPHERIC HEATERS...
Page 49: ...49 16 M 17 M 19 M 21 M 20 M 18 M 19 M LO NOx HEATERS...
Page 50: ...50...
Page 52: ...52 ATMOSPHERIC HEATERS...
Page 53: ...53 ATMOSPHERIC HEATERS...
Page 54: ...54 LO NOx HEATERS...
Page 55: ...55 LO NOx HEATERS...