Catalog No.: 2000.61C
Effective: 12-01-10
Replaces: 07-10-09
XTherm – Type H
Models 1005-2005
Model
Dimensions (in)
MBTUH
Model
(H7-)
Input
Output
B
Height
D
E
F
G*
NPT
K
Flue
Ø
L
M
N
C/A
Ø
P
R
Y
Ship
Weight
(Lbs.)
1005
999
959
55-1/8
45
47-1/8
36-1/2
1-1/4
6
40-1/16
11-1/2
6
47-1/8
8-1/16
6-1/16
1065
1505
1500
1440
67-1/8
57
59-1/16
38-1/2
1-1/4
8
52-1/16
12-5/8
8
59-1/8
8-3/16
6-1/16
1234
2005
1999
1919
81-1/8
71
71-3/16
38-1/2
2
8
64-1/16
12-5/8
8
73-1/8
8-3/16
6-1/4
1461
Note: Ratings shown are for elevations up to 4,500 feet. For installations at elevations
above 4,500 feet, please consult the factory for additional instructions.
* For Propane Gas, all models are 1” NPT
Model 1005
Model 1505
Model 2005
Minimum Pipe Size
2
Minimum Pipe Size
2
Minimum Pipe Size
2
System
Return
Temp
(ºF)
Supply
Temp
1
(ºF)
<80’ eq
80-200’ eq
Supply
Temp
1
(ºF)
<80’ eq
80-200’ eq
Supply
Temp
1
(ºF)
<80’ eq
80-200’ eq
60
138
2” NPT
2-1/2” NPT
147
2” NPT
2-1/2” NPT
154
2” NPT
2-1/2” NPT
80
138
2” NPT
2-1/2” NPT
147
2” NPT
2-1/2” NPT
154
2-1/2” NPT
3” NPT
100
138
2-1/2” NPT
3” NPT
147
2-1/2” NPT
3” NPT
154
2-1/2” NPT
3” NPT
120
145
2-1/2” NPT
3” NPT
158
2-1/2” NPT
3” NPT
170
2-1/2” NPT
3” NPT
140
165
2-1/2” NPT
3” NPT
178
2-1/2” NPT
3” NPT
190
2-1/2” NPT
3” NPT
160
185
2-1/2” NPT
3” NPT
198
2-1/2” NPT
3” NPT
210
2-1/2” NPT
3” NPT
1
– Approximate high fire heater outlet temperature based on the standard heater pump and recommended connecting pipe size.
2
– Minimum pipe size based on total equivalent feet of supply and return piping between the system loop and heater.
NOTE: Primary/Secondary plumbing
is mandatory for proper operation.
CLEARANCES (in.)
Front
Rear
Right
Left
Top
Floor
Vent
Certified Minimum
24
12
1
1
0
0
1
Minimum Service
24
36
24
1
10
N/A
N/A
Amp Draw**
Model
Boiler †
Accessories †
1005
12**
10
1505
12**
14
2005
18**
17
† Separate power connections are
factory supplied and separate supply
breakers must be field supplied.
** Current draw is for boiler only (Supply
breaker must have delayed trip).