Catalog No.:  2000.61C  

Effective:  12-01-10 

Replaces:  07-10-09

 

XTherm – Type H 

Models 1005-2005 

Model            

 

 
 

 

 
 
 

 
 
 

 

Dimensions (in) 

MBTUH 

Model 

(H7-) 

Input 

Output 

Height 

G* 

NPT 

Flue 

Ø 

N  

C/A 

Ø 

Ship 

Weight 

(Lbs.) 

1005 

999 

959 

55-1/8 

45 

47-1/8 

36-1/2 

1-1/4 

40-1/16 

11-1/2 

47-1/8 

8-1/16 

6-1/16 

1065 

1505 

1500 

1440 

67-1/8 

57 

59-1/16 

38-1/2 

1-1/4 

52-1/16 

12-5/8 

59-1/8 

8-3/16 

6-1/16 

1234 

2005 

1999 

1919 

81-1/8 

71 

71-3/16 

38-1/2 

64-1/16 

12-5/8 

73-1/8 

8-3/16 

6-1/4 

1461 

 

Note:  Ratings shown are for elevations up to 4,500 feet. For installations at elevations  

above 4,500 feet, please consult the factory for additional instructions. 

*  For Propane Gas, all models are 1” NPT 

 

 

 

Model 1005 

Model 1505 

Model 2005 

Minimum Pipe Size

2

 

Minimum Pipe Size

2

 

Minimum Pipe Size

2

 

System 

Return 

Temp 

(ºF) 

Supply 

Temp

1

 (ºF) 

<80’ eq 

80-200’ eq 

Supply 

Temp

1

 (ºF) 

<80’ eq

 

80-200’ eq

 

Supply 

Temp

1

 (ºF) 

<80’ eq

 

80-200’ eq

 

60 

138 

2” NPT 

2-1/2” NPT 

147 

2” NPT 

2-1/2” NPT 

154 

2” NPT 

2-1/2” NPT 

80 

138 

2” NPT 

2-1/2” NPT 

147 

2” NPT 

2-1/2” NPT 

154 

2-1/2” NPT 

3” NPT 

100 

138 

2-1/2” NPT 

3” NPT 

147 

2-1/2” NPT 

3” NPT 

154 

2-1/2” NPT 

3” NPT 

120 

145 

2-1/2” NPT 

3” NPT 

158 

2-1/2” NPT 

3” NPT 

170 

2-1/2” NPT 

3” NPT 

140 

165 

2-1/2” NPT 

3” NPT 

178 

2-1/2” NPT 

3” NPT 

190 

2-1/2” NPT 

3” NPT 

160 

185 

2-1/2” NPT 

3” NPT 

198 

2-1/2” NPT 

3” NPT 

210 

2-1/2” NPT 

3” NPT 

1

 – Approximate high fire heater outlet temperature based on the standard heater pump and recommended connecting pipe size. 

2

 – Minimum pipe size based on total equivalent feet of supply and return piping between the system loop and heater. 

NOTE:  Primary/Secondary plumbing 
is mandatory for proper operation. 

CLEARANCES (in.) 

 

 

Front 

Rear 

Right 

Left 

Top 

Floor 

Vent 

Certified Minimum 

24 

12 

Minimum Service 

24 

36 

24 

10 

N/A 

N/A 

 

Amp Draw** 

Model 

Boiler † 

Accessories † 

1005 

12** 

10 

1505 

12** 

14 

2005 

18** 

17 

† Separate power connections are 
factory supplied and separate supply 
breakers must be field supplied. 
** Current draw is for boiler only (Supply 
breaker must have delayed trip).

 