background image

10

COLD WATER RUN

Purpose

The Cold Water Run system utilizes a variable-speed
pump to inject the proper amount of water from the
main system loop into the boiler to maintain the opti-
mum inlet temperature. This approach allows the full
capacity of the boiler to be utilized to meet the system
load, while at the same time continuously maintaining
the optimum inlet water temperature to prevent con-
densation.

Typical Cold Water Run
Applications

Swimming pools.

Snow melting.

Low temperature radiant panel.

Water source heat pumps.

Any system with steady state return water temper-
ature below 105°F. 

CWR vs. CWS

Cold water start is for transient cold water opera-
tion.

Cold water run is for continuous operation below
105°F system return temperature.

Cold water start maintains design flow rate at sys-
tem design temperature but reduces bolier flow
rate during heavy by-pass operation.

Cold water run maintains constant design flow rate
in the boiler.

INSTALLATION

Before arriving at the job site to begin the installation,
it's important to first inspect the system and determine
what materials you will need.  Some parts are includ-
ed with the controller while others you will need to
provide. 

Installation Codes

Installations must be in accordance with local, state,
provincial, and national codes, laws, regulations and
ordinances.  In the absence of local codes, installa-
tions must be in accordance with the latest editions of
the:

National Fuel Gas Code, ANSI Z223.1/NFPA 54

National Electrical Code, ANSI/NFPA 70

For Canada only: CAN/CGA B149.1 installation
Code (B149.1) and CSA C22.1 C.E.C. Part 1 and
Part 2

Mounting the Control Box

The control box should be mounted on the side of the
heater to which the system piping and pump assem-
blies are to be attached. The controller should be
mounted so as to provide maximum support by using
the mounting holes provided on the base of the con-
troller to the side center brace on the heater. You will
need to drill mounting holes and holes through the
heater side panel for the routing of wiring and the sen-
sor. A template is supplied for field-installed kits to
locate the control box properly.

Indoor and Outdoor
Installations

The cold water run control panel is rated for indoor use
only. Do not mount or install the control panel in areas
where dripping, flooding, rain, snow or spraying water
may come in contact with the enclosure. If the injection
pump is located outdoors, the optional outdoor cover
must be installed according to the instructions in the
following section. For outdoor installations mount the
control panel indoors and route the wiring to the appro-
priate connection points. Wire length is not to exceed
25 feet in any one direction. Contact your local sales
representative for further information.

NOTE:

The heater should not be located in an area

where possible water leakage will result in damage
to the area adjacent to the heater or to the structure.
When such locations cannot be avoided,  it  is  rec-
ommended that a suitable drain pan, with adequate
drainage, be installed under the heater. The pan
must not restrict combustion air flow.

CAUTION:

Remote mounted controller must be

installed within 25 feet of the heater.

Summary of Contents for 1000.57A

Page 1: ...nd kept adjacent to the heater or in another safe place for future reference Catalog No 1000 57A Effective 02 28 07 Replaces 02 24 06 P N 241275 Rev 2 INSTALLATION AND OPERATING INSTRUCTIONS COLD WATE...

Page 2: ...2...

Page 3: ...tream and read the thermometer 3 NOTE When this water heater is supplying general purpose hot water for use by individuals a thermo statically controlled mixing valve for reducing point of use water t...

Page 4: ...e sensor A tem plate is supplied for field installed kits to locate the control box properly Attaching the Temperature Sensor Avoid routing wiring on or near other electrical wires conduit motors spar...

Page 5: ...minates GREEN 2 START UP MODE LED on PCB illuminates YEL LOW Before 7 minutes it should go out if boiler inlet temperature is approaching the set point tem perature 3 The ACTUATOR should be in the ful...

Page 6: ...erminal 2 of terminal block 3 to the NO contacts of the DPST relay located in the cold start control panel 14 After the two second delay on the cold start circuit board pin MC outputs a 24 VAC signal...

Page 7: ...ater IF VALVE DOES NOT MOVE Check for voltage out at TB2 1 Should be a 1VDC to 10VDC output to the actuator valve If no voltage is present check for volt age at TB2 3 there should be a 12VDC signal If...

Page 8: ...8 Cold Water Start Troubleshooting Guide...

Page 9: ...9 Wiring Diagram...

Page 10: ...ode ANSI NFPA 70 For Canada only CAN CGA B149 1 installation Code B149 1 and CSA C22 1 C E C Part 1 and Part 2 Mounting the Control Box The control box should be mounted on the side of the heater to w...

Page 11: ...1532 120 22 12 4 62 42 1911 1 3hp 1632 5 6 1802 120 25 13 68 45 1911 1 3hp 1632 5 6 2002 132 26 19 74 46 1935 3 4hp 1634 6 1 2072 132 27 19 75 47 1935 3 4hp 1634 6 1 2342 132 30 21 4 80 50 1935 3 4hp...

Page 12: ...the system 4 Allow heater to cool down before attempting work In order to install the pump cover you will need to rotate the pump body so that the electrical box is point ing downward as outlined in t...

Page 13: ...olts secur ing the pump body in place 4 You will now be able to install the pump cover See Fig 18 and 19 Fig 15 Reposition the pump body so that the electrical box points downward Fig 16 Place the cov...

Page 14: ...14 Typical Boiler Piping Hi Delta shown...

Page 15: ...signal to terminal AL0 of the Hitachi inverter 9 The AL0 relay closes and outputs a 24 VAC signal to the coil of the DPST relay located in the cold run control panel 10 The DPST relay coil energizes a...

Page 16: ...16 Wiring Diagram...

Page 17: ...ornia 1 800 627 2975 Inside California NO Verify 120VAC from TB1 on the heater and correct YES Does TB1 of cold run controller have 120 VAC Heater is in standby mode Correct Wiring YES NO NO YES YES N...

Page 18: ...18 ILLUSTRATED PARTS LISTS Cold Water Start...

Page 19: ...A 007353F PUMP WATER BR 2 1 2 FLANGE 3 4 HP 007348F 007348F PUMP WATER CI 2 1 2 FLANGE 3 4 HP 007354F 007354F PUMP WATER BR 2 1 2 FLANGE 1 HP 007348F 007348F PUMP WATER CI 2 1 2 FLANGE 1 HP 007354F 00...

Page 20: ...20 Cold Water Run...

Page 21: ...2 7 0 0 P H 4 1 E G N A L F 2 I C R E T A W P M U P PUMP WATER BR 2 1 2 FLANGE 3 4 HP 007348F 007348F PUMP WATER CI 2 1 2 FLANGE 3 4 HP 007354F 007354F F 1 5 3 7 0 0 F 1 5 3 7 0 0 P H 1 E G N A L F 2...

Page 22: ...raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Raypak Canada Limited 2805 Slough St Mississauga Ontario Canada L4T 1G2 905 677 7999 Fax 905 677 8036 Litho in U...

Reviews: