It is commonly known that prolonged internal condensation will dramatically shorten the life of standard boilers and
water heaters. While Raypak boilers and water heaters can operate without harmful condensation at lower inlet water
temperatures than the competition, there are still applications that require reliable protection against harmful conden-
sation caused by frequent, extended, cold water start-ups. Raypak’s 

Cold Water Start

protection system utilizes a pro-

portional three-way valve to bypass water from the boiler outlet to the inlet during start-up, when the system return
water temperature is below the minimum acceptable level.

COLD WATER START

Raypak’s Cold Water Start system:

Continuously monitors and adjusts inlet water temperature to prevent condensation 

Regulates minimum inlet water temperature during system start-up

Shuts down boiler if the minimum inlet water temperature is not achieved

Eliminates job site set-up with proprietary self-tuning controller and system-matched components

Utilizes proportional three-way valve to achieve bypass

Allows high-temperature system operation without cycling on high-limit 

Activates alarm if shutdown occurs (option)

C

Co

om

mm

me

errcciia

all  H

Hy

yd

drro

on

niicc  H

He

ea

attiin

ng

g

Office Buildings    •

Factories/Warehouses    •

Greenhouses    •

D

Do

om

me

essttiicc  H

Ho

ott  W

Wa

atte

err  S

Su

up

pp

plly

y

Restaurants    •

Weekend Shut-down    •

(e.g. 6-day/week shopping center)

Dump Loads    •

87% Hot Water Supply Boiler    •

Intermittent Industrial Process    •

MIN INLET

TEMP SETTING

START-UP

TEMP 

BLENDED BOILER
INLET TEMP

SYSTEM RETURN NOW AT
OR ABOVE MINIMUM INLET
SETTING. BYPASS CLOSED,
FULL SYSTEM FLOW

STABLE SYSTEM TEMP

SYSTEM RE

TURN

TEMPERA

TURE

TIME

A

A P

P P

P L

L II C

C A

A T

T II O

O N

N S

S

Boiler Start-Up Cycle

Summary of Contents for 1000 .19C

Page 1: ......

Page 2: ...es minimum inlet water temperature during system start up Shuts down boiler if the minimum inlet water temperature is not achieved Eliminates job site set up with proprietary self tuning controller and system matched components Utilizes proportional three way valve to achieve bypass Allows high temperature system operation without cycling on high limit Activates alarm if shutdown occurs option C C...

Page 3: ...ature to prevent condensation COLD WATER RUN Raypak s Cold Water Run system Continuously monitors and adjusts inlet water temperature to prevent condensation Regulates minimum inlet water temperature regardless of system temperature Shuts down boiler if the minimum inlet water temperature is not achieved Protects boiler from constant low return water temperatures with its proprietary self tuning c...

Page 4: ...LER PUMP 3 WAY VALVE BOILER Cold Water Start J Box Assembly Typical Cold Start Plumbing Pictorial Not to Scale FROM SYSTEM TO SYSTEM SYSTEM PUMP BOILER PUMP VARIABLE SPEED INJECTOR PUMP BOILER Cold Water Run J Box Assembly Typical Cold RunPlumbing Pictorial Not to Scale ...

Page 5: ...ICAL BOILER PIPING COLD WATER RUN Items required for cold water operation are shown Other standard system components have been omitted for clarity Items required for cold water operation are shown Other standard system components have been omitted for clarity ...

Page 6: ...2 NPT 100 150 5 2 3 001 4 000 4 Flange 152 220 4 8 4 001 6 000 4 Flange 254 330 3 9 6 001 8 000 4 Flange 327 440 4 2 Notes 1 Maximum of 4 boilers per system 2 Many variables can impact the proper valve sizing for multiple boilers This sizing is provided as a guide When in doubt consult the factory 3 Multi unit system ALWAYS shipped loose Not available mounted 4 4 flanges bolts and gaskets supplied...

Reviews: