      inverter.

3.5.2  Connection to PV string (DC input)

Figure 3-16 Connect the PV string

Disassembly the inverter from the Grid:

5) The cables are inserted into the terminal accord-

ing to the wire sequence (L1/L2/L3/N/PE), so that 

the insulating terminal is flush with the surface of the 

terminal, and the crimping screw torque is 

2.0±0.1N•m.

6) Insert the main part of AC connector into the

terminal and hear a "click" sound.

Figure 3-7

Figure 3-8

1) Use a screwdriver to press against the unlocked 

position and hold the wire nut and pull it back to 

complete the separation of the male and female 

ends.

2) The female end connector is separated from the 

inverter end connector.

Figure 3-9

9) Complete the installation.

Figure 3-11

Figure 3-10

Figure 3-12

Figure 3-13

3) Hold the unlocking nut with one hand and

rotate it in the direction of the mark, and turn the nut 

in the opposite direction.

4) Use a screwdriver to peel off the positions (both 

sides) indicated by the red circle to complete the 

disassembly.

Figure 3-14

Figure 3-15

7)  Use a wrench to tighten the nut until there is 

a ‘click’ sound.

8)  Press the female end of the wire onto the male

end of the inverter until you hear a ‘click’. 

Telephone  :  +44  (0)  1245  428500        

Email : [email protected]

13

Summary of Contents for RI-ENERGYFLOW 3P Series

Page 1: ...428500 Email sales rayleigh com 3P SERIES 25 Solar Inverter User Manual RI ENERGYFLOW 3P SERIES 25 www rayleigh com Rayleigh Instruments Limited Raytel House Cutlers Road South Woodham Ferrers Chelmsf...

Page 2: ......

Page 3: ...Startingtheinverter 4 Userinterface 4 1 Ledandkey 4 2 LCDdisplay 4 3 Factorysetting 4 4 Settinglanguage 4 6 Self TestinaccordancewithCEI0 21 AppliestoItalyonly 5 Warranty 5 1 Warrantyclaimprocedure 5...

Page 4: ...1 Introduction This manual describes solar inverters RI ENERGYFLOW 3P SERIES25 10KW 15KW 17KW 20KW 25KW These inverters are transformerless based inverter 1 3 Important safety information 1 1 Introduc...

Page 5: ...erter Before installation Installation Disconnecting the inverter Operating the inverter should be used Functional safety parameters considered in each individual case Telephone 44 0 1245 428500 Email...

Page 6: ...dimensions and electrical terminals of RI ENERGYFLOW 3P SERIES 25 10KW 15KW 17KW 20KW 25KW 382 00 510 00 185 00 Figure 2 2 wiring diagram of the inverter system 2 2 Electrical system design 1 EMC SO...

Page 7: ...0 1000 165 2 2 2 30A 30A 17000 W 27 1 A 37500 W 2 2 30A 1 30A 25000 W 40 A RI ENERGYFLOW 3P SERIES 25 DC Input Data AC Output Data 17KW 25KW 15KW 20KW 10KW Protection Anti island Protection Over heat...

Page 8: ...unication Relative Humidity Protection Grades Warranty EMC 506 386 185mm LCD 25 60 0 2W Transformerless 1 The maximum DC input current for RI ENERGYFLOW 3P SERIES 25 25KW is 37 5A Fan 5 7 10 years Fan...

Page 9: ...Korea China W Brazil PEA PEA W MEA MEA W Tunisia Tunisia W 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 Description National Regional Gr...

Page 10: ...nectors for 17KW 20KW 25KW INVERTER 1 MOUNTING PANEL 1 PV CONNECTOR PV CONNECTOR SCREW 1 EXPANSION TUBE 4 QIG 1 QC PASS 1 FACTORY REPORT 1 AC connector 1 GPRS WIFI OPT Before installation and maintena...

Page 11: ...ent 3 3 Installation position 1 Figure 3 3 Distance required of Invertors Figure 3 2 installation position No sun No rain No snow Sunlight Rain Snow 300mm 300mm 500mm 500mm 300mm Telephone 44 0 1245 4...

Page 12: ...Drill 4 x 10mm holes in the wall as dimensions below Step 2 Affix the mounting bracket to the wall using the 4 expansion bolts supplied in the accessories bag Step 3 Hang the inverter on the wall moun...

Page 13: ...t by using a crimping pliers 3 Separate the AC connector 4 Pass the crimped AC wire into the AC connector Figure 3 6 No Description Remark A B C D Protective layer diameter 15 25mm Length of stripped...

Page 14: ...ear a click sound Figure 3 7 Figure 3 8 1 Use a screwdriver to press against the unlocked position and hold the wire nut and pull it back to complete the separation of the male and female ends 2 The f...

Page 15: ...ing nut with one hand and rotate it in the direction of the mark and turn the nut in the opposite direction 4 Use a screwdriver to peel off the positions both sides indicated by the red circle to comp...

Page 16: ...r successful connection information such as power generation and running state of the inverter can be viewed via the App on the phone For details please refer to the module user manual The block diagr...

Page 17: ...NO or a normal close contact COM NC The relay is initially at the NC terminal and it will trip to another contact when a fault occurs Use LED indicators or other equipment to indicate whether the inv...

Page 18: ...and their polarity 3 Any unused terminals are covered 1 Close the DC and AC circuit breakers 2 If the solar panels are providing enough energy the power module will function and the LCD panel will be...

Page 19: ...t Set Country Factory Set Mac Addr xx Set PF Pac W Clear Events Pac W Factory Settings Pac W Clear E total Pac W PFX xxx Pac W Set MacAddr Pac W English Factory Set Portuguese Factory Set VDE4105 Fact...

Page 20: ...4 4 Setting language 4 5 Setting modbus address 4 6 Self Test in accordance with CEI 0 21 Applies to Italy only Auto Test from screen 1 2 3 CEI 0 21 AutoTest Italy Pac 10000W 4 5 18...

Page 21: ...5V 232 6V 223 8V 187ms 195 5V 213 0V 223 5V 1485ms 34 5V 36 2V 226 4V 190ms 50 20Hz 49 88Hz 49 98Hz 95ms 1 2 3 4 5 6 7 49 80Hz 49 88Hz 50 03Hz 88ms 51 50Hz 51 39Hz 50 04Hz 93ms 47 50Hz 48 01Hz 50 01Hz...

Page 22: ...100 50 01 92 Pass Fmin 49 8 100 49 94 92 Pass 51 5 100 51 02 98 Pass Fmin 47 50 100 50 03 89 Pass Read Once the product has been installed and operational it is paramount to register the product to in...

Page 23: ...tions Fault OFR Fault UFR LCD display Clearable Fault Fault 1 1 restarts 2 1 Grid is not connected 3 4 1 2 cooler environment 1 2 call local service 6 Troubleshooting and Maintenance 6 1 Troubleshooti...

Page 24: ...EEPROM_R Fail SciCommLose BusFault CPU ADFault PLLFault AutoTestFail FanError LCD display Permanent Fault Fault 6 2 Maintenance NOTICE Otherwise Rayleigh Instruments shall not be held liable for any d...

Page 25: ...ary Check if the air inlet if necessary the metal enclosure Method System clean Fans Cable entry Electrical Connection Item Once a year Once a year Maintenance Instruction Fan Maintenance broken fans...

Page 26: ...3 3 3 3 3 3 3 3 2 2 2 2 4 4 4 3 24...

Page 27: ...Telephone 44 0 1245 428500 Email sales rayleigh com 25...

Page 28: ...ou have any further technical questions about our product please contact us Head Office Rayleigh Instruments Limited Raytel House Cutlers Road South Woodham Ferrers Chelmsford Essex CM3 5WA United Kin...

Reviews: