E-100-L Installation Instructions

8

Troubleshooting Guide

Problem

Troubleshooting steps

Light is dim or off.

1.  Check that light voltage rating matches supply voltage for heat-tracing circuit. Supply voltage lower or 

higher than light rating will cause malfunctions.

2.  Check that heat-tracing circuit is energized. Although the circuit breaker is on, control devices such as 

thermostats may switch heating cable off.

3.  Following electrical safety procedures, disconnect supply voltage, unscrew light from end seal base and 

check that crimp connections to heating cable bus wires are tight and not crossed or shorted. Loose 

 connections or shorts will cause malfunctions.

4.  With circuit off, attach volt meter leads to crimps. Energize circuit and measure voltage at light. Use the 

following table to determine whether the voltage measured is within the acceptable range.

Catalog name 

Nominal voltage 

Acceptable voltage range

E-100-L1 

100–120 Vac 

58–132 Vac

E-100-L2 

200–277 Vac 

145–305 Vac

• 

If voltage at light is in acceptable range and connections are good

, the light may be defective or 

 damaged. Replace light.

• 

If there is no voltage at the light

, there may be breaks in the heating cable between the power 

 connection and the end seal. Check for splice or tee connections that may be left open.

• 

If voltage at light is above specified limits

, the light may be off. Voltages above specified range can damage 

light. Replace light with correct version for line supply voltage or adjust supply voltage accordingly.

• 

If voltage at light is present but below specified limits

, the light may be dim or off. The following table 

lists typical causes for low voltages and possible solutions.

Cause

Solution

Supply voltage at start of circuit is low (light is 

designed to work with supply voltages within 10% 

of nominal).

Increase power wire gauge size to reduce volt-

age drop between panel and heating cable power 

 connection.

Heating cable length is too long (light is designed 

to work with published maximum  circuit lengths).

Split heating cable into multiple circuits.  Shorten 

length of heating cable.

Heating cable is started under very cold  conditions 

(heating-cable voltage drop is very high for first 

minutes of very cold start-up).

Wait for heating cable to warm up. Voltage at light 

will increase.

Heating cable controller is reducing voltage (light 

may not work with controllers that phase fire to 

reduce line voltage).

Turn off phase firing function in heating cable 

 controller.

Problem

Troubleshooting steps

Cap cannot be tightened 

completely.

1.  Check that heating cable is installed and stripped correctly. The top of the insulated parallel crimps should 

be 2 3/8 in (60 mm), or less, above the top of the plastic strain relief in the stand.

2.  Check that core sealer is positioned properly. The end of the core sealer must be flush against the plastic 

strain relief in the stand.

3.  Check that the threads on the light and stand are clean. The connection wires between the heating cable 

and the light should not be caught in stand threads.

©

2009

Tyco

Thermal

Controls

LLC

PN

863747-000

H55923

12/09

Worldwide Headquarters

Tyco Thermal Controls

307 Constitution Drive

Menlo Park, CA 94025-1164

USA

Tel  (800) 545-6258

Fax  (800) 527-5703

[email protected]

www.tycothermal.com

Important: 

All information, including illustrations, is believed to be reliable. Users, however, should  independently evaluate the 

suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or 

completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls’ only obligations are those 

in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls 

or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of 

the   product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make 

changes–without notification to Buyer–to processing or materials that do not affect compliance with any applicable specification. 

Tyco is a trademark of Tyco Thermal Controls LLC or its affiliates.

Summary of Contents for E-100-L Series

Page 1: ...aged or improperly installed and to comply with the requirements of Tyco Thermal Controls agency certifications and national electrical codes ground fault equipment protection must be used Arcing may not be stopped by conventional circuit breakers Component approvals and performance are based on the use of Tyco Thermal Controls specified parts only Do not use substitute parts or vinyl electrical t...

Page 2: ...t Insulated bus wire Bus wire connection VPL CT 12 30 cm Drain hole 2 Optional If stand is to be installed on bottom side of pipe knock out drain hole prior to inserting cable Slide heating cable through stand Square off cable end with 90 cut 24 60 cm 12 30 cm 45 Indentation bus wire connection on VPL heating cables only 1 Allow approximately 24 in 60 cm of heating cable for installation For VPL c...

Page 3: ... score inner jacket around and down as shown Peel off jacket Cut and remove all fiber strands Score and remove center spacer Remove any remaining fiber material from bus wires Measure exactly 1 3 8 in 35 mm Lightly score inner jacket around and down as shown Peel off jacket Notch core Peel bus wire from core Score core between bus wires at inner jacket Bend and snap core Peel core from bus wire Re...

Page 4: ...core inner jacket around and down as shown Peel off inner jacket Unwind heating element cut and remove as shown Lightly score clear jacket around and down as shown Remove insulation from ends of bus wires mm 10 20 30 40 50 60 in 1 2 mm 10 20 30 40 50 60 in 1 2 mm 10 20 30 40 50 60 in 1 2 Strip length guide for VPL Go to Step 6 ...

Page 5: ... Remove the guide tubes and dispose of them in a plastic bag Make sure the bus wires do not kink bunch or crossover 1 3 4 44 mm Strain relief Braid 10 Pull cable back through end seal stand until braid is just visible above strain relief 1 2 13 mm 11 Trim exposed conductors CAUTION Health Hazard Wash hands after contact with sealant Consult material safety data sheet VEN0033 If needed re twist and...

Page 6: ...Do not pinch heating cable Be sure pipe strap is under heating cable Loop and tape extra heating cable to pipe Minimum bend radius is 3 4 in 20 mm Insulated parallel crimps 13 Position adapter this side up JBS SPA adapter for small pipes Note For 1 in 25 mm and smaller pipes use adapter purchased separately between stand and pipe Crimp bus wires to lead wires Place blue crimps onto bus wires ...

Page 7: ... cable tie through the slot on stand and the slot on the light then tighten Trim Weather seal 16 Apply insulation and weather seal the stand entry Fasten end seal label to insulation Leave these instructions with the end user for future reference ...

Page 8: ...plit heating cable into multiple circuits Shorten length of heating cable Heating cable is started under very cold conditions heating cable voltage drop is very high for first minutes of very cold start up Wait for heating cable to warm up Voltage at light will increase Heating cable controller is reducing voltage light may not work with controllers that phase fire to reduce line voltage Turn off ...

Page 9: ...ncorretamente e para cumprir com os requisitos da Tyco Thermal Controls das certificações de agências regulamentadoras e dos códigos elétricos nacionais deverão ser usados equipamentos de proteção de contra corrente de fuga à terra Arcos voltaicos não podem ser interrompidos por meio de disjuntores convencionais As aprovações e o desempenho de componentes são baseados no uso exclusivo de peças esp...

Page 10: ...do fio condutor VPL CT 12 pol 30 cm Furo de drenagem 2 Opcional Se o suporte for instalado no lado de baixo do tubo bata no furo de drenagem antes de inserir o cabo Deslize o cabo aquecedor através do suporte Dê uma forma retangular na extremidade do cabo com um corte de 90 24 pol 60 cm 12 pol 30 cm 45 Reentrância conexão do fio condutor somente em cabos aquecedores VPL 1 Deixe aproximadamente 60 ...

Page 11: ...ngitudinalmente como mostrado Retire a capa Corte e retire todos os fios da fibra Corte e retire o espaçador central Retire qualquer material de fibra restante dos fios condutores Meça exatamente 35 mm 1 3 8 pol Corte ligeiramente ao redor da capa interna e longitudinalmente como mostrado Retire a capa Corte o núcleo Descasque o fio condutor no núcleo Corte o núcleo entre os fios condutores na cap...

Page 12: ...itudinalmente como mostrado Retire a capa interna Desenrole o elemento de aquecimento corte e retire como mostrado Corte ligeiramente ao redor da capa e longitudinalmente como mostrado Retire o isolamento das extremidades dos fios condutores mm 10 20 30 40 50 60 in 1 2 mm 10 20 30 40 50 60 in 1 2 mm 10 20 30 40 50 60 pol 1 2 Guia de comprimento de desencapamento para VPL Vá ao passo 6 ...

Page 13: ...o Certifique se de que os fios condutores não se dobrem juntem ou cruzem 1 3 4 pol 44 mm Alívio de tensão Blindagem 10 Puxe o cabo aquecedor para trás através do suporte do terminal final até que a blindagem fique visível acima do alívio de tensão 1 2 pol 13 mm 11 Corte os condutores expostos CUIDADO Risco para a saúde Lave as mãos depois de entrar em contato com o vedante Consulte a Ficha de Info...

Page 14: ...e se de que a abraçadeira para tubo fique debaixo do cabo aquecedor Faça um laço e fixe o cabo aquecedor no tubo com fita adesiva O raio mínimo de curvatura é 20 mm 3 4 pol Terminais paralelos isolados para crimpar 13 Posicione o adaptador com este lado para cima JBS SPA adaptador para tubos pequenos Nota Para tubos de 25 mm 1 pol ou menores use o adaptador adquirido separadamente entre o suporte ...

Page 15: ...no suporte e da ranhura no módulo da lâmpada e em seguida aperte a Corte Vedação hermética 16 Aplique isolamento e vedação hermética na entrada do suporte Fixe a etiqueta do terminal final sobre o isolamento Deixe estas instruções de instalação com o usuário final para consulta futura ...

Page 16: ...ento do cabo aquecedor é muito grande a lâmpada é projetada para funcionar com os compri mentos máximos de circuito publicados Divida o cabo aquecedor em vários circuitos Diminua o comprimento do cabo aquecedor O cabo aquecedor é ligado em condições muito frias a queda de tensão do cabo aquecedor é muito alta durante os primeiros minutos de inicialização em baixas temperaturas Aguarde o aqueciment...

Page 17: ...os o instalación defectuosa del cable calefactor así como para la conformidad con los requisitos de Tyco Thermal Controls la homologación oficial y la normativa eléctrica en vigor Es posible que los disyuntores convencionales no logren detener la formación de arcos eléctricos La homologación y el rendimiento de los componentes se basan en el uso exclusivo de piezas especificadas por Tyco Thermal C...

Page 18: ...s VPL CT 30 cm 12 pulg Orificio de drenaje 2 Opcional Si se va a instalar el soporte en la parte inferior de la tubería abra el orificio de drenaje antes de introducir el cable Deslice el cable calefactor por el soporte Remate el extremo del cable con un corte de 90 60 cm 24 pulg 30 cm 12 pulg 45 Muesca conexión de cable de bus sólo en los cables calefactores VPL 1 Considere unos 60 cm 24 pulg de ...

Page 19: ...argo como se indica Pele la funda Corte y retire todos los hilos de fibra Corte y retire el separador central Retire el material de fibra restante de los cables de bus Mida exactamente 35 mm 1 3 8 pulg Corte ligeramente la funda interior alrededor y a lo largo como se indica Pele la funda Haga una muesca en el núcleo Pele el cable de bus desde el núcleo Corte el núcleo entre los cables de bus en l...

Page 20: ...y a lo largo como se indica Pele la funda interior Desenrolle la resistencia córtela y retírela como se indica Corte ligeramente la funda transparente alrededor y a lo largo como se indica Retire el aislamiento de los extremos de los cables de bus mm 10 20 30 40 50 60 pulg 1 2 mm 10 20 30 40 50 60 pulg 1 2 mm 10 20 30 40 50 60 pulg 1 2 Guía de longitud del conector de VPL Vaya al Paso 6 ...

Page 21: ... bolsa plástica Compruebe que los cables de bus no se doblan amontonan ni cruzan 44 mm 1 3 4 pulg Protección contra tirones Malla 10 Tire del cable calefactor a través de la base del soporte del sello final hasta que la malla quede visible sobre la protección contra tirones 13 mm 1 2 pulg 11 Recorte los conductores que quedan a la vista PRECAUCIÓN Riesgo para la salud Lávese las manos después del ...

Page 22: ...e cable queda debajo del cable calefactor Enrosque el cable calefactor sobrante en el conducto y fíjelo con cinta El radio de curva mínimo es de 20 mm 3 4 pulg Conectores de presión paralelos aislados 13 Coloque el adaptador con este lado hacia arriba Adaptador JBS SPA para tubos pequeños Nota Para los conductos de 25 mm 1 pulg y más pequeños utilice un adaptador adquirido por separado entre el so...

Page 23: ...ranuras del soporte y de la lámpara y apriete Recorte Protección contra la intemperie 16 Aplique aislamiento y proteja el acceso al soporte contra la intemperie Fije la etiqueta del sello final al aislamiento Deje al usuario final estas instrucciones de instalación para su consulta futura ...

Page 24: ...tor La longitud del cable calefactor es excesiva la lámpara está diseñada para funcionar con las longitudes de circui to máximas publicadas Divida la traza eléctrica en múltiples circuitos Disminuya la longitud de la traza eléctrica El cable calefactor se activa en condiciones muy frías la caída de voltaje del cable calefactor es muy elevada en los primeros minutos de las partidas con mucho frío E...

Reviews: