INSTALLATION MANUAL
ProSMS 8
5.1
Installation
Very high voltages are present on this ProSMS device.
Disconnect the PV Array and make sure all sources of power are locked out
before performing any work, removing or mounting the device.
For proper operation, external surge protection in combination with correct overcurrent fusing
must be provided in the combiner box where the device is installed, otherwise the ProSMS
device may be damaged. Overcurrent fusing should be installed on all string channels,
preferable on the negative side (ref. picture below).
The unit should be installed in an enclosure with at least IP5x (dust test) environmental rating
per IEC60529.
5.2
Device setting
Before powering device for the first time set device address and communication options as per the
ProSMS settings tables on page 13.
No reboot or removing/applying power is necessary for changes in settings or address to take
effect. ProSMS has an advanced built in mechanism that recognizes settings change and
sets internal parameters to match the settings immediately when settings are changed. This
also applies to baud rate and parity change.
CAUTION
VOLTAGE
DANGER
WARNING
NOTICE
CAUTION
VOLTAGE
DANGER
WARNING
NOTICE
CAUTION
VOLTAGE
DANGER
WARNING
NOTICE
CAUTION
VOLTAGE
DANGER
WARNING
NOTICE
CAUTION
VOLTAGE
DANGER
WARNING
NOTICE
(Insert #1)
Note: Only colors of the Central inverter can be changed if necessary. Please don’t change the
connection Lines colors anymore!!! It is important that is Red and Common - is Blue!
These two colors are common representation for positive and negative potential of a DC system!