The flue system used on this appliance must be provided
by AGA and must be installed in accordance with the
instructions and standards.
A maximum flue of 5 metres and 5 bends can be used
(including horizontal length on the terminal).
Any upwards vertical runs must be immediate to the
appliance to a maximum of 3 metres. (See Fig. 9)
Downwards vertical runs must be no more than 0.5
metres. (See Fig. 10)
Flue can be positioned to rear or front of appliance via 1
bend. (See Fig. 11).
Horizontal runs must be as level as possible.
Care must be taken on mounting the terminal and routing
the flue:-
a. Damage to damp proof course
b. Height above ground
c. General terminal locations (See Fig. 9)
Where the flue passes through combustible material a
minimum of 10mm clearance must be maintained around
the flue pipe and insulation sleeve.
GENERAL REQUIREMENTS
The flue must be adequately supported using the brackets
specified.
The flue pipe must be insulated (supplied).
All joints should be sealed using the sealant provided.
Site requirements
11
FLUE SYSTEM
FIG. 9
FIG. 10
FIG. 11
DESN 514115 B
DESN 514116 B
DESN 514114
Summary of Contents for XT- Oil
Page 24: ...24 Wiring Diagram FIG 27 WIRING DIAGRAM APPLIANCE...
Page 26: ...26...
Page 27: ...27...