![Rayburn Cookmaster 200SFW Installation Instructions Manual Download Page 5](http://html.mh-extra.com/html/rayburn/cookmaster-200sfw/cookmaster-200sfw_installation-instructions-manual_789464005.webp)
COOKER FLUE CONNECTION
FLUE LAYOUTS
5
The minimum diameter for a straight chimney is 150mm
and there should not be more than two bends of 45°
from vertical.
IN ALL TYPES OF CHIMNEYS THE MINIMUM
HEIGHT FOR CORRECT OPERATION OF THE
CHIMNEY IS 4.5m AND SHOULD TERMINATE
ABOVE THE ROOF IN ACCORDANCE WITH
REGIONAL STATUTORY REQUIREMENTS
RECOMMENDED FLUE DRAUGHT - 12 Pa MINIMUM.
THE APPLIANCE SHOULD BE INSTALLED AND
CONFORM TO THE CURRENT CODES OF
PRACTICE FOR INSTALLATION OF DOMESTIC
HEATING AND COOKING APPLIANCES BURNING
SOLID FUEL - BS 8303.
ALWAYS ADVISE THE USER TO CLEAN THE
COOKERS FLUES IN ACCORDANCE WITH THE
OPERATING INSTRUCTIONS AND TO HAVE THE
CHIMNEY SWEPT AT A MINIMUM OF 12 MONTHLY
INTERVALS AFTER THE COOKER IS
COMMISSIONED.
The position of available types of flue layouts are
shown in Figs. 2, 3 and 4, the cooker flue chamber is
adaptable to providing either top or back flue outlets, by
means of the reversible loose socket.
a) Rear Flue Outlet
This must only be used where there is a brick flue
immediately behind the cooker. Provision must be
made for a condensate collecting vessel and
cleaning door. See Fig. 3.
EXTENDED HORIZONTAL FLUE PIPE CONNECTION
IS ALLOWED UP TO A MAXIMUM OF 150mm IN
LENGTH.
NO BEND CONNECTIONS ARE ALLOWED.
b) Top Flue Outlet
The cooker should be connected to the main flue via
a 125mm minimum diameter cast iron flue pipe or
appropriately internally/externally vitreous enamelled
mild steel pipe and be sealed to the cooker flue
chamber with soft rope and fire cement. Any bends
in the flue pipe must not be less than 135° (45° from
vertical) and be complete with a cleaning door.
In Fig. 2 the cooker is installed in an existing recess.
There must be a clearance of not less than 150mm
between the top of the flue pipe and any overhanging
brickwork.
Any cavities or pockets above the register plate should
as far as possible be filled and if necessary the flue
pipe should be extended into the throat of the chimney
and a soot door for chimney sweeping.
If a flue liner or insulated chimney is used, the size
should not be less than 150mm.
In Fig. 3 the cooker is connected direct to a brick flue.
Horizontal pipe runs between cooker and brick flue
must not
be used.
In Fig. 4 the cooker is connected to an existing brick
flue with a length of flue pipe. Square bends and
horizontal runs
must not
be used. There must be a
cleaning door at every bend.
NOTE:
WHATEVER METHOD OF INSTALLATION IS
EMPLOYED. AIR MUST NOT BE ALLOWED TO
ENTER THE CHIMNEY EXCEPT THROUGH THE
COOKER ALL JOINTS MUST BE AIR-TIGHT.
If the chimney is unlined, and there is any doubt about
its condition, it should be lined in accordance with
current Building Regulations.
PROVISION MUST ALWAYS BE MADE FOR
SWEEPING THE CHIMNEY.
IMPORTANT:
CEMENT TYPE PIPES AND FITTINGS
MUST NOT BE USED WITHIN 2m OF THE COOKER.
CHIMNEYS OF PLAIN PIPE ARE NOT
RECOMMENDED BUT CERTAIN PROPRIETARY
MAKES OF INSULATED CHIMNEY ARE SUITABLE.