Reference should be made to British Gas
Publications <<Material. and Installation
Specifications for Domestic Central Heating
and Hot Water >> Draining taps should be at
least 1/2" in BSP nominal size and be in
accordance with BS 2879.
4.8.9
Installation to an existing central heating
system
The System boiler is designed to operate
on a sealed system only. Therefore if the
existing system is of the open water type it
will have to be modified to comply with BS
5376 Part 2.
Before installing a new System boiler to an
existing system, flush out the old system
with a recommended descaling agent.
It is most important that the correct concen-
tration of the water treatment product is
maintained in accordance with the manu-
facturers’ instructions.
If the boiler is installed in an existing system
any unsuitable additives MUST be removed
by thorough cleansing.
BS 7593:1992 details the steps necessary
to clean domestic central heating system.
Also check pipework and renew any corrod-
ed pipework or fittings. Valve glands must
be repacked or replaced wherever neces-
sary and any defective controls exchanged.
WATER TREATMENT
This boiler has a secondary ALUMINIUM
alloy heat exchanger Ravenheat recom-
mended only the use of FERNOX-COPAL,
SENTINEL Xl00 or SALAMANDER CUR-
ROSION GUARD water treatment products,
which must be used in accordance with the
manufacturers instructions. For further
information contact:
Fernox Manufacturing Co. Ltd.
Tel. 01799 550811
Sentinel Division Betz Dearborn Ltd.
Tel. (0151) 424 5351
Salamander (Eng) Ltd
Tel. (0121) 3780952/4508
4.10
ELECTRICAL SUPPLY
Warning: this appliance must be earthed
4.10.1
External wiring to the appliance must be
carried out by a competent person and be in
accordance with the current I.E.E. Regula-
tions and local regulations which apply.
The Ravenheat boiler is supplied for con-
nection to a 230 V - 50 Hz single phase
supply.
The supply must be fused at 3 A.
NOTE: The method of connection to the
electricity supply MUST facilitate complete
electrical isolation of the appliance, by the
use of a fused, double pole isolator, having
a contact separation of at least 3 mm in all
poles. The point of connection to the elec-
tricity supply must be readily accessible and
adjacent to the appliance except, where the
appliance is installed in a bathroom, this
MUST be sited outside the bathroom.
SECTION
5 INSTALLATION
5.1
WARNING
5.1.1
It is MOST IMPORTANT that this appliance
is installed in a VERTICAL POSITION, with
the flue air duct passing through the wall.
Make sure flue slopes 2.5
o
down towards
the boiler that is 45 mm/m fall per metre
of flue length.
Fig. 10
Fig. 11
Summary of Contents for Flue Boiler
Page 16: ...Supplied By www heating spares co Tel 0161 620 6677 ...
Page 26: ...Supplied By www heating spares co Tel 0161 620 6677 2 6 ...
Page 41: ...Supplied By www heating spares co Tel 0161 620 6677 Fig 90 Fig 91 Fig 93 41 ...
Page 45: ...Supplied By www heating spares co Tel 0161 620 6677 ...
Page 49: ...Supplied By www heating spares co Tel 0161 620 6677 ...