18. Programming & Commissioning
This section refers to Password Protected sections of the Pellet fi re Menus. Only Nature’s Flame approved
pellet fi re installers and technicians will have access to these passwords. If you are not a Nature’s Flame
approved installer or technician, please do not attempt to install, program or commission any pellet fi re
from Nature’s Flame.
18.1 Sara Parameters - version BOX 03
Name
Program
Unit
Value
Before
Programming
After
Programming
Adjusted
Settings
Minutes time out
PR01
Min
18
Minutes start
PR02
Min
5
Clean frequency
PR03
Min
60
Cleaning duration
PR04
Sec
20
Screw start
PR05
Sec
1.8
Screw power 1
PR06
Sec
1.6
Screw power 2
PR07
Sec
2
Screw power 3
PR08
Sec
2.4
Screw power 4
PR09
Sec
2.8
Screw power 5
PR10
Sec
3.2
Re-start threshold
PR11
°C
80
No pellet threshold
PR12
°C
50
Off threshold
PR13
°C
45
Maximum threshold
PR14
°C
250
Fan threshold
PR15
°C
80
Smoke ignition
PR16
RPM
2100
Ignition smoke speed
PR17
RPM
1950
1 smoke speed
PR18
RPM
1500
2 smoke speed
PR19
RPM
1720
3 smoke speed
PR20
RPM
1930
4 smoke speed
PR21
RPM
2140
5 smoke speed
PR22
RPM
2350
Air 1 speed
PR23
V
110
Air 2 speed
PR24
V
120
Air 3 speed
PR25
V
130
Air 4 speed
PR26
V
150
Air 5 speed
PR27
V
175
Enable glow plug
PR28
on / off
ON
Suct smoke cleaning
PR29
RPM
2800
Screw cleaning
PR30
Sec
1.3
Pre-heat glow plug
PR31
Sec
150
Screw max load
PR32
Min
4
Flame delta
PR33
°C
20
Screw ignition
PR34
Sec
2.5
Alarms delay
PR35
Sec
60
xHZ frequency
PR36
Hz
50