Operation E-CLICK
4
20
4.4
Reference run
Conduct a reference run
You must decide which state the metering slides are to be in.
1.
Switch both toggle switches to the
Neutral
position.
2.
Switch both toggle switches from
Neutral
to the required position of the
metering slides.
The actuators are moved in the required direction.
Switch off is performed once the stop is reached.
The LEDs light up in the respective colour.
The state of the actuators is stored now, even if the user switches the toggle
switches to the
Neutral
position.
NOTICE
After having restarted the control unit E-CLICK and independently of the
switching state of the toggle switches:
the LEDs are off,
the state of the actuators is unknown.
A reference run is required, therefore.
NOTICE
The LEDs go out if you switch to the
Neutral
position while moving and interrupt
the movement of the actuators this way. The control unit E-CLICK is not able to
identify the state of the actuators.
Perform new reference run.