background image

24 Volt Power Supply

 pg.  2

Installation:

• Locate a suitable mounting location for the supply

• Mount the Power Supply using 6 mounting screws (not provided) and punch out conduit knockouts for wire runs
• For each Call Box you must run an 18 gauge, 2 wire set down to the Power Supply 

• Feed the AC power cable through the knockout located on the bottom of the Power Supply. 
  Attach the power cable to the proper screw terminals – See Power Supply diagram below

• Attach the power cables from the appropriate Call Boxes to the Power Supply
  • For up to 5 Call Boxes, wire 1 set of power cables to individual ports numbered 1 through 5 on the 
    Power Supply. One wire will go to the top screw of the port; the other will go to the bottom port
  • For 5 to 10 Call Boxes, wire one set of power cables to individual ports 1 - 8. Wire 2 sets of power cables 
    to port 9
  • For 11 to 20 Call Boxes, wire two sets of power cables to ports 1 - 7. Wire 3 sets of power cables to 
    ports 8 & 9
  • For 20+ Call Boxes, up to 5 Call Boxes can be wired per port, for a total of 45 Call Boxes.  
    Do not wire more than 5 Call Boxes per port.

• Plug Power Supply into 120 vac outlet or connect the supply to the electrical through a conduit connection 

• Turn power switch in Power Supply to ON

• Verify output voltage to be 24 vdc, if not 24v adjust using the Voltage Adjustment Potentiometer (see below)

• Close the Call Box Power Supply

www.area-of-refuge.com

Voltage 

Adjustment 

Potentiometer

Summary of Contents for 2500-PWR24

Page 1: ...porate Circle Sussex WI 53089 800 451 1460 262 246 4828 fax www area of refuge com 03 13 Made in the USA 3 Year Warranty Installation Operations Manual 2500 PWR24 VDC Power Supply Ver 2 RP8500225 www area of refuge com ...

Page 2: ...ntinually provide Innovative Thinking Design and Value If you have any questions or comments just give us a call Thank you for your business Tom Touchett President 800 451 1460 Installation Page 2 Power Supply Diagram Page 2 Wiring Diagram Page 3 Power Supply Mounting Diagram Page 4 Troubleshooting Page 5 Table of Contents N56 W24720 N Corporate Circle Sussex WI 53089 800 451 1460 262 246 4828 fax...

Page 3: ...hrough 5 on the Power Supply One wire will go to the top screw of the port the other will go to the bottom port For 5 to 10 Call Boxes wire one set of power cables to individual ports 1 8 Wire 2 sets of power cables to port 9 For 11 to 20 Call Boxes wire two sets of power cables to ports 1 7 Wire 3 sets of power cables to ports 8 9 For 20 Call Boxes up to 5 Call Boxes can be wired per port for a t...

Page 4: ... vac Ground 2500 _____ SmartRescue Base Station pg 3 Note A three prong plug is included with the Power Supply Conduit with electrical can also be attached to the Power Supply Wiring requirements for Power Supply to Call Box 1 Minimum requirement is 18 awg 1 pair wire www area of refuge com ...

Page 5: ...ting Dimensions Back Side pg 4 8 30 in 0 60 in 1 50 in 8 30 in 10 60 in 9 60 in 9 00 in 5 85 in 2 70 in 1 36 in 1 10 in 1 50 in 3 50 in 1 50 in 0 60 in 0 60 in 1 50 in Side Bottom Top www area of refuge com ...

Page 6: ...the power supply is wired properly Call station does not have Power Make sure the Green LED s are illuminated on the Power Supply Check to see that each output on the Power Supply is producing 24vdc pg 5 Make sure the power switch is set to the On position on the power supply Technical Support Technical Support is available at 800 451 1460 from 7 30 4 00 p m C S T www area of refuge com ...