background image

8

    render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for 

    this task.

    Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working press-

    ure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until 

    no refrigerant is within the system. 

    When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take 

    place. This operation is absolutely vital if brazing operations on the pipe-work are to take place.

    Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.

13.Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination

of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to

minimise the amount of refrigerant contained in them.

Cylinders shall be kept upright.

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

Label the system when charging is complete (if not already).

Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of

charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

14.Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its

detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an

oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential

that electrical power is available before the task is commenced.

a)Become familiar with the equipment and its operation.

b)Isolate system electrically.

c)Before attempting the procedure ensure that:

Mechanical handling equipment is available, if required, for handling refrigerant cylinders;

All personal protective equipment is available and being used correctly;

The recovery process is supervised at all times by a competent person;

Recovery equipment and cylinders conform to the appropriate standards.

d)Pump down refrigerant system, if possible.

e)If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.

f)Make sure that cylinder is situated on the scales before recovery takes place.

g)Start the recovery machine and operate in accordance with manufacturer's instructions.

h)Do not overfill cylinders. (No more than 80 % volume liquid charge).

i)Do not exceed the maximum working pressure of the cylinder, even temporarily.

j)When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment

are removed from site promptly and all isolation valves on the equipment are closed off.

k)Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

15.Labelling

Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated

and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

16.Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that

all refrigerants are removed safely.When transferring refrigerant into cylinders, ensure that only appropriate refrigerant

recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is avail-

   able. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special 

   cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off 

   valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

   The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at 

   hand and shall be suitable for the recovery of flammable refrigerants.In addition, a set of calibrated weighing scales shall 

   be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good cond-

   ition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and 

   that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult 

   manufacturer if in doubt.

   The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant 

   Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or 

   compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that 

   flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning 

   the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. 

   When oil is drained from a system, it shall be carried out safely. 

Summary of Contents for RC-X7R

Page 1: ...R RC X9R RC X12R RC X18R IMPORTANT NOTE This appliance is using R32 mildly flammable refrigerant Read this manual carefully before installing or operating Make sure to save this manual for future refe...

Page 2: ...d assessment specification 3 Maintenance and repair requires the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrig...

Page 3: ...Transport of equipment containing flammable refrigerants Compliance with the transport regulations 2 Marking of equipment using signs Compliance with local regulations 3 Disposal of equipment using f...

Page 4: ...import and export permit control and landfill disposal ban in respect of abandoned regulated electrical equipment REE have commenced Any person who is engaged in the storage treatment reprocessing or...

Page 5: ...upervised around the unit at all times operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit In cert...

Page 6: ...and the circuit breaker fuse rating should be the same as that of the power cord and wall outlet Power cord conductors are distinguished according to the color as shown in Wiring Diagram located on t...

Page 7: ...circuit should hold a current valid certificate from an industry accredited assessment authority which authorises their competence to handle refrigerants safely in acc ordance with an industry recogni...

Page 8: ...No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a...

Page 9: ...rcuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use Intrinsically safe components are the only types that can be worked on while liv...

Page 10: ...y takes place g Start the recovery machine and operate in accordance with manufacturer s instructions h Do not overfill cylinders No more than 80 volume liquid charge i Do not exceed the maximum worki...

Page 11: ...r at night than in the daytime This is because the noise in the surroundings is comparatively low at night If your feel that the noise is too loud switch the thermostat to lower numbers UNIT PARTS IDE...

Page 12: ...vent It will allow internal air circulation OPEN the vent to discharge stale air NOTE Different models have different operation panels Not all the functions describing below are available for the air...

Page 13: ...air alternately for comfortable cooling heating To stop the air swing feature press the SWING keypad again the indicator light adjacent to the keypad will go off TIMER POWER Press the POWER keypad to...

Page 14: ...he units with operation panel cover DO NOT press or swing the opened operation cover Horizontal airflow adjustment For the units with manual control lever Manually Vertical airflow adjustment Manually...

Page 15: ...filter with warm soapy water The water should be below 40 C 104 F to prevent distortion of the filter 4 If your filter has a small air freshening filter clean this air freshening filter with a hand h...

Page 16: ...sted under non drainage status Make sure that water will not leak from the surrounding area when rubber plug and joint were used Please seal it in case leakage is found Rubber plug Drain pan Drain out...

Page 17: ...he cabinet must remain exposed to the outside of the structure CAUTION Before installing remove all packaging from inside the carton Step 1 Select the best location 1 To avoid vibration and noise make...

Page 18: ...s around the inside and outside to provide satisfactory appearance and protection against the weather insects and rodents see Fig 7 Fig 6 Fig 7 WALL CABINET SCREWS Step 6 Install the unit into the cab...

Page 19: ...n to the cabinet and run a drain hose to a suitable location if required Fig 11 17 NOTE For the unit with power cord comes out from left side please perform the following steps 1 Pull the power cord t...

Page 20: ...tioner plug is pushed completely into the outlet and switched on Check the house fuse circuit breaker box and replace the fuse or reset the breaker If power failure occurs switch off and disconnect un...

Page 21: ...different customization requirements the deepth of the panel may be slightly different So the dimension of D is for reference only RC X7R RC X9R 450 6x350x675 600x380x560 660x428x680 RC X12R RC X18R B...

Page 22: ...s are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please...

Page 23: ......

Page 24: ......

Reviews: