Rasmussen RF-RF-LD30/36-VEI-N/P Owner'S Manual Download Page 5

5

 

 

In the Commonwealth of Massachusetts: 

 

• 

Installation must be performed by a licensed plumber or gas fitter. 

• 

The chimney flue damper, when used with gas logs, will be welded open or completely removed. 

• 

A CO detector shall be installed in the room where the appliance is installed. 

 

A)  Fireplace Gas  

Supply Valve 

Gas Supply  

Pipe 

FIGURE 1 

 Log Lighter  

Valve Assembly (V1) 

FIGURE 2 

A)  Damper 

Clamp 

Flue 

WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts  

specifically approved with this appliance may result in property damage or personal injury. 

The appliance and it’s appliance main gas valve must be disconnected from the gas supply piping system during 

any pressure testing of that system at test pressures in excess of 1/2 psi. The appliance must be isolated from 

the gas piping system by closing its equipment shutoff valve during any pressure testing of the gas supply 

piping system at test pressures equal to or less than 1/2 psi. 

GENERAL INSTALLATION INSTRUCTIONS 

WARNING! CHECK FOR PROPER VENTING 

A properly sized, unobstructed chimney will normally vent all products of combustion. Any odor or smoke detected inside 

the room is an indication that the flue is not functioning properly.

 

SHUT OFF THE BURNER IMMEDIATELY! THE CAUSE OF THE VENTING PROBLEM MUST BE DISCOVERED AND 

CORRECTED BEFORE CONTINUED USE OF THE GAS LOG SET. 

 

Continued use with improper venting may cause damage to your fireplace, room furnishings and could cause serious illness.  

IF IMPROPER VENTING IS SUSPECTED,

 

IMMEDIATELY HAVE LOG SET AND CHIMNEY FLUE SERVICED.

 

 

The installation and the provisions for combustion and ventilation air must conform with 

The National Fuel Gas 

Code ANSI Z223.1 / NFPA54

, or 

The CSA B149.1, Natural Gas and Propane Installation Code, 

latest edition.

 

STEP ONE PREPARATION: 

 

1.  Verify that the Valve Assembly is correctly matched to the log set, 

burner, and gas supply. 

 

2.   Turn off 

Fireplace Gas Supply

 (Figure 1A) . 

 

3.  Thoroughly clean fireplace floor of any ashes and have a qualified 

chimney cleaner insure that the chimney flue and firebox are free of 

soot, creosote, and loose paint. 

 

4.  Attach 

Damper Clamp 

(Figure 2A) over edge of fireplace 

Damper 

Blade 

(Figure 2B) to prevent damper from fully closing  

      accidentally. If unable to attach damper clamp, drill a hole  

      (or holes) in the damper or remove it completely. 

 

IMPORTANT:  

 

THE CHIMNEY DAMPER MUST BE WIDE OPEN AND FIXED IN A MANNER  TO MAINTAIN A PERMANENT FREE OPEN-

ING AT ALL TIMES AS OUTLINED ABOVE. THE AREA OF THE FLUE MUST BE NOT LESS  THAN 1/10 THE AREA OF THE 

FIREPLACE OPENING. THIS GAS LOG SET MUST BE INSTALLED IN A FULLY VENTED METAL OR MASONRY FIRE-

PLACE WITH A WORKING FLUE THAT IS SAFE FOR BURNING A WOOD FIRE. THE FLUE MUST BE FREE OF ANY   

OBSTRUCTIONS AND MUST EXHAUST ALL PRODUCTS OF COMBUSTION. DAMPER AND GLASS DOORS MUST BE 

FULLY OPEN BEFORE LIGHTING OR BURNING FOR PROPER VENTILATION AND TO PREVENT HEAT DAMAGE TO 

THE VALVE.

 

Natural Gas Operating Pressures: Minimum inlet gas supply pressure = 6 inches of water column. Maximum inlet 

gas supply pressure is 7 inches of water column. Propane Gas Operating Pressures: Minimum inlet gas supply 

pressure = 11 inches of water column. The maximum inlet gas supply pressure is 14 inches of water column.  

Opening Height 

(See page 6) 

B) Damper  

Blade 

• 

RF-LD burner 

should not be installed in a Direct vent, B-Vent and or Vent free fireplace. 

• 

Log set is designed  to 

burn with yellow flames

; thus 

adequate ventilation 

is absolutely necessary. 

Summary of Contents for RF-RF-LD30/36-VEI-N/P

Page 1: ...ed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with type of gas indicated on the rating plate INSTALLER Leave this...

Page 2: ...epair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent cleaning may be required due to exc...

Page 3: ...LD30 36 2 Rating I D Plate 3 Flex Connector SSCB 14 4 3 8 x 1 2 FIP Flared Brass Fitting A1 5 Orifice Spud see page 12 for size 6 Orifice Holder Internally Tapped 3 8 x 3 8 Flared MIP Fitting A2T 7 A...

Page 4: ...Switch Cable GV60 SWA 24 Module Receiver GV60 RXA 29 8 Wire Cable GV60 C8 25 Interrupter Block GV60 TIA 30 GV60 Battery Box Cable GV60 BCA 26 Ignition Cable GV60 ICA 31 Plug in Adapter for AC Power Su...

Page 5: ...and ventilation air must conform with The National Fuel Gas Code ANSI Z223 1 NFPA54 or The CSA B149 1 Natural Gas and Propane Installation Code latest edition STEP ONE PREPARATION 1 Verify that the Va...

Page 6: ...E REQUIREMENTS The minimum permanent free opening of the fireplace chimney or chimney damper must be at least the minimum Chimney Area shown below based on a minimum chimney height of at least 8 feet...

Page 7: ...propane gas burner A Natural Gas B Propane FIGURE 6 STEP TWO Sprinkle a light covering of Ember Magic over the Pan Medium Figure 6A and Figure 6B Pull apart Ember Magic fiber material to enhance the g...

Page 8: ...charred burnt effect between the two halves Figure 8 and Figure 9 Place the Longest Log or 2 largest charred logs if applicable Figure 8A and 9A as far forward on the Grate as possible The remaining l...

Page 9: ...ing BATTERY PACK PLACEMENT NOTE Any beeping or unexpected shutdown may be the over temperature safety feature in the receiver If this happens move the receiver into a cooler area and or use the RH2 RH...

Page 10: ...ROL SETTINGS ON GAS VALVE WHILE OPERATING WITH REMOTE TRANSMITTER Valve switch set to 0 Valve switch set to I VALVE IN 0N POSITION Valve switch set to I Flame height control knob turned 0N Flame heigh...

Page 11: ...beep release the reset button Within the subsequent 20 second press the small flame button on the handset until you hear two additional short beeps confirming the code is set If you hear one long bee...

Page 12: ...k pilot flame Weak pilot flame is the NUMBER 1 SERVICE ISSUE REGARDING NUISANCE SHUT OFF Using canned compressed air blow out the opposing air intake ports located at the base of the pilot where the g...

Page 13: ...l light properly The pilot flame should be steady and soft blue surrounding 1 8 inch of the thermocouple Pilot Tube Air Intake Port Thermocouple Tip Piezo Spark Blue Dot Natural Gas Red Dot Propane 1...

Page 14: ...which have been closed or are obstructed with debris will not allow sufficient combustion air into the burner Use compressed air and or a soft bristle brush to clean the air mixer area Air mixers sho...

Page 15: ...alve Vanisher Make sure the fireplace floor is even with the Hearth floor Also change batteries Odor and or Smoke After Break in Period other than Natural Odor of Gas Combustion Most likely causes Lac...

Page 16: ...The maximum liability of RASMUSSEN in connection with this limited warranty shall not in any case exceed the contract price paid for the product claimed to be defective or unsuitable 4 This warranty...

Reviews: