Rasmussen 18DFC7-ME-N Owner'S Manual Download Page 5

 

This heater shall not be installed in a “confined” space or unusually tight construction unless provisions are  

provided for adequate combustion and ventilation air. 

Calculations to Determine Confined or Unconfined Space: 

 

1.   Determine number or rooms (including adjoining rooms with odorless passageways or ventilation grates.) 
 

 

Example:   Living room/Dining Room + 

Kitchen 

 

2.   Determine the Total Volume of the Space (Width x Length x Height).

 

  Example: 

 

Living 

room/Dining Room  14’ x 20’ x 8’  = 2240 cu ft. 

    

 

 

Kitchen   

 

 

 

 

 

 

8’ x 12’ x 8’  =    768 cu ft.  

 

 

 

   

Total Volume of Space 

 

     3008 cu ft. 

 

3.   Divide the total volume of space by 

50 cu ft 

to determine the 

Maximum Supportable Btu/Hr. 

 

 

Example:  3008 cu ft ÷ 50 = 60.160 x 1000 = 60,160  

 

 

Maximum Supportable Btu/Hr. =                 60,160 Btu/Hr. 

 

4.   Add the rated (Btu/hr) of all fuel burning appliances in the “space” to determine 

Actual Btu/Hr. used. 

 

 

Example:  Vent free gas log heater    40,000 Btu/Hr. 

 

 

 

    + Gas water heater           32,000 Btu/Hr. 

 

 

 

    

= Actual Btu/Hr. Used     72,000 Btu/Hr.  

 

Note: Do not include direct vent gas appliances. 

 

5. Compare 

Maximum Supportable Btu/Hr 

to 

Actual Btu/Hr Used.

 

       •  If the 

Actual Btu/Hr used. 

is greater than the 

Maximum Supportable Btu/Hr. 

then the space is 

CONFINED. 

       

•  If the 

Actual Btu/Hr used. 

Is 

less than

 the 

Maximum Supportable Btu/Hr. 

then the space is 

UNCONFINED. 

 

 

Example:  

Maximum Supportable Btu/Hr =  60,160 Btu/Hr. 

    

 

 

 

Actual 

Btu/Hr. 

Used                   =  72,000 Btu/Hr.  

    

 

 

 

Difference 

   

 

 

 

 

11,840 Btu/Hr. = Excess Non-Supportable Btu/Hr. 

 

Because the 

Actual Btu/Hr u

sed Exceeds the 

Maximum Supportable Btu/Hr 

in this example, the space is considered 

Confined Space 

requiring you to either increase the 

Maximum Supportable Btu/Hr 

by the difference, in this case 

11,840 Btu/Hr. or decrease the 

Actual Btu/Hr 

used by the same amount. You may also choose to operate your  

Chillbuster™ as a Vented Appliance instead. 

(See notes and warnings regarding vented installation on Page 7)

 

Adequate Combustion And Ventilation Air Options: 

 

• 

Increasing the 

Maximum Supportable Btu/Hr. 

 

      1.   Add to the number of rooms which comprise the “Space”. To do this you must either completely remove the door 

to an adjoining room, or provide two permanent ventilation grills; one within 12” of the ceiling and another within 
12” of the floor. 

      2.   Provide extra fresh air using ventilation grills and ducts to the outdoors. You must provide two permanent open-

ings.  One within 12” of the ceiling and another within 12” of the floor. Connect these directly to the outdoors or 
spaces open to the outdoors, e.g., attics or crawl spaces. If this route is chosen you 

MUST

 follow the 

National 

Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation 

for required size of 

ventilation grills or ducts. 

 

• 

Lower the 

Actual Btu/Hr used

 by relocating other gas burning appliances outside the “space” or installing a lower 

Btu/Hr heater. In the example, the maximum Btu/Hr. of the heater could be no more than 28,160 Btu/Hr. 

The 

“National Fuel Gas Code, ANSI Z223.1/NFPA 54” 

 

defines a confined space as a space whose volume is less than 

50 cubic feet per 1000 Btu per hour (4.8 m

³

 per kW) of the aggregate input rating of all appliances installed in that space 

and an unconfined space as a space whose volume is not less than 50 cubic feet per 100 Btu per hour (4.8 m

³

 per kw) of 

the  aggregated input rating of all appliances installed in that space. Rooms communicating directly with the space in 
which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined 
space.   

VENT FREE APPLICATIONS 

 SPACING CALCULATIONS

 

Summary of Contents for 18DFC7-ME-N

Page 1: ... or loss of life This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with type of gas indicated on the rating plate This appliance is not convertible for use with other gases Field conversion is not permitted Gas type conversion may only be accomplished at the factory Please contact Rasmus...

Page 2: ...ted before use and at least annually by a professional service person More frequent cleaning may be required due to excessive lint from carpeting bedding material etc It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean WARNING Any change to this heater or its controls can be dangerous This appliance is intended for supplemental heating ...

Page 3: ...8b Piezo Wire misc part 18c Peizo Pal Nut 19 Orifice Natural 35 Propane 50 20 Volcanic Ash VA5 21 Embers EMCB 22 Rating Serial Plate 23 Warning Plate 4 3 8 X 1 2 Pipe Nipple 5 3 8 90 Elbow 6 Regulator R1 3 5 Narural Gas R1 10 5 Propane 7 Gas Supply Input A2 7b Orifice Holder A2 7 Grate DFC7 OLD STYLE DFC7E 8 Damper Clamp DC1 9 Flex Connector SSCB 18 10 3 8 x 1 2 FIP Flared Brass Fitting A1 11 Burn...

Page 4: ... WT 2R d Wireless Wall Thermostat TS 2R e Wireless Wall Switch WS 2R 14 Wireless Hand Held Variable Remote for RE Models STR RMD 15 Remote Receiver for SE or RE models BPR3 16 Remote Housing RH2 sold separately Gas Supply Valves see page 8 and 9 Sold Separately A B C D E LOGS AND ACCESSORIES 13 12 14 15 12 7 8 5 2 10 6 1 3 4 9 11 1 Center log for DFC7 18 24 and 30 U12 2 Front log for DFC7 18 H21a ...

Page 5: ...ease the Actual Btu Hr used by the same amount You may also choose to operate your Chillbuster as a Vented Appliance instead See notes and warnings regarding vented installation on Page 7 Adequate Combustion And Ventilation Air Options Increasing the Maximum Supportable Btu Hr 1 Add to the number of rooms which comprise the Space To do this you must either completely remove the door to an adjoinin...

Page 6: ...r plumbing electrical and gas lines and at other openings VENT FREE APPLICATIONS COMBUSTION AIR CALCULATIONS COMBUSTION AIR CALCULATIONS WORKSHEET 1 Room Width Length Height W x L x H Vol ft 1a 1a 1b 1b 1c 1c 1d 1d 2 Total Volume ft The Sum of Volume of all rooms add lines 1a thru 1d 2 3 Max Supportable Btu Hr Total Volume ft 50 x 1000 divide line 2 by 50 then multiply by1000 3 4 4a Btu hr 4b Btu ...

Page 7: ...vented installation on following page 17 20 15 17 10 12 12 15 20 Height Above Opening Projection Out From Face Non combustible or heat resistant material gypsum board marble sheet rock slate tile etc 8 Minimum from top of firebox opening 25 28 30 28 30 12 20 20 25 When operated as a Vent Free Heater the minimum clearances from the fireplace opening to combustible materials must be maintained as ou...

Page 8: ... TO THE VALVE GENERAL INSTALLATION INSTRUCTIONS The installation and the provisions for combustion and ventilation air must conform with The National Fuel Gas Code ANSI Z223 1 NFPA54 or The CSA B149 1 Natural Gas and Propane Installation Code latest edition WARNING CHECK FOR PROPER VENTING A properly sized unobstructed chimney will normally vent all products of combustion Any odor or smoke detecte...

Page 9: ...e before continuing B Gas Supply Pipe A 1 2 FIP x 3 8 Flared Elbow FIGURE 3 MINIMUM AND MAXIMUM INLET GAS SUPPLY PRESSURE Theminimuminletgassupplypressureshall be5inchesofwatercolumnonNatural Gasand 11inchesofwatercolumnon Propane Themaximuminletgassupplypressureshall be7inchesofwatercolumnonNatural Gasand14inchesofwater column on Propane Theappliance anditsmaingas valvemustbedisconnectedfrom the ...

Page 10: ...ore than one to two pieces of ember material in depth To ensure proper ignition and combustion and to enhance ember performance gently loosen lift Ember Material with a screw driver after approximately five minutes of burn time STEP THREE LOG PLACEMENT ALL MODELS NOTE Thinner less densely packed pieces of Ember Material will enhance the overall glowing ember effect e g the looser the pieces the be...

Page 11: ... pins Figure 9A and B place the Center Top Log Figure 9C diagonally over both Front Logs The pins for the center log will be the right side pins if facing each front log Next place the right and left top logs over the remaining two log locator pins Figure 10A and B The top logs for the DF HG18 will be the CH3a chunks shown below For the 24 and 30 use the BE2a chunks see page 4 6 FIGURE 9 A Log Loc...

Page 12: ...sound of a crackling fire adding a cozy feel to your log set see also Parts and Acces sories page 4 Black Volcanic Ash used to help conceal Remote Receiver Wires FIGURE 12 C B FIGURE 11 Top View Volcanic Ash WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury A R...

Page 13: ...ed on the front right side of the CHILLBUSTER face plate Figure 13 and Figure 14A and turn clockwise to OFF 2 Before lighting wait at least five minutes to allow gas which may have accumulated around burner to escape then slightly push in the EASY Safety Valve Knob and turn to PILOT OFF Figure 14 3 Depress knob until air dissipates and gas flows to pilot Press the Piezo Ignitor Button to light the...

Page 14: ...RATION RE VARIABLE FLAME HEIGHT AND SE REMOTE READY MODELS 1 Turn Valve Knob to ON position Figure 18A 2 Slide switch on the Receiver Figure 19 to REMOTE position RE Models 3 Depress the ON HI button on the TRANSMITTER Figure 18B until a click is heard The burner will then light to Full on NOTE Reducing the burner flame can be achieved by pressing the LO button one beep at a time to the desired fl...

Page 15: ... operating the heater This appliance is equipped with a Safety Pilot System designed to shut itself off if enough fresh air is not available Additional ventilation may be optained by opening a window or a door to another room Although your CHILBUSTER is very realistic in appearance it is not a real wood burning fireplace Matches paper garbage or any other foreign material MUST NOT be thrown on top...

Page 16: ... and burner ports where flame comes out of the burner should be periodically cleaned of debris Use compressed air and or a soft bristle brush to clean burner ports and air shutter area Air shutters should not be altered from factory settings WARNING Failure to keep the burner primary air opening clean may result in sooting or property damage Keep air intake holes of ODS Pilot see Page 13 Figure 17...

Page 17: ...r Relieve any tight bends or kinks in the Flex Connector Switch to a smooth aluminum connector which can be purchased at hardware or home improvement stores Burner Flame is Too High 8 12 Above Top Logs or Too Low Below Top Logs Incorrect gas supply pressure or burner orifice used 1 Ensure gas type of set is proper for gas type being used Make sure the gas pressure coming into the fireplace falls b...

Page 18: ...of incidental or consequential damages so the above limitation or exclusion may not apply to you 3 The maximum liability of RASMUSSEN in connection with this limited warranty shall not in any case exceed the contract price paid for the product claimed to be defective or unsuitable 4 This warranty does not extend to any product manufactured by RASMUSSEN which has been subjected to misuse neglect ac...

Reviews: