Raritan PXE Quick Setup Guide
2
QSG-PXE-1C-v3.5.0-E
255-80-0007-00 RoHS
Mounting 1U Models Using L-Brackets and Buttons
This section describes how to mount a 1U PXE device using
L-brackets and two buttons.
To mount 1U models using L-brackets and two
buttons:
1.
Align the two edge slots of the L-bracket with the two
screw holes on the top of the PXE device.
2.
Screw the L-bracket to the device and ensure the bracket
is fastened securely.
3.
Repeat Steps 1 to 2 to screw another L-bracket to the
bottom of the device.
4.
After both L-brackets are installed, you can choose either
of the following ways to mount the device in the rack.
Using rack screws, fasten the device to the rack
through two identical holes near the edge of each
L-bracket.
Mount the device by screwing a mounting button in the
back center of each L-bracket and then having both
buttons engage the mounting holes in the rack. The
recommended torque for the button is 1.96 N·m (20
kgf·cm).
Mounting Zero U Models Using Buttons
1.
Turn to the rear of the PDU.
2.
Locate the two screw holes on the rear panel.
3.
Screw a button in each screw hole. The recommended
torque for the button is 1.96 N·m (20 kgf·cm).
4.
Press the PDU forward, pushing the mounting buttons
through the mounting holes, then letting the PDU drop
slightly.
Mounting Zero U Models Using L-Brackets and
Buttons
1.
Fasten the L-bracket to each end of the PDU.
2.
Choose either of the following ways to fasten the PDU to
the rack.
Attach the rack screws to the two rackmount holes of
each L-bracket.
Screw a mounting button in the back center of each
L-bracket and then have both buttons engage the
mounting holes in the rack. The recommended torque
for the button is 1.96 N·m (20 kgf·cm).
QS Rule
Connecting the PXE to a Power Source
The distance between a PDU and its power source must be
SHORTER than the PDU's line cord to avoid stretching out the
cord. A locking connector used at the power source is highly
recommended for a secure connection.
To connect a PDU to the power source:
1.
Verify that all circuit breakers on the PXE are set to ON. If
not, turn them ON.
Or make sure that all fuses are inserted and seated
properly. If there are any fuse covers, ensure that they
are closed.