Raritan PX3TS Quick Setup Manual Download Page 2

 

PX3TS Transfer Switch Quick Setup Guide 

2

QSG-PX3TS-0A-v2.6-E 

 255-80-0032-00 RoHS 

 

2.  Adjust slide-rail assemblies to match your rack posts and 

fasten them to the rack using your own fasteners. 

 

3.  Line up the mounting brackets with slide-rails and push this 

product into rails. 

 

4.  Fasten the front mounting ears to the rack using your own 

fasteners. 

 

 

QS Rule 

 

Inlet and Outlet Power Connections 

The PX3TS connects to two different, but identically rated, 
branch circuits. 

The PX3TS will operate when the branch circuit voltages are 
out of phase, but works most reliably and fastest when in 
phase. The front panel Phase Sync lamp lights if inlets are out 
of phase. 

 

Connecting Power and Equipment 

Your PX3TS may have fuses or circuit breakers. Verify that all 
are firmly seated or set to ON before connecting power. 

The PX3TS inlets are labeled INLET 1 (I1) and INLET 2 (I2). 
INLET 1 is the factory default preferred inlet. 

 

To make power connections: 

1.  Connect PX3TS inlets to branch circuits. 
2.  Connect loads to PX3TS outlets. 
3.  Apply power to branch circuits. 

 

QS Rule 

 

Front View 

 

1. CONSOLE/MODEM port 
2. USB-B port 
3. ETHERNET port 
4. SENSOR port 
5. USB-A port 
6. FEATURE port 
7. LCD display 
8.  LCD control buttons 
9.  Transfer switch status indicators 
10. Transfer switch alarm indicators 
11. Transfer switch control buttons 

 

QS Rule 

 

Summary of Contents for PX3TS

Page 1: ...ng or disconnecting either inlet plug make sure both sources of power to this product are turned off WARNING Connect this product to an AC power source whose voltage is within the range specified on t...

Page 2: ...reliably and fastest when in phase The front panel Phase Sync lamp lights if inlets are out of phase Connecting Power and Equipment Your PX3TS may have fuses or circuit breakers Verify that all are f...

Page 3: ...ality is not optimal but acceptable Critical red Power is not available or power quality is not acceptable Note See Power Quality Setup on page 5 for how to configure voltage and frequency settings QS...

Page 4: ...mp Meaning Manual Disabled The front panel Manual Transfer button is disabled Phase Sync Inlets are out of phase Fuse Blown fuse Replacement is Bussmann FWC 32A10F or equivalent Internal Failure Inter...

Page 5: ...ccurs 4 Enable disable retransfer when inlets are out of phase 5 Optional Thresholds for inlet phase angle difference reporting Values do not affect phase sync detection or transfers Power Quality Set...

Page 6: ...Windows 1 Make sure the PX3TS is NOT connected to the computer via a USB cable 2 Run dominion serial setup 2 0 exe and follow online instructions to install the driver Note If any Windows security wa...

Page 7: ...ommand SSID network wireless SSID ssid ssid SSID string If necessary configure more wireless parameters shown in the following table To set Use this command BSSID network wireless BSSID bssid bssid AP...

Page 8: ...mask subnet mask IPv4 or IPv6 gateway network version gateway ip address ip address gateway s IP address To set Use this command IPv4 or IPv6 primary DNS server network version primaryDNSServer ip add...

Page 9: ...ific wireless LAN adapters Supported 802 11 network protocols vary according to the wireless LAN adapter being used with the PX3TS See USB Wireless LAN Adapters on page 8 Making a Wireless Connection...

Reviews: