Appendix K: Additional PX3 Information
683
Assumption:
Upper Warning threshold is enabled.
Upper Warning = 20 (degrees Celsius)
Deassertion Hysteresis = 3 (degrees Celsius)
"Deassertion" level = 20-3 = 17 (degrees Celsius)
When the PX3 detects that a temperature sensor's reading drops below
20 degrees Celsius, moving from the "above upper warning" range to the
"normal" range, either of the following may occur:
If the temperature falls between 20 and 17 degrees Celsius, the PX3
does NOT perform the "deassertion" action.
If the temperature drops to 17 degrees Celsius or lower, the PX3
performs the "deassertion" action to announce the end of the "above
upper warning" state.
PDView App for Viewing the PX3
Raritan has developed an app that can turn your iOS or Android mobile
device into a local display for the PX3.
This app is called PDView and it can be downloaded for free.
PDView is especially helpful when your PX3 is not connected to the
network but you need to check the PX3 status, retrieve basic information,
or even change network settings.
Requirements for using PDView:
The PX3 is running firmware version 3.0.0 or later.
If you are using an Android device, it must support USB "On-The-Go"
(OTG).
An appropriate USB cable is required.
For Android, you need an USB OTG adapter cable.
For iOS, use the USB cable shipped with your iOS mobile device.
To install PDView:
1.
Use your mobile device to download the PDView app from the Google
Play or Apple's App Store.
Summary of Contents for PX3-1000 series
Page 5: ......
Page 92: ...Chapter 4 Connecting External Equipment Optional 70...
Page 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Page 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Page 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...