Chapter 4: Using SNMP
351
SNMP Gets and Sets
In addition to sending notifications, the BCM2 is able to receive SNMP get
and set requests from third-party SNMP managers.
•
Get requests are used to retrieve information about the BCM2, such
as the system location, and the current on a specific outlet.
•
Set requests are used to configure a subset of the information, such
as the SNMP system name.
Note: The SNMP system name is the BCM2 device name. When you
change the SNMP system name, the device name shown in the web
interface is also changed.
The BCM2 does NOT support configuring IPv6-related parameters
using the SNMP set requests.
Valid objects for these requests are limited to those found in the SNMP
MIB-II System Group and the custom BCM2 MIB.
The BCM2 MIB
The SNMP MIB file is required for using your BCM2 device with an SNMP
manager. An SNMP MIB file describes the SNMP functions.