14 

Power Meter Quick Setup Guide 
QSG-PMM-0

B

-E 

 255-64-0004-00 

5

Enter a name for the 
circuit. 

6

Select the circuit type: 
One-Phase LN, One-
Phase LL, One-Phase 
LLN, or Three-Phase. 
Circuit type cannot be 
changed later. 

7

Enter the current rating 
of the circuit in Amps. 

8

Enter the rating of the CT 
connected at this circuit 
position in Amps. 

9

Click the Phase or CT# 
to edit the automatic 
labels. 

10

Click Create. 

11

Circuits appear in the list 
with a black bracket 
around the circuit 
positions. 

Summary of Contents for PM Series

Page 1: ...d only for use with 0 33V output current transducers CTs DO NOT USE CURRENT OUTPUT e g 5A CTs ON THIS PRODUCT Failure to follow these instructions can result in overheating and permanent equipment dam...

Page 2: ...wer meter with neutral and earth current monitoring PMB a 96 channel branch circuit monitor that plugs into PMM A PMM PMB monitors a panel board mains and branch circuit PMC power meter controller One...

Page 3: ...ited by plug and ratings are labeled on back on unit Current Measurement Inputs Input Range 0 400mV Input Impedance 10k CT Type Voltage Output 333mV at rated current CT Rated Current 1 1200A Meter Mea...

Page 4: ...Temperature 0 60 C Operating Humidity 5 85 RH Operating Elevation 0 3000m Conformance Safety UL EN 61010 1 EMC EMI EN61326 1 FCC Part 15 Class A Power Meter PMM Connectors and Controls A Voltage measu...

Page 5: ...ctor cable CT 5 connector 6 Multi conductor cable CT 6 connector 7 Multi conductor cable CT 7 connector 8 Multi conductor cable CT 8 connector Power Meter Controller PMC A MODBUS RDU isolated RS 485 B...

Page 6: ...ail Pull white tab here to remove Voltage and Current Measurement Wiring A Protect phase lines with fused disconnects rated for available short circuit current at connection point B All wiring 14 22 A...

Page 7: ...anels White labels for sequentially numbered panels C Multi conductor CT cable Available lengths 3m 10m D Connect labeled end into matching labeled connector All CTs 333mV output DO NOT current output...

Page 8: ...auxiliary AC power source Powering from the voltage measurement inputs minimizes circuitry but the meter may stop functioning if the voltage turns off Powering from an auxiliary single phase circuit i...

Page 9: ...ain wired to a single controller PMC using shielded cat 5 Ethernet cable The wiring order of the modules and controller is not important A All cables shielded Cat 5 each cable 100m max length B Switch...

Page 10: ...ect a cat 5 cable between the PC and PMM network ports 3 Open a browser Enter the URL https pdu local The login page appears If the URL does not resolve use the IP address of the PMC Retrieve the dire...

Page 11: ...from the BCM2 Support page Follow the instructions in the spreadsheet To configure with the product web interface Make a network connection to the product See Login and Configuration on page 10 Follow...

Page 12: ...Ratings are marked on the CT 5 Click OK The configured power meter displays in the dashboard If there are more unconfigured power meters the scan results stay open Configure Panel Mains Circuit 1 In t...

Page 13: ...Ratings are marked on the CT 7 Click OK The configured branch circuit monitor displays in the dashboard Configure Panel Branch Circuits 1 In the dashboard click the BCM to open the pop up menu 2 Click...

Page 14: ...LL One Phase LLN or Three Phase Circuit type cannot be changed later 7 Enter the current rating of the circuit in Amps 8 Enter the rating of the CT connected at this circuit position in Amps 9 Click t...

Page 15: ...ialog opens 3 Double click the reading you want to set thresholds for A new dialog opens on top 4 Select the checkbox for the level and enter the threshold current in amps Click OK This example shows...

Page 16: ...h automatic and manual modes In automatic mode the display scrolls through readings Manual Mode In manual mode you can select readings and settings to view Press or to view the Main Menu To return to...