Raritan EMX Quick Setup Guide
2
QSG-EMX-0I-v2.5.0
255-80-6106-00 RoHS
Mount the device by screwing a mounting button in the
back center of each L-bracket and then having both
buttons engage the mounting holes in the rack. The
recommended torque for the button is 1.96 N·m (20
kgf·cm).
QS R ule
Mounting a 1U EMX Device
Using the appropriate brackets and tools, fasten the 1U EMX
device to the rack or cabinet.
To mount the 1U EMX device:
1. Attach a rackmount bracket to each side of the EMX with
the provided screws.
2. Insert the cable-support bar into rackmount brackets.
3. Secure with the provided end cap screws.
4. Mount the EMX device on the rack by securing the
rackmount brackets' ears to the rack's front rails with your
own screws, bolts, cage nuts, or the like.
QS R ule
Connecting the EMX to a Power Source
If your EMX device is designed to use a cable retention clip,
install the clip before connecting a power cord. A cable
retention clip prevents the connected power cord from coming
loose or falling off.
The use of cable retention clips is highly recommended for
regions with high seismic activities, and environments where
shocks and vibrations are expected.
To connect the EMX device to a power source:
1. Install the cable retention clip by inserting both ends into
the tiny holes on two hexagon screws adjacent to the
power socket.