TROUBLESHOOTING

WARNING:  

After the Tablet Dispenser has had water added, it contains a very strong halogen solu

-

tion.  Always wear protective gloves and ventilate well to work on tablet dispenser.  Before doing any  

maintenance or repairs, follow WINTERIZING/STORAGE procedures . 

CAUTION:  

Tablet Dispenser may be under pressure. Open lid slowly to relieve pressure.

TROUBLESHOOTING

No water to tablet dispenser

• Control malfunction

 

Check voltage from control to water solenoid  

 

valve

Press fill button and check voltage on the  

 

terminal for water solenoid

• Clogged line, check valve or fitting

 

Check for clog between Water valve and Tablet  

 

Dispenser. Clean or replace clogged part. Check  

 

valve is located inside the fitting 41-151A (#24).

• Empty time not programmed correctly

 

If Drain Manifold and Air Pump is energized too 

short to fill the Tablet Dispenser, re programming 

is needed. See  page   11.

Overflow or water level too high in dispenser

• Clogged discharge fitting in tablet dispenser

 

Press empty button to run air pump and clear any  

 

clog.

• Clogged Check valve (treatment tank adapter)

 

Clean or replace check valve (41-170) located   

 

on the tank 

• Water fill time not programmed correctly

 

If Water Valve is energized too long it will overfill 

the dispenser, re programming is needed. See  

page 11.

• Air pump malfunction:

 

Press empty button and check voltage on the air  

 

pump terminals. Check the pressure of air pump  

 

(should be at least 5 PSI). Check valve for air  

 

pump is located inside the fitting 41-151B(#29).

• Float sensor malfunction:

 

If  error LED indicates water level high and actual  

 

water level is not high , check float sensor for  

 

proper operation.

Nothing happens when button is pushed

• Fuses blown

 

Check fuse on circuit board

• Water level is too high

 

If water level is high , start and fill  button a are  

 

 disabled. Empty button will continue to function.

• Cable connection:

 

Check if cable for switch panel is corroded or  

 

loose.

See exploded part view for location of parts

Error LED

START BUTTON

CAUSE

On 

Does not work

Motor fuse  blown

Slow flashing

Works

Tablets need refill

Fast flashing

Does not work

Dispenser overfilled

Error LED 

L519 _0919jlc 

Summary of Contents for 21SRP1512

Page 1: ...o personnel that may result from improper installation or operation of this product WARNING HAZARD OF SHOCK AND FIRE Always use recommended fuse or circuit breaker and wire size WARNING HAZARD OF FLOO...

Page 2: ...lding tank is above the LOW LEVEL treatment cycle starts Macerator pump is activated and moves approximately 1 gallon of waste from the holding tank to the treatment tank Treatment cycles runs for 2 m...

Page 3: ...level 3 If cycle completes normal there is a 8 second pause before next cycle will start During this pause none of the buttons except No Discharge mode button is functional MAINTENANCE CAUTION Do not...

Page 4: ...nstructions in the Owner s Manual for that particular toilet Recommissioning IMPORTANT Do not open shut off valve feeding control module until Treatment Tank is full Do not operate PURASAN EX until Tr...

Page 5: ...er Size with macerator pump Fuse Specifications 3 1 4 8 3 cm 4 3 4 12 cm SWITCH PANEL DIMENSIONS Depth 8 22 3cm Width 16 40 6cm TREATMENT UNIT DIMENSIONS Height 13 34 3cm TABLET DISPENSER DIMENSIONS F...

Page 6: ...ubing 6 3 8 ID tubing For Treatment unit 6 3 8 ID tubing Switch Panel Switch Panel Gasket Tablet Dispenser Inside the module Drain Manifold Water Valve SPC control box 6 black and orange wire to conne...

Page 7: ...e wall FIG 6 Switch Panel Cable Supplied is 16 feet 1 Locate in head compartment where indicator lights will be visible 2 Using base plate mark the cutout for the panel See FIG 7 3 Route cable between...

Page 8: ...FE tape or nonpermanent thread sealing compound on threaded PVC fittings and connections Avoid low areas in hose that would allow untreated waste to collect 1 Connect discharge of macerator to one int...

Page 9: ...odule Using cable clamp secure cable on the wall near dispenser 2 Connect sensor cable to control module SPC Note Complete programming for Fill and Empty timing before connecting shutoff valve key swi...

Page 10: ...PTIONAL SensaLevelTM BLACK WHITE OR RED BLACK WATER SOLENOID AIR PUMP DRAIN MAINIFOLD NEG POS 3 AMP FUSE TO POS TERMINAL BLACK 12AWG RED 12AWG BLUE BLACK RED CABLE CABLE RED 86 30 87 85 FUSE 25 AMP 12...

Page 11: ...you have left program mode Macerator Pump FIG 11 FILL EMPTY ERROR Treatment PROGRAMMING After hold time air pump and drain valve will drain solution Make sure that water is drained from entire tube u...

Page 12: ...1 22 57 48 47 46 45 44 43 40 41 70 71 80 81 85 84 86 82 83 72 27 39 37 38 36 32 54 53 36 31 30 58 41 137W 221351W 12V 221352W 24V 41 100AW 162000WA SPC 59 66 64 67 68 69 28 29 24 33 34 35 50 55 65 L51...

Page 13: ...seal 34 41 138 B Plunger 35 41 138A Washer for plunger 36 F204 6 32 x 3 8 Flat head mach screw 4 37 LWS Spring 38 F203 Washer 5 16 x 3 4 39 F233 Spring Roll Pin 50 41 187 Shaft Boot 53 41 152 Base Pla...

Page 14: ...QUENCE Note Fill time and Empty times are programmable Total treatment time is 120 seconds FILL CYCLE HOLD CYCLE EMPTY CYCLE DRAIN MANIFOLD PORTS Fig13 Water in Fill Air in Air to disp Empty To tank C...

Page 15: ...tablet dispenser Press empty button to run air pump and clear any clog Clogged Check valve treatment tank adapter Clean or replace check valve 41 170 located on the tank Water fill time not programme...

Page 16: ...HER PERSONS FOR ANY SPECIAL OR CONSE QUENTIALDAMAGES WHETHERARISING OUT OF BREACH OF WARRANTY BREACH OF CONTRACT OR OTHERWISE SOME STATES DO NOTALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSE...

Reviews: