OM-8000 & 9000W SERIES PREP TABLES

INSTALLATION

CAUTION:  THIS UNIT CONTAINS R290 FLAMMABLE REFRIGERANT.  USE CAUTION 

WHEN HANDLING MOVING AND USE OF THE REFRIGERATOR OR FREEZER.  

AVOID DAMAGING THE REFRIGERANT TUBING OR INCREASE THE RISK OF A 

LEAK. 

WARNING:  FAILURE TO FOLLOW INSTALLATION GUIDELINES AND 

RECOMMENDATIONS MAY VOID THE WARRANTY ON YOUR UNIT.

WARNING:  IT IS IMPORTANT THAT YOUR UNIT HAS ITS OWN DEDICATED LINE. 

CONDENSING UNITS ARE DESIGNED TO OPERATE WITH A VOLTAGE 

FLUCTUATION OF PLUS OR MINUS 10% OF THE VOLTAGE INDICATED ON 

THE UNIT DATA TAG. BURN OUT OF A CONDENSING UNIT DUE TO EXCEEDING 

VOLTAGE LIMITS WILL VOID THE WARRANTY.

 

THE DANFOSS CONTROLLER HAS LOW VOLTAGE PROTECTION AND WILL 

NOT OUTPUT VOLTAGE TO THE COMPRESSOR IF VOLTAGE IS LESS THAN 
104V.

WARNING:  IT IS IMPORTANT THAT A VOLTAGE READING BE MADE AT THE COMPRESSOR 

MOTOR ELECTRICAL CONNECTIONS, WHILE THE UNIT IS IN OPERATION 

TO VERIFY THE CORRECT VOLTAGE REQUIRED BY THE COMPRESSOR IS 

BEING SUPPLIED.  LOW OR HIGH VOLTAGE CAN DETRIMENTALLY AFFECT 
OPERATION AND THEREBY VOID ITS WARRANTY.

WARNING:  EVAPORATOR FANS RUN CONTINUOUSLY WHILE THE BASE IS POWERED 

ON.

WARNING:  THIS UNIT IS INTENDED FOR USE IN LABORATORIES IN COMMERCIAL, 

INDUSTRIAL, OR INSTITUTIONAL OCCUPANCIES AS DEFINED IN THE 

SAFETY STANDARD FOR REFRIGERATION SYSTEMS, ASHRAE 15. 

SELECTING A LOCATION FOR YOUR NEW UNIT

The following conditions should be considered when selecting a location for 
your unit:
1. 

Floor Load: 

 The area on which the unit will rest must be level, free of vibration, 

and suitably strong enough to support the combined weights of the unit plus 
the maximum product load weight. All casters must be in contact with the floor 
to support the weight. Casters may require shims in order for the caster to be 
in contact with the floor. NOTE:  If there is a question pertaining to weight load 
limits, consult the factory at 1-888-994-7636.

2. 

Clearances:

  Unit shall have a clearance of 0 inches at the top, 0 inches at 

the rear and 0 inches at each side.

3. 

Ventilation:

  The air cooled self contained unit requires a sufficient amount 

of cool clean air.  Avoid surrounding your unit around other heat generating 
equipment and out of direct sunlight.  Also, avoid locating in an unheated 

room or where the room temperature may drop below 70° F (21°C) or above 
86°F (32°C). Do not place any object that can block the ventilation exhaust 
from the machine compartment register.

INSTALLATION CHECKLIST

After the final location has been determined, refer to the following checklist prior 
to start-up:
1.  Check all exposed refrigeration lines to ensure that they are not kinked, 

dented, or rubbing together or rubbing against any steel.

2.  Check all visible components for any potential damage.
3.  Check that the condenser and evaporator fans rotate freely without striking 

any stationary members.

4.  Unit must be property leveled; Check all legs or casters ensure they all are 

in contact with the floor while maintaining a level work surface.  Adjusting 
bullet feet height or shimming casters may be necessary if the floor is not 
level.  NOTE:  Damage to equipment may result if not followed.  Unified 
Brands is not responsible for damage to equipment if improperly installed.

5.  Plug unit into power source.  Unit will come on.  If unit does not turn on, refer 

to controller operation section of this manual to manually turn on the unit.

6.  Allow unit time to cool down to holding temperature. If temperature 

adjustments are required, the control is located on the front panel.  Confirm 
that the units is holding the desired temperature.

7.  If unit has drawers, check drawer to ensure the drawer slides freely and fully 

extents along with seating in the cabinet properly when closed.

8.  Refer to the front of this manual for serial number location.  Please record 

this information in your manual on page 1 now.  It will be necessary when 
ordering replacement parts or requesting warranty service.

9.  Allow your unit to operate for approximately 45 minutes before putting in 

food in the rail.  Allow 2 hours for base of the unit to cool down to storage 
temperature, prior to loading product. NOTE:  All motors are oiled and sealed.

ELECTRICAL SUPPLY

The wiring should be done by a qualified electrician in accordance with local 
electrical codes.  A properly wired and grounded outlet will assure proper 
operation.  Please consult the data tag attached to the compressor to ascertain 
the correct electrical requirements.  Supply voltage and amperage requirements 
are located on the serial number tag located on the rear interior wall. 

IMPORTANT - READ FIRST - IMPORTANT

INTERIOR EVAPORATOR COVER

EXTERIOR OF UNIT

RISK OF FIRE OR EXPLOSION. 

FLAMMABLE REFRIGERANT USED. 

DO NOT USE MECHANICAL DEVICES 

TO DEFROST REFRIGERATOR. DO NOT 

PUNCTURE REFRIGERANT TUBING.

RIESGO DE INCENDIO O EXPLOSIÓN. REFRIGERANTE INFLAMABLE UTILIZADO. NO 

UTILICE DISPOSITIVOS MECÁNICOS PARA DESCONGELAR EL REFRIGERADOR. NO 

PERFORE LA TUBERÍA DEL REFRIGERANTE.

RISQUE D’INCENDIE OU 

D’EXPLOSION. 

INFLAMMABLE 

RÉFRIGÉRANT UTILISÉ. 

NE PAS UTILISER DE 

DISPOSITIFS 

MÉCANIQUES POUR 

DÉGIVRER LE 

RÉFRIGÉRATEUR. NE 

FAIRE AUCUN TUBE 

RÉFRIGÉRANT DE 

PONCTION.

DANGER

SB6.1.2

WARNING          ALERTE

CAUTION ATTENTIÓN

DO NOT REMOVE PANEL - HIGH VOLTAGE -

QUALIFIED PERSONNEL ONLY

NE PAS RETIRE LE PANNEAU - HAUTE TENSION -

PERSONNEL QUALIFIÉ SEULEMENT

NO RETIRE EL PANEL - ALTA TENSIÓN - 

CALIFICADO PERSONAL

MOVING PARTS, DO NOT OPERATE 

WITH COVER REMOVED

PIÉCES MOBILES NE PAS FAIRE 

FONCTIONNER SANS COUVERCLE

LAS PIEZAS DE MOVIMIENTO NO FUNCIONAN 

CON LA CUBIERTA RETIRADA

PP LBL1701 REV B

LABEL DIMENSION:  9 in x 3.25 in 

RISK OF FIRE OR EXPLOSION. 

DISPOSE OF PROPERLY IN 

ACCORDANCE WITH FEDERAL OR 

LOCAL REGULATIONS. 

FLAMMABLE REFRIGERANT USED.

PRECAUCIÓN 

RIESGO DE INCENDIO O EXPLOSIÓN. DESÉCHELO ADECUADAMENTE CONFORME 

A REGLAMENTOS FEDERALES O LOCALES. REFRIGERANTE INFLAMABLE UTILIZADO.

MISE EN GARDE

 RISQUE 

D’INCENDIE OU 

D’EXPLOSION. ÉLIMINER 

(or DISPOSER) 

CORRECTEMENT 

CONFORMÉMENT AUX 

RÉGLEMENTATIONS 

FÉDÉRALES OU LOCALES. 

RÉFRIGÉRANT 

INFLAMMABLE UTILISÉ.

SB6.1.4 

LABEL DIMENSION:  6 in x 2.75 in 

PP LBL1704 REV B

CAUTION

RISK OF FIRE OR EXPLOSION DUE TO 

PUNCTURE OF REFRIGERANT TUBING; FOLLOW 

HANDLING INSTRUCTIONS CAREFULLY. 

FLAMMABLE REFRIGERANT USED.

PRECAUCIÓN 

RIESGO DE INCENDIO O EXPLOSIÓN DEBIDO A LA PERFORACIÓN DE LA TUBERÍA DE 

REFRIGERANTE; SIGA CUIDADOSAMENTE LAS INSTRUCCIONES DE MANEJO. REFRIGERANTE 

INFLAMABLE UTILIZADO.

MISE EN GARDE

 RISQUE 

D’INCENDIE OU 

D’EXPLOSION EN RAISON 

DE LA PERFORATION DU 

TUBE RÉFRIGÉRANT; 

SUIVEZ ATTENTIVEMENT 

LES INSTRUCTIONS DE 

MANIPULATION. 

RÉFRIGÉRANT 

INFLAMMABLE UTILISÉ.

CAUTION

SB6.1.5

PP LBL1705 REV B

LABEL DIMENSION:  6.25 in x 2.8 in 

RISK OF FIRE OR EXPLOSION. FLAMMABLE 

REFRIGERANT USED. CONSULT REPAIR MANUAL 

/ OWNER’S GUIDE BEFORE ATTEMPTING TO 

INSTALL OR SERVICE THIS PRODUCT. ALL 

SAFETY PRECAUTIONS MUST BE FOLLOWED. 

PRECAUCIÓN 

RIESGO DE INCENDIO O EXPLOSIÓN. REFRIGERANTE INFLAMABLE UTILIZADO. CONSULTE EL MANUAL DE REPARACIÓN / 

MANUAL DEL USUARIO ANTES DE INSTALAR O REPARAR ESTE PRODUCTO. DEBEN SEGUIRSE LAS PRECAUCIONES DE SEGURIDAD.

MISE EN GARDE 

RISQUE 

D’INCENDIE OU 

D’EXPLOSION. RÉFRIGÉRANT 

INFLAMMABLE UTILISÉ. 

CONSULTER LE MANUEL DE 

RÉPARATION / GUIDE DE 

L’UTILISATEUR AVANT 

D’ESSAYER D’INSTALLER OU 

DE RÉPARER CE PRODUIT. 

TOUTES LES PRÉCAUTIONS 

DOIVENT ÊTRE RESPECTÉES.

SB6.1.3.b 

PP LBL1703 REVB

LABEL DIMENSION:  7.5 in x  5.36 in

SB6.1.3.a 

RISK OF FIRE OR EXPLOSION. FLAMMABLE 

REFRIGERANT USED. TO BE REPAIRED ONLY 

BY TRAINED SERVICE PERSONNEL. DO NOT 

PUNCTURE REFRIGERANT TUBING.

PELIGRO 

RIESGO DE INCENDIO O EXPLOSIÓN. REFRIGERANTE INFLAMABLE UTILIZADO. DEBE SER REPARADO 

SOLAMENTE POR PERSONAL DE SERVICIO CAPACITADO. NO PERFORE LA TUBERÍA DEL REFRIGERANTE.

DANGER 

RISQUE 

D’INCENDIE OU 

D’EXPLOSION. 

RÉFRIGÉRANT 

INFLAMMABLE UTILISÉ. 

POUR ÊTRE RÉPARÉ QUE 

PAR UN TECHNICIEN 

QUALIFIÉ. NE PAS 

PERFORER LE TUBE 

RÉFRIGÉRANT.

CAUTION

DANGER

NEAR EXPOSED REFRIGERANT TUBING

NEAR MACHINE COMPARTMENT AND NAMEPLATE

Summary of Contents for 9000W-290 Series

Page 1: ...estions 888 994 7636 RETAIN THIS MANUAL FOR FUTURE REFERENCE NOTICE Due to a continuous program of product improvement Unified Brands reserves the right to make changes in design and specifications wi...

Page 2: ...necessary when ordering replacement parts or requesting warranty service 9 Allow your unit to operate for approximately 45 minutes before putting in food in the rail Allow 2 hours for base of the unit...

Page 3: ...MAKE CHANGES OF 2 DEGREE INCREMENTS AT A TIME ALLOW FOR THE UNIT TO OPERATE 24 HOURS BETWEEN ADJUSTMENTS IF THE 2 DEGREE ADJUSTMENT IS NOT ENOUGH ANOTHER ADJUSTMENT CAN BE MADE IF THE SETTINGS NEED TO...

Page 4: ...a monthly basis Condenser coils are a critical component in the life of the compressor and must remain clean to assure proper air flow and heat transfer Failure to maintain this heat transfer will af...

Page 5: ...at the end of this manual When in doubt turn unit off and contact service at 888 994 7636 or tsrandell unifiedbrands net SYMPTOM POSSIBLE CAUSE PROCEDURE Unit does not run No power to unit Plug in uni...

Page 6: ...ND REPAIR Leak check an R 290 system the same way you would an R 134a or R 404A system with the following exceptions 1 Do not use a Halid leak detector on a R290 system 2 Electronic leak detector must...

Page 7: ...MED RAIL DBL COMP SYSM X X X X X 1 RP CNT1806 CONTOLLER PROGRAMMED BASE SGL COMPR SYSM X X X X X X X 1 RP CNT1807 CONTOLLER PROGRAMMED BASE DBL COMP SYSM X X X X 2 RF CNT1602 SENSOR COIL X X X X X X X...

Page 8: ...UNIT X X X X X 5A RP SHD1806 SHROUD COND UNIT X 5B RP SHD1807 SHROUD COND UNIT X X X 5C RP SHD1808 SHROUD COND UNIT X 6 RP PNL1803 COVER ACCCESS SIDE CMPR L OR R X X X X 7 HD SHL180 SHELF 22 X 25 X X...

Page 9: ...MAGNET X X X 4 HD BMP034 BUMPER RUBBER X X X 5 RP SHD1814 SHROUD COND UNIT X 5A RP SHD1815 SHROUD COND UNIT X 5B RP SHD1816 SHROUD COND UNIT X 6 HD SHL160 SHELF 19 X 25 X X 6A HD SHL180 SHELF 22 X 25...

Page 10: ...REPLACEMENT PARTS 888 994 7636 8148N 290 8260N 290 8268N 290 8383N 290 8395N 290 84111N 290 8148W 290 8268W 290 8395W 290 ITEM SERVICE PART DESCRIPTION 1 RP FAN1801 FAN ASSIST ASSY X X X 2 RF FAN1401...

Page 11: ...F FAN1401 CONDENSER FAN X X X X X X X X 5 RF FAN0703 FAN GUARD X X X X X X X X 6 RF FLT251 FILTER DRIER 1 4 DBL INLET X X X X X X X X 7 RP BRK1720 MOUNTING CLIP FILTER DRIER T07 1167 X X X X X X X X 8...

Page 12: ...X X 2 RF CMP1604SC COMPRESSOR START COMPONENTS X X X X 3 RP CAP1802 CAP TUBE RAIL X X X X 4 RF FAN0601 CONDENSER FAN X X X X 5 HD GRD1610 FAN GUARD X X X X 6 RF FLT251 FILTER DRIER 1 4 DBL INLET X X...

Page 13: ...X X X X X X 2 RP CAP1804 CAP TUBE BASE X X X X 2A RP CAP1803 CAP TUBE BASE X X X X X 3 RF FAN1401 FAN EVAPORATORS X X X X X X X X X 4 RP DRP107 EVAPORATOR DRAIN PAN X X X X X X X X X 5 RP PNL107 290 S...

Page 14: ...RF COI107 EVAPORATOR COIL X X X 2 RP CAP1803 CAP TUBE BASE X X X 3 RF FAN1401 FAN EVAPORATORS X X X 4 RP DRP107 EVAPORATOR DRAIN PAN X X X 5 RP PNL107 290 SIDE COIL 8000N COMMON X X X 6 RP PNL108 290...

Page 15: ...X X 2 IN GSK9902 GASKET 18 5 X 24 5 PUSH IN X X 2A IN GSK1025 GASKET 21 75 X 24 5 PUSH IN X X X 2B IN GSK1030 GASKET 24 5 X 24 5 PUSH IN X X X X X 3 HD HDL0103 DOOR HANDLE recessed X X X X X X X X X 4...

Page 16: ...7 X X 2 IN GSK1025 GASKET 21 75 X 24 5 PUSH IN X 2A IN GSK1030 GASKET 24 5 X 24 5 PUSH IN X X 3 HD HDL0103 DOOR HANDLE recessed X X X 4 RP HNG9900 HINGE ASSY UNIVERSAL LEFT RIGHT X X X 4A RP HNG026 HI...

Page 17: ...WER CARTRIDGE 24 X X X 2B RP MOD029A DRAWER CARTRIDGE 27 X X X X X 3 RF FRT9903 DRAWER FRONT 21 X X 3A RF FRT9904 DRAWER FRONT 24 X X X 3B RF FRT9905 DRAWER FRONT 27 X X X X X 4 RP FRM0301 DRAWER FRAM...

Page 18: ...R HANDLE X X X 4 RP TRK05SM DRAWER TRACKS 1L 1R X X X 5 IN GSK1042 DRAWER GASKET 24 Top X 5A IN GSK1043 DRAWER GASKET 24 Bottom X 5B IN GSK1048 DRAWER GASKET 27 Top X X 5C IN GSK1047 DRAWER GASKET 27...

Page 19: ...SCRIPTION 1 PB VLV1803 BALL VALVE 1 1 2 PVC FAMALE X X X X X X X X X X X X 2 PB TBG1801 TUBING 1 VINYL BLACK X X X X X X X X X X X X 3 HD CLM1801 CLAMP 1 OETIKER X X X X X X X X X X X X 4 HD CLP1801 C...

Page 20: ...INSERT THREADED SOUTCHO X X X X X X 3 HD PIN001 PIN KEY PAN RAIL X X X X X X 4 RP DSN001 DRAIN SCREEN 2 X X X X X X 5 RP HNG006 HINGE PAN COVER SET OF 2 X X X X X X 6 HD PIN0101 PIN LOCATING 0 875 LEN...

Page 21: ...HOD0310 HOOD COVER X 1G RP HOD1803 HOOD COVER X 1H HP HOD0609 HOOD COVER X 2 HD ROD100 HOOD COVER ROD W SINGLE BEND X X X X X 2A HD ROD200 HOOD COVER ROD W DOUBLE BEND X X 3 HD PIN107 PIN THREADED SO...

Page 22: ...22 OM 8000 9000W SERIES PREP TABLES Wiring Diagram 8000 290 SINGLE COMPRESSOR...

Page 23: ...23 OM 8000 9000W SERIES PREP TABLES Wiring Diagram 8000 290 DOUBLE COMPRESSOR...

Page 24: ...24 OM 8000 9000W SERIES PREP TABLES Wiring Diagram 9000W 290...

Page 25: ...25 OM 8000 9000W SERIES PREP TABLES Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Reviews:

Related manuals for 9000W-290 Series