Typical Scenarios

WES3 Water Interface

Scenario One

I20 1 has a WES Water Cable Sensor fitted to the input of the device. This is 

configured to monitor the pipework in a plant room while refurbishment work 
takes place. This is located a couple of hundred metres away from the main 

shut-off valve. Nothing is attached to the output.

I20 2 is deployed next to the shut-off valve. Nothing is attached to the input 
but the output is connected to the shut-off valve. In this scenario the water 
is detected by I20 2 which triggers the input and raises a “WTR” alert on the 

WES3 network.

This triggers the output on all Water I20’s (in this instance I20 2 only. This then 
shuts off the valve via I20 2. A “WTR” alert is triggered on the WES3 Connect 

and (where used) the REACT cloud and mobile application.

WATE

R INTERFA

CE

W

ATE

R DETECTION C

AB

LE

CONNECT

WATER

INTERFA

CE

VALVE

Scenario Two

I20 1 has a WES Water Cable Sensor fitted to the input of the 
device. The shut-off valve in this case is co-located within the 
plant room so the output from I20 1 is connected directly to this, 
i.e. both the input and output are connected.

I20 2 is deployed next to an adjacent shut-off valve. Nothing is 
attached to the input,  the output is connected to the shut-off 
valve. In this scenario the water is detected by I20 1 which triggers 
the input and raises a “WTR” alert on the WES3 network.

This triggers the output on all Water I20’s (in this instance I20 2 

and also the valve connected to I20 1.  Both valves are therefore 
shut off. A “WTR” alarm is triggered on the WES3 Connect and 
(where used) the REACT cloud and mobile application.

WATE

R INTERFA

CE

W

ATE

R DETECTION C

AB

LE

CONNECT

WATER

INTERFA

CE

VALVE

VALVE

WATE

R INTERFA

CE

W

ATE

R DETECTION C

AB

LE

CONNECT

WATER

INTERFA

CE

VALVE

VALVE

WATE

R INTERFA

CE

W

ATE

R DETECTION C

AB

LE

CONNECT

WATER

INTERFA

CE

VALVE

VALVE

Scenario Three

Two separate zones - I20 1 has a WES Water Cable Sensor fitted to the input of the device.  The shut-off valve in this case is co-located within 
the plant room so the output from I20 1 is connected to directly to this, i.e. both input and output are connected.  I20 2 is deployed next to an 

adjacent shut-off valve.  Nothing is attached to the input but the output is connected to the shut-off valve. 

In this scenario the water is detected by 120 1 which triggers the input and raises a “WTR” alert on the WES3 network.  This triggers the output 

on all Water I20’s (in this instance I20 2 and also its own valve at 120 1).  Both valves are therefore shut off.  A “WTR” alarm is triggered at the 
WES3 Connect and (where used) the REACT cloud and mobile application. 

I2O 1

I2O 2

CONNECT

I2O 1

I2O 2

CONNECT

I2O 1

I2O 2

CONNECT

I2O 1

I2O 2

CONNECT

Summary of Contents for WES3

Page 1: ...1 RAMTECHGLOBAL COM WES3 Interface Manual RAMTECHGLOBAL COM...

Page 2: ...l Interface LED Indications WES3 Maintenance Interface LED Indications 4 4 4 4 4 5 6 7 8 9 10 11 12 13 14 15 Device Parameters Dimensions mm HxWxD 235 x 161 x 58 excl Antenna 81mm and USB 15mm Weight...

Page 3: ...3 RAMTECHGLOBAL COM WES3 Interface Range Water Interface Maintenance Interface Medical Interface Standard Interface...

Page 4: ...todiallers WES3 Water Interface The WES3 Water Interface enables water detection devices such as detection cables to be connected to a WES network providing automatic 24 7 monitoring and raise a notif...

Page 5: ...Input The input requires a volt free contact from a relay and should not be connected to power Alarm NOT Triggered Alarm Triggered IN IN IN IN INPUT OUTPUT CONNECTIONS The Interface has two auxiliary...

Page 6: ...wide range of projects be it a new build through to extensive refurbishment projects The Interface is capable of communicating with most commonly used technologies in existing buildings construction...

Page 7: ...laying one of these patterns require further investigation and should not be relied upon as part of the fire alarm and detection system until the fault has been corrected Use the chart at the bottom o...

Page 8: ...st floods or groundwater O Detection of water leaks in drip tray Water detection tape and cable features O Detects liquid along the entire length of the sensing cable O Easy to lay wrap install and se...

Page 9: ...d from sharp or metallic objects to prevent false activation O It is recommended that the cable is securely fixed using suitable fixings available from Ramtech Electronics O If the Water Detection Tap...

Page 10: ...determine the nature of the issue Red LED Three periodic red flashes and one green flash red red red and green indicates the interface unit is latched which means the water cable tape has been activa...

Page 11: ...shut off valve In this scenario the water is detected by I20 1 which triggers the input and raises a WTR alert on the WES3 network This triggers the output on all Water I20 s in this instance I20 2 a...

Page 12: ...installations where offsite notification via REACT is not available e g areas where cellular signal is unavailable In the event of a medical alert being raised from a WES3 call point the output of the...

Page 13: ...page to determine the nature of the issue Red LED The red LED will flash every 4 seconds when the unit has been triggered Flash of both green and amber Note Clearing the medical alert from the WES3 s...

Page 14: ...the fault issue is detected The alert activates the output of the unit and can trigger connected devices such as an autodialler monitoring system or Building Management System BMS These alerts include...

Page 15: ...nits displaying one of these patterns require further investigation and should not be relied upon as part of the fire alarm and detection system until the fault has been corrected Use the chart at the...

Page 16: ...hglobal com WES units may be operated in these countries Contact Us Ramtech Customer Support Technical advice is available over the phone by contacting Ramtech Customer Support and site visits can be...

Reviews: