TERMINAL STRIP CONNECTIONS 

Terminal #  1 - COMMON: 

Low voltage common. 

Terminal# 2 -REV  LOOP: 

Stops the gate from  closing.  If the gate is open, 

it  holds  the gate open.  If the gate  is closing,  it 

stops and reopens the gate.  If the gate is closed, 

the gate will remain closed.  The function can be 

altered  with  Dip  Switch  "C"  4  (see  "Dip  Switch 

Configuration").  Used with loop detectors, photo 

eyes, safety edges ... etc.  Becomes active with a 

closed contact to common. 

Terminal # 3 - CLOSE: 

Closes the gate.  Used with three button stations 

or  pushbuttons.  Becomes  active  with  a closed 

contact to common. 

Terminal # 4 - FIREBOX: 

Opens the gate.  Used with fire department key 

switches & controls.  Opens with closed contact 

to  common.  Closes  immediately  when  closed 

contact on common is removed. 

Terminal 

# 5 -

EXIT: 

Opens the gate.  Used with loop detectors, photo 

eyes,  keypads,  phone entry systems, three-but­

ton stations ... etc.  Becomes active with a closed 

contact to common. 

Terminal# 6-PHANTOM: 

Keeps the gate open when the open limit switch 

is activated.  Used with loop detectors. Becomes 

active with a closed contact to common. 

Terminal 

-

RADIO: 

Operation depends on dip switch "C" 3 (See "Dip 

Switch Configuration").  Used with an  RF receiver 

or  pushbutton.  Becomes  active with  a  closed 

contact to common. 

Terminal # 8 -EDGE: 

When  triggered  the  gate  will  stop.  The  gate 

will remain stopped until the detector is cleared. 

Once  the  detector  is  cleared,  the  operator  will 

resume  normal  operation.  If  triggered  twice 

before  reaching  a  limit  switch,  the  alarm  will 

sound for 6 minutes and the control board will not 

RAMSET 

accept any commands.  After  the 6 minutes the 

24  VDC  is  removed from the alarm connection 

and the board resets to normal operation. 

Terminal#  9 and  10  - LIMIT  1 & LIMIT 2: 

Direction depends on Dip Switch "C" 7 (See "Dip 

Switch  Configuration").  Stops  the  motor  from 

moving in one direction.  These wires are preset 

in  factory  and  should  not  be  moved.  Becomes 

active with a closed contact to common. 

Terminal#  11 and  12 -COMMON: 

Low voltage common. 

Terminal#  13 - +24 VAC: 

Provides 24 VAC for peripheral accessories. 

Terminal#  14 and  15- MAG(-) & MAG(+): 

Supplies 24  VDC to a  Magnetic  Lock  when  the 

gate is closing  or closed.  If  gate  is opening or 

opened, then no power is  supplied.  Leave open 

if not used. 

Terminal#  16 - M  BRAKE: 

Used ONLY on the Ram 50 Operator.  If while the 

gate  is  closed  someone  or  something  tries  to 

manually open  the  gate  without  a  proper  signal 

(keypad, exit loop, radio signal ... ), the motor will 

lock  up  for 6 minutes.  After the 6  minutes,  the 

operator will then secure close the gate. 

Terminal#  17 and  18 -MOTOR 1 & MOTOR  2: 

Supplies power to the motor.  Direction depends 

on Dip Switch "C" 7 (see "Dip Switch Configura­

tion'').  These wires are preset and connected in 

the factory and should not be moved. 

Terminal#  19 and  20 -AC HOT & NEUTRAL: 

110  VAC  or  220  VAC to  power  the  operator. 

Voltage  is  predetermined  at  factory  and  cannot 

be changed by the installer or technician. 

15 

--

www.RamsetStore.com  |  (800) 878-7829  |  [email protected]

Summary of Contents for RAM 300

Page 1: ...www RamsetStore com 800 878 7829 Sales RamsetStore com...

Page 2: ...ence or appropriate WARNING training with gate operators IMPORTANT SAFETY REQUIREMENTS INSTRUCTIONS WARNING To reduce the risk ofinjury 01 death I READ FOLLOWALL INSTRUCTIONS 2 Never let children oper...

Page 3: ...TRIC EYE OR LOOP DETECTOR CHECK THE E R D SENSITIVITY MAKE SURE THAT ALL AREAS AROUND THE GATE ARE SAFE AND SECURE SUCH AS THE FRONT REAR AND TRAVEL AREA COMMUNICATE WITH THE END USER INSTRUCT THE END...

Page 4: ...ate the controls Outdoor or easily accessible controls shall have a security feature to prevent unauthorized use g The stop and or reset button must be located in the line of sight of the gate Activat...

Page 5: ...s vehicular gate operator Class m A vehicular gate operator or system intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to s...

Page 6: ...Lubricated by oil bath gives smooth and quit operation CHASSIS 3 16 hot rolled steel FINISH Gold zinc plated to inhibit corrosion POWER FAILURE RELEASE Exclusive foot pedal release OVERALL DIMENSIONS...

Page 7: ...given in illustration 3 Level top edge of form 4 Set reinforcing bars and wire mesh 5 Allow pad to cure for 48 hours and remove forms Outside Property Inside Property j 0 Gate Closed See Fig 5 6 or8...

Page 8: ...to be tightened to a minimum of 40 lbs above weight of gate in order to avoid slipping lii Miil Gate travel is adjusted by loosening the limit Cams and positioning them until proper gate travel has be...

Page 9: ...ES FROM 14 TO 18 IN LENGTH 8 42 34 OPERATOR PIVOT SHAFTCENTER 50 32 314 76 r h H1hii 32 SHORTARM DIM LONGARMDUA SPACE REQUIRED FOR A STANDARD GATE IN THE OPEN POSITION l i L liH iiil www RamsetStore c...

Page 10: ...PIVOTSHAFTCENTER 24 1 4 44 1 4 24 _ o N GAR M o IM _ MINIMUM SPACE REQUIRED FOR COMPACT INSTALLATION 20 minimum space required between open gate and wall for this compact installation 20 10 lihl Hil...

Page 11: ...rosses loop area Photoelectric Safety Sensor Photo Eye prevents the gate from closing when any object interrupts the beam Outside Property Operator Factory pre set for LH operation __ INSTALL A SAFETY...

Page 12: ...sing this button will cause the gate to stop moving Closing Pressing this button will cause the gate to close Reset E R o Board Push all three pushbuttons for approximately 5 seconds All three L E D s...

Page 13: ...slave gates that work together should be set lo the same Dip Switch A 4 112 HP E R D address Side gates use the address setup Sw 4 5 Function Sw Function OFF Most sensitive ON Setting for stronger E R...

Page 14: ...ommand and reverse with a second command Dip Switch c 4 ONE PASS Sw Function OFF Normal Operation fully opens and closes ON One pass mode The gate will open until the reversing IOOP is initially activ...

Page 15: ...flector Safety Sensor Photo Eye Rev Loop P Safety Sensor Reflector Photo Eye for Backplane Radio Terminal Slrlp Electric Motor 120VAC or 220VAC hihl iiill In order to use COMMON and ST remove jumper 2...

Page 16: ...is cleared the operator will resume normal operation If triggered twice before reaching a limit switch the alarm will sound for 6 minutes and the control board will not RAMSET accept any commands Aft...

Page 17: ...er Stave ___ _ Master Slave Plug Synchronizes movement between two gates 3WYes A B and Common Battery Back up System plug Standard Connections Reven e Loop Fite Box Exit Loop Pnamom L oop Rad o EdgO S...

Page 18: ...Inputs 1 2 Reverse 3 4 Exit 5 6 Phantom Use with ILD 24 Loop wires should be connected to this plug JP4 JP5 JP8 Reverse Exit Phantom Sensor Used with the Ramset ILD 24 plug in loop detector The Loop w...

Page 19: ...25 10 3 6 70 74 71 72 2 69 55 57 63 4 28 26 85 77 79 84 83 81 82 23 75 73 54 5 16 30 29 8 36 37 9 53 35 24 11 12 13 31 34 41 39 32 33 15 15 42 40 14 27 7 76 78 78 84 52 www RamsetStore com 800 878 782...

Page 20: ...0 50 41 Wire Harness Outlet R300 1 19 800 50 90 Wire Harness Foot Pedal R300 1 20 800 51 03 Wire Harness Limit Switches R300 1 21 800 51 22 Wire Harness Radio terminal R300 1 22 800 51 23 Wire Harness...

Page 21: ...75 05 Access Door Assembly 1 56 800 16 00 Access Door Stainless Steel R300 1 57 800 18 00 Key Access Door 313 2 58 800 18 01 Lock Assembly 313 Key 1 59 800 32 40 Screw Machine 6 32 x 3 8 flat 2 60 80...

Page 22: ...on Washer Torque Limited 3 R300 1 80 800 34 22 Set Screw 1 4 20 x 3 8 2 81 800 36 20 Bolt Hex Head 3 8 16 x 1 3 82 800 46 30 Bushing UHMW Sprocket ID 1 3 4 OD 2 R300 1 83 800 58 02 Arbor Nut Torque Li...

Page 23: ...the area of a moving gate 4 All opening devices such as a keypad cardreader should not be installed close to the gate where the gate could possibly cause injury 5 Use warning signs attached on both s...

Page 24: ...e area of a moving gate Use the emergency release only when the gate is not moving Make sure when using the foot releaseorhand crank the circuit breaker for the operator is turned off Have the technic...

Page 25: ...gnetic Lock Battery Back up System Heavy Duty Industrial Uphill Hinges Uphill Arms To be used under uneven conditions Radio Receiver RAMSET LCD KP Liquid Crystal Display Key1 ad RAMSET ILD 24S Plug in...

Reviews: