rako RSR-DLI User Manual Download Page 5

Auto Heal Data 

When programming is complete press this button to store DLI network information. Failure 
to do so will mean in the event of lamp failure the entire DLI network will need to 
re-programmed. 

This button will store the current state of the DLI network within the RSR-DLI.  This means that  if a 
single ballast is removed and replaced the new ballast will have the same short address 
automatically uploaded to it.  If more than one DLI ballast needs to be replaced the entire network 
must be re-addressed using the “Force Readdress” button. 

Extra features of RSR-DLI 

Swap Channels 

The Swap Channels tile in the DLI setup tab allows for custom readdressing of the DLI short 
addresses themselves. Individual short addresses can be moved on to or swapped with each other 
by using this interface.

 

This will readdress the DLI ballast to the short address as set in each box, “Perform Swap” will 
directly switch the position of the two ballast. “Perform Move” will result in both ballasts having a 
the short address of “DLI Short Address 2”. 

Visible Channels 

Sometimes not all 15 channels in the room will be required by the RSR-DLI (less than 15 
separately controllable sets  of DLI ballasts required). When this is the case then the “Visible 
Channels” tab can be used to reduce the number of channels the RSR-DLI occupies in the 
software. 

 

Slide the “channels used” slider to match the number of Channels required by the RSR-DLI and the 
remaining channels are freed up to be used by other devices. 

 

RSR-DLI 

Manual Version 3.0.3 

Reviews: