rako RAK4-R Instruction Manual Download Page 4

Step 4  

 

Insert the circuit board on to the 
two screw on either side of the 
metalwork.  
 
Do not screw down at this stage 
as the buzz bars need to be 
accessible for Neutral/Earth 
connections of curtain/blind 
circuits.  
 
Connect Live, Neutral, Earth for 
board supply as indicated.  

Step 5  

 

Insert the RJ45 cable from the 
RAK-LINK/RxLink into the port 
on the RAK4-F.  
 
See “Wiring for different motor 
types” for load connections  
 
 

Wiring for different motor types: 

Mains switching  

The RAK4-R is most commonly used with “mains switching blinds”.  The six way terminal 
block is fed with permanent mains and has two switched mains outputs. A three core and 
earth cable should be run from the RAK4-R to the blind.  
 

24V Polarity switching 
 

The RAK4-R can also be used to control 24V polarity switching blinds. In this case a 
separate 24V power supply is required and a two core cable should be run from the RAK4-R 
to the blind.  
 

Contact Closure  
 

The RAK4-R can be used to provide a control signal to the blinds. In this case a 3 core cable 
is run from the RAK4-R to the blind control box.  

RAK4-R

       Manual Version 2.1.4 