If it is found that there is excessive draught in the chimney then either an adjustable flue
damper or alternatively a draught stabiliser should be fitted. The adjustable flue damper
should not close off the flue entirely but should in its closed position leave a minimum
continuous opening free area of at least 20 % of the total cross sectional area of the flue or
fluepipe.
Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping
the chimney and connecting fluepipe.
You should also familiarise yourself with the draught conditions for chimneys with 2 flues.
The flue outlet spigot is 150 mm in diameter.
For strong draughts, the chimney or flue should be fitted with a draught stabiliser. In which
case, it is important to ensure that there is a free flow-through area of minimum 20 cm² when
the regulating gate is shut. Otherwise, the fuel energy may not be used optimally. If, at any
time, you are unsure about the condition of the chimney, you should contact a chimney
sweep.
Remember that access to the access door should be kept clear.
Summary of Contents for RAIS Q-BIC
Page 1: ...ENGLISH RAIS manual for Q BIC Q BIC insert 1 U S E R M A N U A L RAIS Q BIC RAIS Q BIC INSERT...
Page 2: ...We cannot be held responsible for any misprints...
Page 11: ...ENGLISH RAIS manual for Q BIC Q BIC insert 11...
Page 17: ...ENGLISH RAIS manual for Q BIC Q BIC insert 17...
Page 35: ...ENGLISH RAIS manual for Q BIC Q BIC insert 35...
Page 37: ...ENGLISH RAIS manual for Q BIC Q BIC insert 37...
Page 39: ...ENGLISH RAIS manual for Q BIC Q BIC insert 39 6 2 10 4 3 9 1 7 5 8...
Page 40: ...RAIS A S Industrivej 20 DK 9900 Frederikshavn www rais dk...